Technical information
6-50 Terminal 42 Output
Option: Function:
[131] Reference 4-20mA Minimum Reference - Maximum
Reference
[132] Feedback 4-20mA
-200% to +200% of 20-14 Maximum
Reference/Feedb.
[133] Motor cur. 4-20mA
0 - Inverter Max. Current (16-37 Inv.
Max. Current)
[134] Torq.0-lim 4-20 mA
0 - Torque limit (4-16 Torque Limit
Motor Mode)
[135] Torq.0-nom
4-20mA
0 - Motor rated torque
[136] Power 4-20mA 0 - Motor rated power
[137] * Speed 4-20mA 0 - Speed High Limit (4-13 and 4-14)
[139] Bus ctrl. 0 - 100%, (0-20 mA)
[140] Bus ctrl. 4-20 mA 0 - 100%
[141] Bus ctrl t.o. 0 - 100%, (0-20 mA)
[142] Bus ctrl t.o.
4-20mA
0 - 100%
[143] Ext. CL 1 4-20mA 0 - 100%
[144] Ext. CL 2 4-20mA 0 - 100%
[145] Ext. CL 3 4-20mA 0 - 100%
NOTE
Values for setting the Minimum Reference is found in open
loop 3-02 Minimum Reference and for closed loop
20-13 Minimum Reference/Feedb. - values for maximum
reference for open loop is found in 3-03 Maximum
Reference and for closed loop 20-14 Maximum Reference/
Feedb..
6-51 Terminal 42 Output Min Scale
Range: Function:
0.00 %* [0.00 -
200.00 %]
Scale for the minimum output (0 or
4mA) of the analog signal at terminal 42.
Set the value to be the percentage of
the full range of the variable selected in
6-50 Terminal 42 Output.
6-52 Terminal 42 Output Max Scale
Range: Function:
100.00
%*
[0.00 -
200.00
%]
Scale for the maximum output (20mA) of the
analog signal at terminal 42.
Set the value to be the percentage of the full
range of the variable selected in 6-50 Terminal
42 Output.
6-52 Terminal 42 Output Max Scale
Range: Function:
130BA075.12
(mA)
0%
20
0/4
100%
Current
Analogue
output
Min Scale
par. 6-93
Variable
for
output
example:
Speed
(RPM)
Analogue
Output
Max Scale
par. 6-94
It is possible to get a value lower than 20mA
at full scale by programming values >100% by
using a formula as follows:
20
mA
/
desired
maximum
current
× 100 %
i
.
e
. 10
mA
:
20
mA
10
mA
× 100 % = 200 %
EXAMPLE 1:
Variable value= OUTPUT FREQUENCY, range = 0-100 Hz
Range needed for output = 0-50Hz
Output signal 0 or 4mA is needed at 0Hz (0% of range) -
set 6-51 Terminal 42 Output Min Scale to 0%
Output signal 20mA is needed at 50Hz (50% of range) - set
6-52 Terminal 42 Output Max Scale to 50%
0/4 mA
20 mA
50% 100%0%
50Hz 100Hz0Hz
130BA858.10
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG11CD02 - VLT
®
is a registered Danfoss trademark 79
3
3