Product specifications

31
ACDS-B 065D, 070D, 080D, 090D, 100D
PHYSICAL SPECIFICATIONS:
Ta b l e 1 4 d
ENGLISH I.P. & S.I. UNITS
NOTES: (1) CH2 - Oversized cooler required where indicated for 42°F (5.5°C) LWT. NR - Not Required
(2) CH3 - Oversized cooler required where indicated for 4F (4.5°C) LWT. VIC - Victaulic Connections
(3) Units with Low Ambient Option use (1) 1 HP (0.76 kW) in lieu of (1) 1.5 HP (1.15kW) fan motor per circuit
(4) Minimum Starting/Operation Ambient with a maximum of 5 MPH wind across coil & minimum load per Table 1.
(5) Low Ambient Option requires (1) 1 HP (0.76 kW) variable speed fan, motor per circuit.
(6) Extra Low Ambient Option requires electronic expansion valve(s), variable speed fan, 50% glycol, 50% minimum load
and maximum 5 MPH wind across coil and may require additional system modifications. Contact factory..
ACDS-B MODEL 065D 070D 080D 090D 100D
Nominal Capacity in Tons (kW) 65 (235) 70 (240) 80 (280) 90 (300) 100 (350)
Quantity of Compressors 4 4 4 4 4
STANDARD EVAPORATOR CXD1209F09 CXD1209F09 CXD1209F09 CXD1209B07 CXD12120B07
Water Volume, Gallons (Liters) 28 (106) 28 (106) 28 23 (87.1) 30 (1136)
Minimum Flow Rate, GPM (L/S) 112/6.94 112/6.94 112/6.94 140/8.68 188/11.65
Maximum Flow Rate, GPM (L/S) 365/22.63 365/22.63 365/22.63 380/23.56 459/28.45
Water Conn. Size In/Out (Type) 4" VIC 4" VIC 4" VIC 4" VIC 4" VIC
(CH2) OPT. CLR for 42°F (5.5°C) LWT(1) NR NR NR NR NR
Water Volume, Gallons (Liters) NR NR NR NR NR
Minimum Flow Rate, GPM (L/S) NR NR NR NR NR
Maximum Flow Rate, GPM (L/S) NR NR NR NR NR
Water Conn. Size In/Out (Type) NR NR NR NR NR
(CH3) OPT. CLR for 40°F (4.5°C) LWT(2) NR NR NR NR NR
Water Volume, Gallons (Liters) NR NR NR NR NR
Minimum Flow Rate, GPM (L/S) NR NR NR NR NR
Maximum Flow Rate, GPM (L/S) NR NR NR NR NR
Water Conn. Size In/Out (Type) NR NR NR NR NR
CONDENSER L216 L216 L312 L312 L216
Fan Quantity - All 30" (766mm) Diameter 6 6 6 6 8
Motor Quantity(3) (2) 6 (2) 6 (2) 6 (2) 6 (2) 8
Standard Fans - Nominal RPM 1140 1140 1140 1140 1140
Standard Fans - HP (3) (1) 1.5 (1) 1.5 (1) 1.5 (1) 1.5 (1) 1.5
Standard Fans - (kW) (3) (0.76) 1.15 (0.76) 1.15 (0.76) 1.15 (0.76) 1.15 (0.76) 1.15
Opt. Extra Queit Fans - Nominal RPM 855 855 855 855 855
Opt. Extra Quiet Fan Motor - HP (kW) (3) 1.0 (0.76) 1.0 (0.76) 1.0 (0.76) 1.0 (0.76) 1.0 (0.76)
GENERAL DATA
Min.Starting/Operating Ambient°F (°C) (4) 30 (-1.1) 30 (-1.1) 30 (-1.1) 30 (-1.1) 30 (-1.1)
with HGBP, °F (°C) (4) 49 (4.4) 49 (4.4) 49 (4.4) 49 (4.4) 49 (4.4)
Low Ambient Option, °F (°C) (5) 0 (-18) 0 (-18) 0 (-18) 0 (-18) 0 (-18)
Extra Low Ambient Option, °F (°C) (6) -20 (-29) -20 (-29) -20 (-29) -20 (-29) -20 (-29)
Number of Circuits 2 2 2 2 2
Refrigerant Charge, lbs. (kgs) R22 125 103 150 160 165
Shipping Wt., lbs. (kgs) Alum. Fin Cond. 6444 6615 7080 7302 7998
Shipping Wt., lbs. (kgs) Copper Fin Cond. 7099 7270 7712 7934 8872
Operating Wt., lbs.(kgs) Alum. Fin Cond. 6678 6849 7314 7494 8248
Operating Wt., lbs.(kgs) Copper Fin Cond. 7333 7504 7946 8126 9122