Technical information
3.12 Main Menu - LonWorks - Group 11
Parameter group for all LonWorks specific parameters.
Parameters related to LonWorks ID.
11-00 Neuron ID
Range: Function:
0 * [0 - 0 ] View the Neuron chip's unique Neuron ID number.
11-10 Drive Profile
Option: Function:
This parameter allows selecting between
LONMARK Functional Profiles.
[0] * VSD profile The Danfoss Profile and the Node Object
are common for all profiles.
[1] Pump controller
11-15 LON Warning Word
Range: Function:
0 * [0 - 65535 ] This parameter contains the LON specific
warnings.
Bit Status
0 Internal fault
1 Internal fault
2 Internal fault
3 Internal fault
4 Internal fault
5 Reserved
6 Reserved
7 Reserved
8 Reserved
9 Changeable types
10 Initialization error
11 Internal communication error
12 Software revision mismatch
13 Bus not active
14 Option not present
15 LON input (nvi/nci) exceeds limits
11-17 XIF Revision
Range: Function:
0 * [0 - 0 ] This parameter contains the version of the external
interface file on the Neuron C chip on the LON
option.
11-18 LonWorks Revision
Range: Function:
0 * [0 - 0 ] This parameter contains the software version of the
application program on the Neuron C chip on the
LON option.
11-21 Store Data Values
Option: Function:
This parameter is used to activate storing of
data in non-volatile memory.
[0] * Off Store function is inactive.
[2] Store all
setups
Stores all parameter values in the E
2
PROM.
The value returns to Off when all parameter
values have been stored.