Specification
Web: www.dual-lite.com • Tech Support: (866)-313-3909
701 Millennium Blvd. • Greenville, SC 29607 U.S.A.
Copyright © Dual-Lite, a division of Hubbell Lighting, Inc., All Rights Reserved
Specifications subject to change without notice. • Printed in U.S.A.
0603491 03/18
APPLICATION INFORMATION
5"
8.5"
2.25"
EV-LED
Electronics
Upon failure of normal utility power, a solid-state transfer switch automatically activates the emergency LED lamp-heads. Upon resumption of normal utility
power, the battery is disconnected from the load and recharged through a microprocessor controlled pulse charger. The battery is a maintenance-free Nickel
Metal Hydride(NiMH) type. The EV series accepts dual-voltage input of 120 or 277VAC at 60 Hz, or an optional 220-240VAC input at 50-60 Hz. A low voltage
battery disconnect (LVD) feature protects the battery from severe damage during prolonged power failures. Manual testing is available at any time using the
push-to-test button.
Number of Lamps- 2 High Power LEDs at 1 watt each configured so that if 1 lamp malfunctions, the remaining lamp will continue to provide illumination to
the -0(no-head) option will power 1 double-head remote (EVR2 or EVODW) at 2 watts per lamp (145 lumens). This option allows the battery to be located in a
conditioned environment.
Lamp Color: Cool White
Total Lamp Output: 1W, 88 Lumens per LED
2W (optional), 145 Lumens per LED
System efficacy: 80lm/W
Rated LED lifecycle: greater than 100,000 hrs.
Standard Features Include:
• Intelligent 2-wire input connection
• External push-to-test switch and AC-on indicator
• Battery re-charge within 24 hours
• AC Lock-out circuit
• Low voltage disconnect
• Conduit entry knock-out located at the top center
• Microprocessor controlled pulse charger
Optional Spectron Feature:
• Self-diagnostics monitors LED status, LED load transfer circuit, battery
capacity and charger function and displays any fault detection by
means of a flashing code
• Self-Test feature automatically runs a 1 minute test once a month and
an alternating 30 or 60 minute test once every 6 months. Multi-color
LED indicator provides visible fault detection and charging status.
• User initiated 1 or 90-minute system test feature
• 15 minute re-transfer delay
• Automatic unit transfer in brown-out conditions (below 80% of
nominal AC input voltage)
Operating Temperature Range:
Standard: 68˚ to 86˚F (20˚ to 30˚C)
Damp Listed: 50˚ to 104˚F (10˚ to 40˚C)
Weight: 2.0 lbs
SPECIFICATIONS
DIMENSIONS
MAXIMUM POWER CONSUMPTION
Meets Life Safety Code minimum illuminance of 0.1 fc and average illuminance of 1.0 fc. Assumes open
space with no obstructions, mounting height of 7.5', ceiling height of 9' and reflectances of 80/50/20.
Photometry files available on the Dual-Lite web site (www.dual-lite.com).
W
D
Single Unit Coverage
S
PW
Multi-Unit Spacing
AC
Voltage
Hz. Amps. Watts
Power
Factor
EV2
EV2D
120 60 0.015 1.10 0.61
240 60 0.009 1.43 0.62
277 60 0.008 1.45 0.62
EV4D
120 60 0.022 2.00 0.73
240 60 0.015 2.51 0.65
277 60 0.014 2.75 0.63
1 fc Average
Using 1 Watt
Heads
Using 2 Watt
Heads
Path Width
(PW)
Spacing
(S)
Spacing
(S)
3’ 27’ 39’
6’ 20’ 33’
1 fc Minimum
Using 1 Watt
Heads
Using 2 Watt
Heads
Path Width
(PW)
Spacing
(S)
Spacing
(S)
3’ 14’ 18’
6’ 10’ 14’
Maintenance mode power consumption less than 0.5 watts.
1 fc Average
Using 1 Watt Heads
Depth (D) Width (W)
16’ 10’
Using 2 Watt Heads
Depth (D) Width (W)
26’ 10’
1 fc Minimum
Using 1 Watt Heads
Depth (D) Width (W)
6’ 10’
Using 2 Watt Heads
Depth (D) Width (W)
9’ 10’
EV Series
Architectural LED Emergency Light