Manual
11
BURNER SETTINGS TABLES
Table 3: RIELLO 40BF DIRECT VENT PRELIMINARY BURNER SETTINGS
Boiler Model
Head
Type
Inser-
tion
Depth
Firing
Rate
[GPH]
Com-
bustion
Liner
Nozzle
Mfr.
Nozzle
Type
Pump
Pres-
sure
[PSI]
Head
Setting
Air
Setting
Pressure
Switch
Setpoint
Rated
AFUE
Effi ciency
[%]
4075
Reverse 2.75" 0.75
Oval Delavan
0.65x60W 150 3 5.0 0.25" WC 86.0
4095
Standard 1.75" 0.95
Oval Delavan
0.75x90B 175 1 4.0 0.25" WC 85.0
4110
Standard 1.75" 1.10
Oval Delavan
1.00x90B 125 2 5.0 0.25" WC 84.0
5100
Standard 2.75" 1.00
None Delavan
0.75x60B 175 1 5.0 0.80" WC 86.5
5115
Standard 1.75" 1.15
None Delavan
1.00x80B 130 2 5.8 0.80” WC 85.0
5135
Standard 1.75" 1.35
None Delavan
1.20x80B 125 4 5.8 0.80” WC 84.0
6130
Standard 2.75" 1.30
V6 Delavan
1.00x45B 175 2 8.0 0.90" WC 86.5
Timings
Pre-purge 12 seconds
Post-Purge 45 seconds
Boiler
Model
Riello
Oil
Burner
Model
ECR Oil Burner
Part Number
4075 40BF3
240007528
4095 40BF5
240009407
4110 40BF5
240009408
5100 40BF5
240007529
5115 40BF5
240009409
5135 40BF5
240009410
6130 40BF5
240007530