Product specifications
45
PART LOAD INFORMATION
TABLE 19
(1) Performance shown includes compressor(s) and fans per ARI 550/590-98.
(2) EER @ part load step = (% CAP รท % kW) x full load EER from rating tables.
(3) IPLV/NPLV shown on the rating tables per per ARI 550/590-98 at 100, 75, 50 & 25% load.
(4) Consult rating tables for 100% CAP & kW data.
(5) High IPLV (NPLV) / COP ratings provided by special staging of tandem-scroll compressors.
%% % % COP
Step Step Step Step IPLV (IPLV)
English
Metric SI
Capacity Control Steps ( Expressed in %)
ACDS-B
Model
015S %CAP 100 59 -- -- 13.74 4.03
%Kw 100 40 -- --
020S %CAP 100 59 -- -- 13.65 4.0
%Kw 100 41 -- --
025S %CAP 100 59 -- -- 13.62 3.99
%Kw 100 41 -- --
027S %CAP 100 57 -- -- 15.4 4.51
%Kw 100 33 -- --
030S %CAP 100 60 -- -- 14.9 4.37
%Kw 100 38 -- --
025D %CAP 100 78 59 31 13.62 3.99
%Kw 100 71 41 18
030D %CAP 100 79 59 31 13.89 4.07
%Kw 100 69 41 17
035D %CAP 100 78 59 29 13.89 4.07
%Kw 100 66 41 16
040D %CAP 100 78 59 31 15.1 4.43
%Kw 100 63 37 16
045D %CAP 100 82 62 32 15.09 4.42
%Kw 100 67 40 17
050D %CAP 100 78 59 30 15.13 4.43
%Kw 100 61 36 16
055D %CAP 100 81 59 28 15.26 4.47
%Kw 100 63 36 14
057D %CAP 100 81 61 32 14.76 4.33
%Kw 100 67 39 17
060D %CAP 100 81 60 31 14.84 4.35
%Kw 100 67 39 17
065D %CAP 100 78 59 26 14.26 4.18
%Kw 100 63 39 15
070D %CAP 100 80 59 29 13.64 4.0
%Kw 100 67 39 19
080D %CAP 100 79 60 27 13.86 4.06
%Kw 100 64 40 17
090D %CAP 100 80 60 28 13.47 3.95
%Kw 100 66 40 19
100D %CAP 100 80 60 31 14.18 4.16