System information

Electrical Specifications
Input
Input voltage: 120, 208, 240, 277, or 347 VAC +10-15%.
Other voltages available on request
Input frequency: 60Hz ±3%
Synchronizing slew rate: 1 Hz per second nominal
Operating temperature: 0°C to 40°C (3F to 10F)
Input lightning protection: Meets ANSI 62.41, UL 924 and
UL 1778 requirements
Output
Output voltage: 120, 240, 277, 120/240, 120/277, or 347 VAC.
Other voltages available upon request
Output regulation: (static) ±5% based on a 5% - 100%
resistive load
Output distortion: Less than 5% THD linear load
Load power factor: .75 lag to .8 lead
Output frequency: Normally, synchronized to utility, +.05 Hz
during emergency
Overload: 150% momentary. 120% for five minutes
Time to transfer to inverter after utility power failure: No break
Battery
Battery charger: Automatic with internal diagnostic indicators
Recharge time: 24 hours. Meets UL 924 requirements
Battery protection: Automatic low-battery voltage
disconnect. Automatic restart upon utility return
Battery switch: Also used as battery isolator
Standard battery: S - Sealed lead-calcium 10-year life
Optional batteries:
G - Sealed lead-calcium 20-year life
N - Wet nickel-cadmium 25-year life
Battery voltage: 96VDC or 144VDC (system dependent)
Runtimes: 90 minutes standard. Other runtimes available on
request
Relative humidity: 95% non-condensing
Note: 100% battery capacity rated at 25°C (77°F). Optimum system
performance between 20°C (68°F) and 29°C (8F); temperatures
outside of this range will affect battery performance and life.
System Features
True “no break” power to loads
Pulse width modulated sine wave output
Low input current distortion
Unique “Off-Line” design increases efficiency to 98% and
reduces heat output
Up to 150% momentary overload capacity
Surge and transient protection circuitry
42,000 RMS symmetrical ampere short-circuit rating
Inverter load versatility lighting (including fluorescent,
incandescent, HID, electronic or power-factor corrected
ballasts), fire, security, communication systems and other
critical loads
Provides computer and network backup
Microprocessor control allows completely automatic
self-diagnostic operation to warn of potential problems
Password protected to prevent unauthorized tampering
Automatic self-testing and test logging as required by NFPA 101
Automatic logging of alarm and inverter events
2-line x 40-character digital display
Inverter communication intelligent, two-way communication
capability provided through the systems RS232 terminal
Built-in backfeed relay to protect personnel from potential
shock hazard
Standard 90-minute battery runtime (optional runtimes available)
Load flexibility and reliability — use of a buildings existing
lighting elements for emergency reduces the likelihood of
unknown lamp failure
No additional backup systems to maintain or test
Intelligent, easy-to-use system
Display panel monitors and controls all parameters
Two-year, on-site electronics warranty covers parts and labor
Batteries carry pro-rata warranty
Only front access required for service
System Operations
A solid-state charger transforms the incoming utility voltage
into a regulated DC supply voltage to charge the batteries.
A maintenance-free battery is provided on standard models
to maintain power to the inverter. The batteries are fitted with
a suitably rated DC switch and fuse to provide overload and
short-circuit protection and also allow isolation from the system
for maintenance purposes.
A high-frequency, pulse width modulated inverter transforms
the battery energy into low-distortion, no break, sine wave AC
voltage to supply the emergency load.
90% boost tap for line regulation protects against brownouts
and conserves batteries for emergencies.
System Features And Design
Sp e ctron
®
l S n
l
i f e
S
a f e ty
n
e t w or k
5
Battery
Pulse
Width
Modulated
Inverter
Solid-State
Transfer
Switch
Energy
Storage
Transformer
Filter
AC
Emergency
Power
Battery
Charger
Control
Circuits and
Utility Switch
AC Utility
Input
Microprocessor
IMPORTANT: Features and specifications are subject to change without notice.
Contact factory for most recent product information.