Installation Guide
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. Do not use outdoors.
2. Do not mount near heaters or hot surfaces.
3. Equipment should be mounted in locations and at heights where it will not readily be subjected to
tampering by unauthorized personnel.
4. The use of accessory equipment not authorized by the manufacturer may cause an unsafe condition.
5. Do not use this equipment for other than its intended purpose.
6.Serviceofthisequipmentshouldbeperformedbyqualiedservicepersonnel.
SAVE THESE INSTRUCTIONS
FIRE ALARM PANEL (-FAP) OPTION
IMPORTANT: FAP option wires must be run and connected before sign
housing is attached to canopy. FAP option connects to 24 volt AC or DC
(purple wires).
Flash Rate: .5 seconds on, .5 seconds off.
DC REMOTE (-DC) OPTION
IMPORTANT: DC Remote option wires must be run and connected before
sign housing is attached to canopy. DC Remote option connects to 6-24
volt DC [yellow (–), blue(+)].
TROUBLE SHOOTING
Unit does not light
• Check wiring connections.
Emergency circuit does not work
• Batteriesareshippedunchargedanddisconnected.
Connect power pack leads and charge before testing.
• Makesurechargerboardisproperlyseated.
• Checkwiringconnections.
MAINTENANCE
Signs should be tested and maintained in accordance with
National Electrical Code and NFPA 101 Life Safety Code
requirements. It is recommended that emergency exit signs
be tested for 30 seconds once a month and for 90 minutes
once a year.
RECYCLING INFORMATION
All thermoplastic parts are recyclable.
All cartons contain recycled materials.
Please recycle responsibly.
NOTICE:
Emergency model exit signs contain rechargeable
nickel-cadmium batteries which must be recycled or
disposed of properly.
1.
Connect option wires
(provided) to grey
connector on PC board.
2.
Route wires through transformer
compartment and out canopy or
backplate .
Building ground connection.
CAUTION: Never remove or
loosen transformer ground wire
connections.
DUAL CIRCUIT OPTION
Connect transformers to separate AC utility sources using quick connect
terminals provided for each circuit.
120VAC - connect black and white leads.
277VAC - connect red and white leads.
VANDAL/TAMPER RESISTANT APPLICATION (IF PROVIDED)
1. Remove directional arrows (if required) as outlined in this instruction guide.
2. Beforemountingtheexitsign,installthe.093polycarbonatevandalresistantshieldontothe
exit face(s) using four #8 x 3/8” tamper resistant screws and nuts supplied (see below). Tighten
hardware using the spanner head screwdriver provided.
Install the exit sign following the mounting instructions in this instruction guide. After mounting
the exit sign, install the two #8 x 3/8” tamper resistant screws into the sides of the exit as shown
below. Tighten screws using spanner head screwdriver provided.
NOTE: On end mounted models, install only one tamper resistant screw into the side opposite
the mounting canopy.
Spanner head
screwdriver
(provided)
#8 x 3/8”
tamper resistant
screws and nuts (typ. 4)
.093” polycarbonate
vandal resistant shield
#8 x 3/8” tamper resistant screws (typ. 2)
Cast Aluminum
LED Exit Signs
Installation Instructions
Hubbell Lighting, Inc. Life Safety Products • www.dual-lite.com