Eternalight 1 Emergency Lighting Inverter
KWatts
Input
Voltage
Output
Voltage
Utility Feed
Amps
Max Output
Amps
KWatts
Input
Voltage
Output
Voltage
Utility Feed
Amps
Max Output
Amps
120 43.7 120 87.5
240 21.8 240 43.7
120
277
88
18.9
120
277
175
37.9
120 43.7 120 87.5
240 21.8 240 43.7
208
277
51
18.9
208
277
101
37.9
120 43.7 120 87.5
240 21.8 240 43.7
240
277
44
18.9
240
277
88
37.9
120 43.7 120 87.5
240 21.8 240 43.7
277
277
38
18.9
277
277
76
37.9
120 43.7 120 87.5
240 21.8 240 43.7
277 18.9 277 37.9
5.25
480
480
22
10.9
10.5
480
480
44
21.8
120 58.3 120 104.1
240 29.1 240 52.0
120
277
117
25.2
120
277
209
45.1
120 58.3 120 104.1
240 29.1 240 52.0
208
277
68
25.2
208
277
121
45.1
120 58.3 120 104.1
240 29.1 240 52.0
240
277
59
25.2
240
277
105
45.1
120 58.3 120 104.1
240 29.1 240 52.0
277
277
51
25.2
277
277
91
45.1
120 58.3 120 104.1
240 29.1 240 52.0
277 25.2 277 45.1
7
480
480
30
14.5
12.5
480
480
53
26.0
120 75.0 120 125.0
240 37.5 240 62.5
120
277
150
32.4
120
277
250
54.1
120 75.0 120 125.0
240 37.5 240 62.5
208
277
87
32.4
208
277
145
54.1
120 75.0 120 125.0
240 37.5 240 62.5
240
277
75
32.4
240
277
125
54.1
120 75.0 120 125.0
240 37.5 240 62.5
277
277
65
32.4
277
277
109
54.1
120 75.0 120 125.0
240 37.5 240 62.5
277 32.4 277 54.1
9
480
480
38
18.7
15
480
480
63
31.2
All Circuit Breakers provided by end user, that are connected to the inputs and outputs need to have a Trip Curve which is at least 10
times the rated current for .3 seconds, this is to prevent the breakers from tripping during startup of the unit or the loads, attached to the
units. Some Manufacturers refer to these breakers as "High Inrush" breakers.