Specification Sheet

Power Consumption
Models Without Heater Models With Heater
120VAC 2.78 watts 120VAC 15.2 watts
277VAC 2.88 watts 277VAC 15.7 watts
Power factor, average: 0.8 (lagging)
Electronics
Upon failure of the normal utility power, a solid-state transfer switch
automatically activates the emergency lamp. Upon resumption of the
normal utility power, the battery is disconnected from the load and
recharged through a solid-state charging unit. A low voltage battery
disconnect feature protects the battery from severe damage during
prolonged power failures. Spectron® self-testing/self-
diagnostic circuitry provides automatic system testing on a monthly
and semi-annual basis. Manual testing is available at any time using
the push-to-test button: push once for a 60-second system test; push
twice for a 90-minute system test.
Number of Lamps: Four high output LEDs
Lamp Configuration: Two sets of 2 LEDs provide illumination. In the
unlikely event that any single LED should fail the remaining LEDs
willcontinue to function.
Lamp Type: Solid state high output LEDs
Lamp Color: Cool White, 6350K
Total Lamp Output: 405 Lumens
Input: 120/277VAC, 60 Hz
Battery Charger: Temperature compensating, constant current
Transfer: Solid state
Functional Circuitry: AC lockout, transformer isolation, transient
surge protection, low voltage battery disconnect, brownout
detection, time delay retransfer
Battery Recharge Cycle: per UL time standards
Test Means: Integral test switch
Battery: Sealed, maintenance-free Nickel-Cadmium
Operating Temperature Range for Models without Heater:
0°C to 50°C (32°F to 122°F)
Operating Temperature Range for Models with Heater:
-30°C to 50°C (-22°F to 122°F)
PG
Indoor/Outdoor Emergency Lighting Unit
SINGLE UNIT COVERAGE MULTIPLE UNIT SPACING
Mounting Height: 9'
Outdoor Reflectance: 0/30/10
Indoor Reflectance: 80/50/20
Mounting Height: 9'
Illuminated Path Depth: 6'
Outdoor Reflectance: 30/10
Indoor Reflectance: 80/50/20
Indoor
Outdoor
1 FC Average (W x D)
33' X 10' 27' X 10'
1 FC Minimum (W x D)
10' X 10' 9' X 10'
Indoor Outdoor
1 FC Average
44' 33'
1 FC Minimum
16' 15'
W
D
Path of Egress
1 FC Average
DIMENSIONS
SPECIFICATIONS
ILLUMINATION PATTERN
Dual-Lite • www.dual-lite.com
A Hubbell Lighting, Inc. brand with representatives’ offices in principal cities throughout North America.
Copyright
©
Hubbell Lighting Inc., All Rights Reserved Specifications subject to change without notice. • Printed in U.S.A.
0603387 F 05/11
3.1875"
11"
7"