Technical information
9-53 Profibus Warning Word
Range: Function:
0 * [0 - 65535 ] This parameter displays Profibus communi-
cation warnings. Please refer to the Profibus
Operating Instructions for further information.
Read only
Bit: Meaning:
0 Connection with DP-master is not ok
1 Not used
2 FDLNDL (Fieldbus Data link Layer) is not ok
3 Clear data command received
4 Actual value is not updated
5 Baudrate search
6 PROFIBUS ASIC is not transmitting
7 Initialisation of PROFIBUS is not ok
8 Frequency converter is tripped
9 Internal CAN error
10 Wrong configuration data from PLC
11 Wrong ID sent by PLC
12 Internal error occured
13 Not configured
14 Timeout active
15 Warning 34 active
9-63 Actual Baud Rate
Option: Function:
This parameter displays the actual
Profibus baud rate. The Profibus
Master automatically sets the baud
rate.
[0] 9,6 kbit/s
[1] 19,2 kbit/s
[2] 93,75 kbit/s
[3] 187,5 kbit/s
[4] 500 kbit/s
[6] 1500 kbit/s
[7] 3000 kbit/s
[8] 6000 kbit/s
[9] 12000 kbit/s
[10] 31,25 kbit/s
[11] 45,45 kbit/s
[255] * No baudrate found
9-65 Profile Number
Range: Function:
0 * [0 - 0 ] This parameter contains the profile identification.
Byte 1 contains the profile number and byte 2 the
version number of the profile.
NOTE
This parameter is not visible via LCP.
9-70 Programming Set-up
Option: Function:
Select the set-up to be edited.
[0] Factory setup Uses default data. This option can be used
as a data source to return the other set-ups
to a known state.
[1] Set-up 1 Edits Set-up 1.
[2] Set-up 2 Edits Set-up 2.
[3] Set-up 3 Edits Set-up 3.
[4] Set-up 4 Edits Set-up 4.
[9] * Active Set-up
Follows the active set-up selected in
0-10 Active Set-up.
This parameter is unique to LCP and fieldbuses. See also
0-11 Programming Set-up.
9-71 Profibus Save Data Values
Option: Function:
Parameter values changed via Profibus are not
automatically stored in non-volatile memory.
Use this parameter to activate a function that
stores parameter values in the EEPROM non-
volatile memory, so changed parameter values
will be retained at power-down.
[0] * Off Deactivates the non-volatile storage function.
[1] Store all
setups
Stores all parameter values for all set-ups in the
non-volatile memory. The selection returns to
Off [0] when all parameter values have been
stored.
[2] Store all
setups
Stores all parameter values for all set-ups in the
non-volatile memory. The selection returns to
Off [0] when all parameter values have been
stored.
9-72 ProfibusDriveReset
Option: Function:
[0] * No action
[1] Power-on
reset
Resets frequency converter upon power-up,
as for power-cycle.
[3] Comm option
reset
Resets the Profibus option only, useful after
changing certain settings in parameter
group 9-**, e.g. 9-18 Node Address.
When reset, the frequency converter
disappears from the fieldbus, which may
cause a communication error from the
master.