Specifications

LSN (Life Safety Network) Inverter Suggested Specifications
specifying circuit breaker options, decrease the available number of output breakers by the
proper number of positions chosen.
___ Normally-Off Output Breaker Options:
___ Monitored (recommended) ______Voltage ____ Amp Rating (20 amp maximum)
___ Unmonitored ______Voltage ____ Amp Rating (20 amp maximum)
Used when the lighting fixtures are to be energized only during a power outage. The normally-
off circuit breakers are user programmable for a delay of up to 999 seconds. A maximum of
eight positions are available for all models. Single pole 120V and 277V breakers occupy one
position each, while double pole 208V or 240V breakers occupy two positions each. When
specifying circuit breakers, decrease the available number of output breakers by the proper
number of positions chosen.
___ Alternate Run Time (AR):
UL Listed to Standard 1778 (Uninterruptible Power Supply Equipment)
Up to four-hour run time is available. Example: AR240.
[Note: The National Electrical Code (NEC) requires a minimum of 90-minute run times for
emergency lighting installation requirements].
___Short Battery Cabinet (SBC):
For applications where headroom is limited, the Short Battery Cabinet (SBC) can be used to
reduce the overall installation by 15 inches. Available with 1.0, 2.0, 2.7, 3.7, 5.5 and 6.6 KVA
systems with Type S batteries only. Consult factory for additional details
___ Cat 60 Cabinet Locks (CL60):
Universal cabinet locks for all electronic and battery cabinets
___ Email Device (EML):
A device that automatically notifies the user of system test results and alarm conditions. The
email device sends detailed notifications to up to six pre-programmed email addresses.
Requires customer supplied CAT5 cable connected to user network. Each designated email
address automatically receives a unit status report following all weekly, monthly and annual
tests or when an alarm condition is detected. Status reports include readings on key
operating parameters, as well as complete alarm and inverter log printouts in uncoded user-
friendly descriptions.
___ Remote Status Panel (RSP):
Provides remote system annunciation of inverter and alarm status. Operates up to 1,000 feet
away.
The following color-coded indicators are provided:
Alarm LED (Red)
Audible Alarm
Charging LED (Red)
Emergency Power LED (Yellow)
Ready LED (Green)
A/C On LED (Green)
0603447 Rev C Page 4 of 8 Rev. 9-23-09