ELECTRICAL DATA:
ACDS-B Nom. Qty. Wires Wire Qty. Wires Wire
Model Code Volts Per Pole Size Range Per Pole Size Range
NOTE: Single point power is standard for all models ACDSB 015S to ACDSB 100D.
FIELD WIRING (60HZ/3PH)
Supply Voltage
Single Source Power - Wire Size Range and Quantity
60 Hz.
Standard Terminal Block
Optional - Unit Mtd. Disconnect Switch
Ta b l e 1 6 b
AK 208 1 #6 TO 400 MCM 1 #4 TO 350MCM
045D AN 230 1 #6 TO 400 MCM 1 #4 TO 350MCM
AR 460 1 #12 TO 2/0 1 #4 TO 4/0
AS 575 1 #12 TO 2/0 1 #14 TO 1/0
AK 208 1 #6 TO 400 MCM 1 #4 TO 350MCM
050D AN 230 1 #6 TO 400 MCM 1 #4 TO 350MCM
AR 460 1 #12 TO 2/0 1 #4 TO 4/0
AS 575 1 #12 TO 2/0 1 #14 TO 1/0
AK 208 1 #6 TO 400 MCM 1 #4 TO 350MCM
055D AN 230 1 #6 TO 400 MCM 1 #4 TO 350MCM
AR 460 1 #12 TO 2/0 1 #4 TO 4/0
AS 575 1 #12 TO 2/0 1 #4 TO 4/0
AK 208 1 #6 TO 400 MCM 2 3/0 TO 250MCM
057D AN 230 1 #6 TO 400 MCM 2 3/0 TO 250MCM
AR 460 1 #12 TO 2/0 1 #4 TO 4/0
AS 575 1 #12 TO 2/0 1 #4 TO 4/0
AK 208 1 #6 TO 400 MCM 2 3/0 TO 250MCM
060D AN 230 1 #6 TO 400 MCM 2 3/0 TO 250MCM
AR 460 1 #12 TO 2/0 1 #4 TO 4/0
AS 575 1 #12 TO 2/0 1 #4 TO 4/0
CD 208 1 #6 TO 400 MCM 1 2/0 to 600MCM
065D AN 230 1 #6 TO 400 MCM 1 2/0 to 600MCM
AR 460 1 #6 TO 400 MCM 1 #4 TO 350MCM
AS 575 1 #12 TO 2/0 1 #4 TO 4/0
CD 208 1 #4 TO 500 MCM 1 2/0 to 600MCM
070D AN 230 1 #4 TO 500 MCM 1 2/0 to 600MCM
AR 460 1 #6 TO 400 MCM 1 #4 TO 350MCM
AS 575 1 #12 TO 2/0 1 #4 TO 4/0
CD 208 1 #4 TO 500 MCM 1 2/0 to 600MCM
080D AN 230 1 #4 TO 500 MCM 1 2/0 to 600MCM
AR 460 1 #6 TO 400 MCM 1 #4 TO 350MCM
AS 575 1 #12 TO 2/0 1 #4 TO 4/0
CD 208 2 #4 TO 500 MCM 2 2/0 to 600MCM
090D AN 230 2 #4 TO 500 MCM 2 2/0 to 600MCM
AR 460 1 #6 TO 400 MCM 1 #4 TO 350MCM
AS 575 1 #6 TO 400 MCM 1 #4 TO 350MCM
CD 208 2 #4 TO 500 MCM 2 2/0 to 600MCM
100D AN 230 2 #4 TO 500 MCM 2 2/0 to 600MCM
AR 460 1 #6 TO 400 MCM 1 #4 TO 350MCM
AS 575 1 #6 TO 400 MCM 1 #4 TO 350MCM