Technical information
EXAMPLE 2:
Variable= FEEDBACK, range= -200% to +200%
Range needed for output= 0-100%
Output signal 0 or 4mA is needed at 0% (50% of range) -
set 6-51 Terminal 42 Output Min Scale to 50%
Output signal 20mA is needed at 100% (75% of range) -
set 6-52 Terminal 42 Output Max Scale to 75%
0/4 mA
20 mA
50% 75% 100%0%
0% +100% +200%-200%
130BA856.10
EXAMPLE 3:
Variable value= REFERENCE, range= Min ref - Max ref
Range needed for output= Min ref (0%) - Max ref (100%),
0-10 mA
Output signal 0 or 4mA is needed at Min ref - set
6-51 Terminal 42 Output Min Scale to 0%
Output signal 10mA is needed at Max ref (100% of range) -
set 6-52 Terminal 42 Output Max Scale to 200%
(20mA/10mA x 100%=200%).
20 mA
10 mA
0/4 mA
100% 200%
0%
Max ref Max ref X 20/10Min ref
130BA857.10
6-53 Terminal 42 Output Bus Control
Range: Function:
0.00 %* [0.00 - 100.00 %] Holds the level of Output 42 if
controlled by bus.
6-54 Terminal 42 Output Timeout Preset
Range: Function:
0.00 %* [0.00 -
100.00 %]
Holds the preset level of Output 42.
6-54 Terminal 42 Output Timeout Preset
Range: Function:
In case of a bus timeout and a timeout
function is selected in 6-50 Terminal 42
Output the output will preset to this
level.
3.8.7 6-6* Analog Output 2 MCB 101
Analog outputs are current outputs: 0/4 - 20mA. Common
terminal (terminal X30/8) is the same terminal and
electrical potential for analog common connection.
Resolution on analog output is 12 bit.
6-60 Terminal X30/8 Output
Same options and functions as 6-50 Terminal 42 Output.
Option: Function:
[0] * No operation
6-61 Terminal X30/8 Min. Scale
Range: Function:
0.00
%*
[0.00 -
200.00 %]
Scales the minimum output of the selected
analog signal on terminal X30/8. Scale the
minimum value as a percentage of the
maximum signal value, i.e. 0mA (or 0hz) is
desired at 25% of the maximum output value
and 25% is programmed. The value can
never be higher than the corresponding
setting in 6-62 Terminal X30/8 Max. Scale if
value is below 100%.
This parameter is active when option module
MCB 101 is mounted in the frequency
converter.
6-62 Terminal X30/8 Max. Scale
Range: Function:
100.00
%*
[0.00
-
200.00
%]
Scales the maximum output of the selected
analog signal on terminal X30/8. Scale the value
to the desired maximum value of the current
signal output. Scale the output to give a lower
current than 20mA at full scale or 20mA at an
output below 100% of the maximum signal
value. If 20mA is the desired output current at
a value between 0 - 100% of the ful-scale
output, program the percentage value in the
parameter, i.e. 50% = 20mA. If a current
between 4 and 20mA is desired at maximum
output (100%), calculate the percentage value
as follows:
20
mA
/
desired
maximum
current
× 100 %
i
.
e
. 10
mA
:
20
mA
10
mA
× 100 % = 200 %