3-3 OUPUT CONNECTIONS
1. Verify that power source to the unit is OFF, locked and tagged according to
OSHA requirements.
CAUTION
Verify that the output voltage as stated on the DE1 nameplate matches the actual
output voltage of the unit. Ensure that the intended connected load does not
exceed unit capacity. If the voltage does not match, or the intended applied load
exceeds unit capacity, STOP installation of the DE1 and contact Customer
Service at DSPM.
2. Verify that Output cable(s) and conduit(s) are routed correctly and are in position
to connect the unit.
3. Punch the appropriate sized conduit hole in the unit.
4. Pass wires through the mounting hole.
5. Secure conduit fitting to the panel of unit.
6. Connect power wires to the output, neutral and ground terminal blocks. These
are pre-wired to the DE1 System. See the picture above.
3-4 BATTERIES AND BATTERY CABLES
WARNING!!
FOLLOW THE BATTERY SAFETY PROCEDURE IN THE FRONT OF THIS MANUAL.
The DE1 system has fixed battery trays. All battery systems connect the batteries in
series, i.e. plus terminal to minus terminal from one battery to another battery. The
battery circuit breaker must be off during the installation. Install the batteries and
connect the battery cables. The DE1 utilizes 10, 18 or 20 battery, bus voltage should be
12 to 13.2 VDC times the number of battery provided (See battery diagram). Connect
the battery string to the DC Circuit Breaker. See picture below.