22
43 WDTMR trap Software has detected a Watchdog timer overflow
45 ISBS xfer Static Bypass Switch has transferred load to Inverter
46 Inv Stop Inverter has unexpected shut off
47 Pwr on RST CPU initialization complete
49 ESTOP trap Emergency Stop option has caused an emergency transfer to utility
50 RunState0 Power has been applied to system
51 RunState1 Initial system checks complete, awaiting DC breaker closure
52 RunState2 Startup complete, system ready
53 RunState3 Utility power failure, system is on a battery run
54 Bypass on System is in bypass
56 Battry Low Battery Voltage is low, causes a system shutdown
57 KeyCode OK Key Code Accepted
58 AirFlow DN AirFlow fault detected, DC BUS set to minimum value
CAUTION
Verify that the output voltage as stated on the UPS nameplate matches the actual
output voltage of the unit. Ensure that the intended connected load does not
exceed unit capacity. If the voltage does not match, or the intended applied load
exceeds unit capacity, STOP installation of the UPS and contact Customer
Service at DSPM.