Technical information

5-66 Terminal X30/6 Pulse Output Variable
Select the variable for read-out on terminal X30/6.
This parameter is active when option module MCB 101 is
installed in the frequency converter.
Same options and functions as parameter group 5-6*.
Option: Function:
[0] * No operation
[45] Bus ctrl.
[48] Bus ctrl., timeout
[51] MCO controlled
[100] Output frequency
[101] Reference
[102] Feedback
[103] Motor current
[104] Torque rel to limit
[105] Torq relate to rated
[106] Power
[107] Speed
[108] Torque
[109] Max Out Freq
[119] Torque % lim
5-68 Pulse Output Max Freq #X30/6
Select the maximum frequency on terminal X30/6 referring to
the output variable in 5-66 Terminal X30/6 Pulse Output Variable.
This parameter cannot be adjusted while the motor is running.
This parameter is active when option module MCB 101 is
mounted in the frequency converter.
Range: Function:
Application
dependent*
[0 - 32000 Hz]
3.7.9 5-9* Bus Controlled
This parameter group selects digital and relay outputs via
a fieldbus setting.
5-90 Digital & Relay Bus Control
Range: Function:
0 * [0 -
2147483647 ]
This parameter holds the state of the
digital outputs and relays that is controlled
by bus.
A logical '1' indicates that the output is
high or active.
A logical '0' indicates that the output is low
or inactive.
5-90 Digital & Relay Bus Control
Range: Function:
Bit 0 CC Digital Output Terminal 27
Bit 1 CC Digital Output Terminal 29
Bit 2 GPIO Digital Output Terminal X
30/6
Bit 3 GPIO Digital Output Terminal X
30/7
Bit 4 CC Relay 1 output terminal
Bit 5 CC Relay 2 output terminal
Bit 6 Option B Relay 1 output terminal
Bit 7 Option B Relay 2 output terminal
Bit 8 Option B Relay 3 output terminal
Bit 9-15 Reserved for future terminals
Bit 16 Option C Relay 1 output terminal
Bit 17 Option C Relay 2 output terminal
Bit 18 Option C Relay 3 output terminal
Bit 19 Option C Relay 4 output terminal
Bit 20 Option C Relay 5 output terminal
Bit 21 Option C Relay 6 output terminal
Bit 22 Option C Relay 7 output terminal
Bit 23 Option C Relay 8 output terminal
Bit
24-31
Reserved for future terminals
5-93 Pulse Out #27 Bus Control
Range: Function:
0.00 %* [0.00 - 100.00
%]
Contains the frequency to apply to
the digital output terminal 27, when
it is configured as [Bus Controlled].
5-94 Pulse Out #27 Timeout Preset
Range: Function:
0.00 %* [0.00 - 100.00
%]
Contains the frequency to apply to
the digital output terminal 27, when
it is configured as [Bus Controlled
Timeout] and timeout is detected.
5-95 Pulse Out #29 Bus Control
Range: Function:
0.00 %* [0.00 - 100.00
%]
Contains the frequency to apply to
the digital output terminal 29, when
it is configured as [Bus Controlled].
5-96 Pulse Out #29 Timeout Preset
Range: Function:
0.00 %* [0.00 - 100.00
%]
Contains the frequency to apply to
the digital output terminal 29, when
it is configured as [Bus Controlled
Timeout] and timeout is detected
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG11CD02 - VLT
®
is a registered Danfoss trademark 73
3