Installation Instructions and User Manual For Inverter Power Systems 1.0 - 17.
READ AND FOLLOW ALL SAFETY INSTRUCTIONS IMPORTANT SAFEGUARDS When using electrical equipment, you should always follow basic safety precautions, including the following: 1. Read and follow all safety instructions. 2. Do not install the LSN (Life Safety Network) inverter system outdoors. 3. Do not install near gas or electric heaters or in other high-temperature locations. 4. Use caution when servicing batteries. Battery acid can cause burns to skin and eyes.
Table of Contents Section 100 System Installation Instructions Description Page 101. Unit Specifications............................................................................................................................................................ 4 102. Receiving, Moving and Storing Systems and Batteries................................................................................................ 5 103. Installation Requirements..................................................
Section 100 System Installation Instructions 101 Specifications Input • Input voltage: 120, 208, 240, 277or 347VAC +10-15%. Other voltages available on request • Input frequency: 60Hz ±3% • Synchronizing slew rate: 1 Hz per second nominal • Input lightning protection: Meets ANSI 62.41, UL 924 and UL 1778 requirements Output • Output voltage: 120, 240, 277, 240/120, 277/120 or 347VAC.
102. Receiving, Moving and Storing Systems and Batteries 102.1 Shipping Damage LSN inverter systems and batteries are normally shipped separately. Carefully inspect all cartons upon receipt for evidence of shipping damage. Notify carrier immediately of leaking or damaged cartons for possible concealed damage. All LSN electronics cabinet cartons are shipped with tip and vibration indicators. Refuse all shipments in which the tip or vibration indicators have been activated. 102.
103. Installation Requirements 103.1 Operating Environment Install the LSN inverter system in a clean, cool, dry place with normal ventilation for human habitation and level floors. CAUTION: Batteries and LSN Electronics cabinets are very heavy. Check to assure that the floor is capable of safely bearing the load. Operating Temperature: LSN inverter Systems are UL Listed for 20° to 30° C (+ 68° to +86° F) operation.
104. Cabinet Mounting 104.1 Dimensions Electronics Cabinet Circuit Breaker Access Door B User Interface Panel Battery Cabinet B Table 104A - Dimensions: Unit and Battery Cabinets Width (A) Height (B) Depth (C) Footprint 30 in. (76 cm) 46 in. (117 cm) 18.65 in (47 cm) 3.88 Ft2 (.36 m2) Table 104B - Clearances Required: Sides Top Front 0 in. (0 mm) 12 in. (31 cm) 30 in. (76 cm) C A 104.
104.3 Cabinet Installation Based on the desired cabinet configuration for the application, remove the appropriate knockouts in the electronics and battery cabinets. See Figures 1, 2, 3, or 4 for the knockout locations. Follow the general sequence below to install the cabinets. CAUTION: Batteries and LSN Electronics cabinets are very heavy. Check to assure that the floor in the installation area is capable of safely bearing the load. 1.
Configuration “B” Three Cabinet Systems Configuration “A” Two Cabinet Systems Install Wall Mounting Brackets To Top Cabinet On Both Sides Install Wall Mounting Brackets To Top Cabinet On Both Sides Configuration “C” Four Cabinet Systems Install Wall Mounting Brackets To Outermost Surfaces Of Upper Cabinets 9
5. Battery Installation and Connection Installing the Batteries and DC Wiring Important Safety Precautions The installer must take these precautions: 1. Wear protective clothing, eye-wear, rubber gloves and boots. Batteries contain corrosive acids or caustic alkalis and toxic materials and can rupture or leak if mistreated. Remove rings and metal wristwatches or other metal objects and jewelry.
105.1 Tools The following tools are required to install the system batteries. Other tools may be necessary if optional batteries have been ordered. CAUTION: Always use insulated tools for battery installation. Always torque to the manufacturer’s recommendations. • Petroleum Jelly • Slotted Screwdriver • 3-inch Socket Extension • Ratchet • Electrical Tape • Digital Volt-Ohm Meter 105.
105.3 Battery Installation Procedure Battery Voltage: Select which wiring diagram to use from this table KVA Rating System DC Voltage Number of Batteries Battery Fuse Rating (Amps) Wiring Diagram Fig. 1.0K 96 8 100 1 2.0K 96 8 100 1 2.7K 96 8 100 1 3.7K 96 8 100 1 4.8 96 8 125 1 5.5K 96 16 125 2 6.6K 96 16 125 2 8.3K 144 24 125 3 10.0K 12.5K 144 144 24 24 125 150 3 3 15.0K 17.
Fig. 1 BATTERY WIRING DIAGRAM 8 BATTERY SYSTEMS CAUTION: Orient all batteries with the positive terminals to the right as shown in the diagram above. Carefully observe battery polarity when making inter-cell and inter-tier connections. Refer to page 17 for battery terminal torque specifications.
Fig. 2 BATTERY WIRING DIAGRAM 16 BATTERY SYSTEMS CAUTION: Orient all batteries with the positive terminals to the right as shown in the diagram above. Carefully observe battery polarity when making inter-cell and inter-tier connections. Refer to page 17 for battery terminal torque specifications.
Fig. 3 BATTERY WIRING DIAGRAM 24 BATTERY SYSTEMS CAUTION: Orient all batteries with the positive terminals to the right as shown in the diagram above. Carefully observe battery polarity when making inter-cell and inter-tier connections. Refer to page 17 for battery terminal torque specifications.
Fig. 4 BATTERY WIRING DIAGRAM 36 BATTERY SYSTEMS 1300736 Rev E CAUTION: Orient all batteries with the positive terminals to the right as shown in the diagram above. Carefully observe battery polarity when making inter-cell and inter-tier connections. Refer to page 17 for battery terminal torque specifications.
105.4 Battery Cabinet Voltage Check and DC Fuse Installation Note: This procedure applies to a 36 battery system. Fewer steps may be required depending on the number of batteries in the system. Important: Always observe proper polarity when taking battery voltage measurements. 1. Using a digital volt-ohm meter (DVM), check for correct nominal battery voltage between right side of fuse block F1 and left side of battery cabinet terminal block TB2 (NEG -).
106. AC Connections CAUTION A. All LSN inverter system units contain hazardous AC and DC voltages. Because of these voltages, a qualified electrician must install the LSN inverter system, AC line service, and batteries. The electrician must install the AC line service according to local, state and NEC codes and must be familiar with batteries and battery installation. B.
5. If not previously done, remove knockouts for AC Input and AC Output in the top of the LSN inverter system (See Figure 1 in Section 104.1). CAUTION: Do not drill the cabinet; drill filings may damage the unit and prevent it from operating. If larger knockouts are needed, use a chassis punch to enlarge the appropriate knockout. Do not add additional or unnecessary knockouts.
107. RS232 Connections All LSN inverter systems are supplied with an RS232 communications port. This port may be used for remote monitoring and control of the system. Connecting the RS232 Port to a Computer or Terminal Note: Connections to the RS232 port must be wired according to Class 1 wiring methods as described in NEC Section 725, Part B. The LSN inverter system is provided with an industry standard DB-9 molded female cable. This cable is located within the LSN system inverter cabinet.
109. Maintenance Bypass Switch Phase Check If you are not using a bypass switch with the LSN inverter system, the phase check is not necessary, so you can skip this section and go directly to Section 110 to complete the system start-up. If the LSN unit does have a bypass switch, complete the following phase check once you have made all of the terminal strip connections and installed the batteries.
! CAUTION: If a Make Before-Break type bypass switch is being used, equipment will be damaged if the switch position is changed while AC line voltage is applied and the LSN system is turned off or operating in inverter (DC) mode. Make sure the LSN system is running on line (AC mode) and supplying output voltage before changing the bypass switch position. See the instructions supplied with your bypass switch. 7. Turn the bypass switch to the “LINE" position.
Section 200 User Manual 201.
201.1 Using The Interface Panel The User Interface Panel is used to display over 250 system parameters, operating modes, alarms and stored logs. When the correct password is entered, the user can also change system modes and parameter values. If the wrong key is pressed at any time, press (CLR) and then the correct key. The control panel will beep each time you press a key. Before changing parameter settings or system modes, a user password must be entered.
User Keypad Actions [PRG] 0 [ENT] ****** [ENT] 093000[ENT] Display Readout Enter Control Code Setup Value Enter Control Code Setup Value 0 Password Required Please enter 6-Digit user password Enter Control Code Setup Value 0 Time 14:00:00 Enter Time (HH:MM:SS) __:__:__ Time 14:00:00 Enter Time (HH:MM:SS) 09:30:00 IMPORTANT: The "TIME" (parameter 0) and "DATE" (parameter 10) must be set by user in order for system to operate properly. 201.
201.6 Parameter “Hot Key” Listing By Function User changeable parameters are shown in boldface.
201.6 Parameter “Hot Key” Listing By Function User changeable parameters are shown in boldface.
202. System Self-Diagnostics Self-testing/self-diagnostic electronics perform continuous testing of subsystems, insuring performance to prescribed operating parameters. Operation outside of prescribed limits or system malfunctions will result in an alarm indication on the system’s user interface display panel. Depending on the type of alert, the panel alarm indication may be visual or audiovisual. User-programmable discharge tests are automatically performed on a monthly and annual basis.
203.5 Performing a Manual Test Manual 5-minute tests may be performed at any time using the following procedure: 1 Press [PRG], 182, [ENT]. 2. Display will read "Password Required" 3. Press "944944" (or current user defined password), [ENT]. 4. Display will read "Start Immediate Monthly Systest Menu, Start (1)" 5. Press "1". 6. Display will read "Monthly Test Started" The LSN system will operate in inverter mode for five minutes.
Battery Voltage Log (Hot Key # 155) An hourly log of the systems total battery voltage and the charging current. Retains the last 48 entries. 081200 13:00 BatV 108.1 V ChgI 0.1 A 081200 12:00 BatV 108.1 V ChgI 0.1 A 081200 11:00 BatV 108.1 V ChgI 0.1 A Battery Discharge Voltage Log (Hot Key # 156) Logs the total battery voltage, at 5-minute intervals, while system is in inverter mode. Also displays the duration of the power failure and the system's output VA.
205. Alarms What They Mean And How To Respond When the LSN system detects a problem, it: • Sounds an alarm • Illuminates the red "ALARM" LED on the User Interface Panel, and • Displays an error message If the system was ordered with an optional e-mail device and the alarm condition lasts for more than five minutes, the unit will automatically send an alarm e-mail to all programmed e-mail locations. In The Event Of An Alarm Condition 1.
Alarm Message What it means ALM VA Hi 16218 15000 Unit has detected an overload and is about to shut down. ALM I2C Comm Microprocessor failure. ALM BattV Hi 182 177 Battery voltage is too high. ALM BattV Lo 125 127 Battery voltage is too low. If unit is in Inverter mode it is about to shut down. ALM BattV Nr Lo 130 132 Battery voltage is near Low level. ALM AmbT Hi 62C 60C Ambient temperature within the electronics ALM CktBrkr Trip One or more output circuit breaker has tripped.
206. Communications Each LSN system is supplied with a DB-9/RS232 communication port enabling the user to communicate with the equipment from a remote location. Owner must supply the connecting cable with a DB-9 Male end, and the appropriate connector at the other for the COM port used on the PC. Follow instructions supplied with the PC to set up communications through a terminal emulation program such as Hyper Terminal on Windows '95, '98.
The e-mail device automatically sends an e-mail to the addresses programmed whenever: • The unit performs a weekly, monthly or annual system test • The unit sounds an alarm NOTE: Communication option installation and wiring instructions are provided in the print package supplied with the unit. 208. Service Options Factory Start-Up Factory Start-Up is provided standard.
300. Maintenance 300.1 Safe Shut Down Procedure CAUTION To avoid possible equipment damage or personal injury, assume that there is AC voltage present inside the LSN inverter system unit any time AC input power or DC battery voltage is applied. The inverter is capable of providing output voltage from the batteries even when there is no AC input line voltage. When AC input voltage is present, the unit can provide output voltage even when the batteries are disconnected.
300.2 Routine System Maintenance The LSN inverter system unit is designed to provide years of trouble-free operation. Its self-testing/self-diagnostic microprocessor will check the batteries and inverter regularly to ensure proper operation. The unit does require some routine attention to assure peak performance. Dual-Lite recommends a Preventative Maintenance check be performed by a qualified service technician at least every six months.
300.4 Battery Maintenance and Replacement This section provides precautions for qualified service personnel working with unit batteries. No user serviceable parts are within the system's cabinets Important Safety Precautions The service technician must take these precautions: 1. Wear protective clothing, eye-wear, rubber gloves and boots. Batteries contain corrosive acids or caustic alkalis and toxic materials and can rupture or leak if mistreated.
CAUTION: A battery can present a risk of electrical shock and high short circuit current. Battery replacement should only be performed by qualified service personnel familiar with battery systems.
5. Remove the batteries from the cabinet. Batteries can be very heavy, use proper lifting methods when removing battery. 6. Install new batteries following the instructions outlined in Section 105.3. Battery Disposal WARNINGS: Do not dispose of batteries in a fire, the batteries could explode. Do not open or mutilate batteries. Released electrolyte is highly toxic and harmful to the skin and eyes. CAUTION: Batteries contain lead.
Appendix 1. Parameter “Hot Key” Numerical Listing Param. No.
Appendix 1. Parameter “Hot Key” Numerical Listing Param. No.
Appendix 1. Parameter “Hot Key” Numerical Listing Param. No.
Notes: 43
1300736 A Hubbell Lighting, Inc. brand with representatives' offices in principal cities throughout North America. Copyright © Hubbell Lighting, Inc. 44 Printed in U.S.A. All Rights Reserved. Content subject to change without notice.