Product specifications

26
065D 236.3 65.6 3.18 225.8 72.2 2.79 214.6 79.4 2.43
070D 261.5 74.3 3.15 250.2 81.5 2.77 237.6 89.4 2.42
080D 283.8 81.0 3.16 272.1 88.9 2.79 259.8 97.6 2.44
090D 315.6 91.4 3.15 302.3 100.1 2.78 288.8 110.0 2.43
100D 340.8 93.2 3.25 326.6 101.9 2.88 312.3 111.8 2.53
R22 - 60 HZ - Standard Unit - 1140 RPM Fans
6.5
6.5
Ta b l e 1 3a
ENTERING CONDENSER AIR TEMPERATURE
LWT ACDS-B 30°C 35°C 40°C
°C MODEL kWo kWi COP kWo kWi COP kWo kWi COP
015S 47.1 12.6 3.17 44.9 14.0 2.78 42.7 15.4 2.42
020S 63.9 17.1 3.19 60.7 19.0 2.78 57.5 21.0 2.41
025S 83.1 23.1 3.20 79.0 25.4 2.79 74.5 28.1 2.41
027S 97.1 27.4 3.21 92.0 30.1 2.78 86.5 33.1 2.40
030S 109.9 31.3 3.21 104.1 34.5 2.78 98.1 37.9 2.40
025D 93.1 24.7 3.20 88.8 27.3 2.80 84.6 30.2 2.45
030D 113.5 31.0 3.21 108.0 34.3 2.79 102.2 37.9 2.41
035D 121.7 33.2 3.24 115.6 36.7 2.81 109.4 40.6 2.43
040D 140.0 37.6 3.22 133.1 41.6 2.81 125.9 46.0 2.43
045D 167.0 45.8 3.24 158.5 50.4 2.82 149.4 55.6 2.43
050D 180.0 50.4 3.20 170.6 55.5 2.78 160.7 61.1 2.40
055D 199.7 56.5 3.21 189.1 62.2 2.78 178.1 68.4 2.40
057D 206.9 56.0 3.20 196.4 61.9 2.78 185.5 68.2 2.41
060D 212.8 56.9 3.24 201.8 62.8 2.82 190.4 69.3 2.44
PERFORMANCE DATA: S. I. UNITS
NOTES: (1) Other performance requirements can be selected from the Dunham-Bush Electronic Catalog
(2) Ratings based on ARI Standard 550/590-98, 5°C water range in evaporator & .018 fouling factor
(3) Interpolation between ratings is permissable but extrapolation is not
(4) KWi is for compressor only. COP is for entire unit. See Physical Specs for fan kW