WinDSX Tech – FAQ Notes
Error 9” when trying to edit System Parameters or Location is caused by the
increased number of regional time zones in Windows. Accommodations for
Microsoft’s time zone structuring have been provided in our latest software releases.
The problem should not appear with WinDSX 3.7.121 and higher.
http://www.dsxinc.com/support.htm
Operation Must Use an Updateable Query” is typically caused by inadequate
Windows permissions to the files in the target Path to Database. Usually seen when
adding Workstation PC’s to an existing system.
If there appears to be no control of relays on a DSX-1043 Intelligent Controller,
make sure it is defined with a Device Type of OR”. Also, make sure there is a short
between the Relay Override input terminals near the center of the Controller.
These were pins 24-25 on older 1043’s, pins 50-51 on newer 1043’s.
3.7/4.7 Upgrade
-
Software Version 3.7/4.7 and higher has a new feature that allows
Time Zone Linking. This new linking logic will only work if all of the controllers in
the location are of 1040 Series, 1022, or 1032 controllers with the 1030PR5 retrofit
processor. All controllers in the location will require V3129 or higher. This feature
cannot be used if any of the controllers are of the old style 1030 Series or 1021. The
3.7/4.7 versions also require new updated versions of PC Master and Soft I/O.
When trying to program a DSX-LAN module from a PC you’re not familiar with,
and you can’t get !!! to prompt for a password, try this test. Type the letters AT and
hit enter. If you get an OK back on the screen, you’re not using the correct comm
port. You’re actually talking to an internal dialup modem.
If WinDSX ever generates a C++ error when starting, check the WinDSX/Errors
sub folder. If it exists, double click on cserrorlog.txt to open in Notepad. Scroll
down to the last entry in the list. If you see a reference to ‘Unrecognized database
format, C:\WinDSX\alarm.mdb’, close Notepad, delete any files in the Errors folder,
then delete alarm.mdb in the WinDSX folder. Run Repair and repair the existing
database. Then modify the update.txt to have a 1 instead of a 0. Save it close it and
re-Start WinDSX and verify that the program runs OK.