Product specifications
27
R22 - 60 HZ - Standard Unit - 1140 RPM Fans
6.5
6.5
Ta bl e 1 3b
ENTERING CONDENSER AIR TEMPERATURE
LWT ACDS-B 45°C 49°C (See Note 4)
015S 40.4 17.1 2.10 38.4 18.5 1.90
020S 54.1 23.2 2.07 51.3 25.1 1.80
025S 69.7 31.0 2.06 65.6 33.5 1.80
027S 80.9 36.4 2.06 76.2 39.1 1.80
030D 91.9 41.5 2.07 87.0 44.5 1.80
025D 80.0 33.4 2.12 76.0 36.2 1.90
030D 96.2 41.9 2.08 91.2 45.3 1.80
035D 103.0 44.9 2.09 97.7 48.6 1.80
040D 118.3 50.8 2.09 112.0 54.9 1.90
045D 139.5 61.3 2.08 131.1 66.2 1.80
050D 150.2 67.3 2.06 141.4 72.5 1.80
055D 166.8 75.1 2.06 157.6 80.7 1.80
057D 174.3 75.0 2.08 165.1 80.8 1.90
060D 178.7 76.2 2.10 169.2 82.0 1.90
065D 202.4 87.2 2.11 191.9 93.8 1.87
070D 223.4 97.9 2.10 210.7 105.0 1.85
080D 246.5 107.2 2.13 234.9 115.5 1.89
090D 275.0 120.9 2.12 263.5 130.3 1.90
100D 297.7 122.8 2.22 285.7 132.4 1.98
PERFORMANCE DATA: S. I. UNITS
NOTES: (1) Other performance requirements can be selected from the Dunham-Bush Electronic Catalog
(2) Ratings based on ARI Standard 550/590-98, 5°C water range in evaporator & .018 fouling factor
(3) Interpolation between ratings is permissable but extrapolation is not
(4) KWi is for compressor only. COP is for entire unit. See Physical Specs for fan kW
(5) High Ambient Applications over 48°C may be affected by the unit’s automatic “High Pressure
Limiting” function that unloads the circuit if head pressure reaches limits by allowing only one
compressor per circuit to run.