History Log Key:
The History Log is used to record certain events that reflect the status and operating
mode of the unit.
There are 64 lines (00 through 63).
It is read by holding down the Alarm Scan button. Each time the button is pressed, the
log is read sequentially with the most recent event being displayed first. After 00 is
displayed, the system will cycle around to 63.
After 64 events are logged, the system will start recording again at 00.
Code Message
Description
00 00 Blank – used in clearing Alarm History
01 alarm clr Alarm History has been cleared
02 Phase SEQ Input phase sequence has caused a fault and must be changed
04 Input OV Input voltage has gone over fault limit
05 Input UV Input voltage has gone below fault limit
07 Input CONT System has failed to detect closure of the Input Contactor
08 Outpt HiV Output voltage has gone over fault limit
09 Output LoV Output voltage has gone below fault limit
10 Outpt OFrq Output frequency has gone over fault limit
11 Outpt UFrq Output frequency has gone below fault limit
12 Phase FLT Input phase sequence fault has not been corrected and system has timed
out
13 Invrtr FLT a hardware fault has been detected by the inverter control board (IGBT
PCBA); caused by IGBT failure, unexpected power on reset, or DC Bus
over voltage
14 DC Bus OV DC Bus has gone over fault limit
15 DC Bus UV DC Bus has gone below fault limit
16 Input OFrq Input frequency has gone over fault limit
17 Input UFrq Input frequency has gone below fault limit
18 RECT off Rectifier has shut off unexpectedly
20 Invrt Ofrq Inverter frequency has gone over fault limit
21 Invrt UFrq Inverter frequency has gone below fault limit
22 ISBS open Inverter Static Bypass Switch has not engaged and system has timed out
23 USBS fault Utility Static Bypass Switch has failed test
24 USBS short Utility Static Bypass Switch failure, output voltage still detected after off
command was issued
26 Output OVL Output Current has gone over fault limit
28 Estop OPEN Emergency Stop option enabled during system power-up
35 UPS abort System faults have caused system to switch to bypass
36 Normal run Automated system test concluded
37 BATT test Automated system test initiated (15 minute rectifier shutoff and battery
run)
38 Inv start Inverter has been started and matched with utility voltage
40 NMI trap NMI button on processor board has been pressed, date and time marker
41 STKUF trap Software Stack underflow detected
42 STKOF trap Software Stack overflow detected