Technical information

3.9.5 8-5* Digital/Bus
Parameters for configuring the control word Digital/Bus
merging.
NOTE
These parameters are active only when 8-01 Control Site is
set to [0] Digital and control word.
8-50 Coasting Select
Option: Function:
Select control of the coasting function via the
terminals (digital input) and/or via the bus.
[0] Digital
input
Activates Start command via a digital input.
[1] Bus Activates Start command via the serial
communication port or fieldbus option.
[2] Logic AND Activates Start command via the fieldbus/serial
communication port, AND additionally via one
of the digital inputs.
[3] * Logic OR Activates Start command via the fieldbus/serial
communication port OR via one of the digital
inputs.
8-52 DC Brake Select
Option: Function:
Select control of the DC brake via the terminals
(digital input) and/or via the fieldbus.
NOTE
Only selection [0] Digital input is available
when 1-10 Motor Construction is set to [1]
PM non salient SPM.
[0] Digital
input
Activates Start command via a digital input.
[1] Bus Activates Start command via the serial
communication port or fieldbus option.
[2] Logic AND Activates Start command via the fieldbus/serial
communication port, AND additionally via one
of the digital inputs.
[3] * Logic OR Activates Start command via the fieldbus/serial
communication port OR via one of the digital
inputs.
8-53 Start Select
Option: Function:
Select control of the frequency converter start
function via the terminals (digital input) and/or
via the fieldbus.
[0] Digital
input
Activates Start command via a digital input.
8-53 Start Select
Option: Function:
[1] Bus Activates Start command via the serial
communication port or fieldbus option.
[2] Logic AND Activates Start command via the fieldbus/serial
communication port, AND additionally via one
of the digital inputs.
[3] * Logic OR Activates Start command via the fieldbus/serial
communication port OR via one of the digital
inputs.
8-54 Reversing Select
Option: Function:
Select control of the frequency converter
reverse function via the terminals (digital
input) and/or via the fieldbus.
[0] * Digital
input
Activates Reverse command via a digital input.
[1] Bus Activates Reverse command via the serial
communication port or fieldbus option.
[2] Logic AND Activates Reverse command via the fieldbus/
serial communication port, AND additionally
via one of the digital inputs.
[3] Logic OR Activates Reverse command via the fieldbus/
serial communication port OR via one of the
digital inputs.
NOTE
This parameter is active only when 8-01 Control Site is set
to [0] Digital and control word.
8-55 Set-up Select
Option: Function:
Select control of the frequency converter set-
up selection via the terminals (digital input)
and/or via the fieldbus.
[0] Digital
input
Activates the set-up selection via a digital
input.
[1] Bus Activates the set-up selection via the serial
communication port or fieldbus option.
[2] Logic AND Activates the set-up selection via the fieldbus/
serial communication port, AND additionally
via one of the digital inputs.
[3] * Logic OR Activate the set-up selection via the fieldbus/
serial communication port OR via one of the
digital inputs.
8-56 Preset Reference Select
Option: Function:
Select control of the frequency converter
Preset Reference selection via the terminals
(digital input) and/or via the fieldbus.
Parameter Description
VLT
®
HVAC Drive Programming Guide
86 MG11CD02 - VLT
®
is a registered Danfoss trademark
3
3