Technical information
[200] Full
Capacity
All pumps running and at full speed
[201] Pump1
Running
One or more of the pumps controlled by the
Cascade Controller are running. The function
will also depend on the setting of in
25-06 Number of Pumps. If set to No [0] Pump
1 refers to the pump controlled by relay
RELAY1 etc. If set to Yes [1] Pump 1 refers to
the pump controlled by the frequency
converter only (without any of the build in
relays involved) and Pump 2 to the pump
controlled by the relay RELAY1. See below
table:
[202] Pump2
Running
See [201]
[203] Pump3
Running
See [201]
Setting in parameter
group 5-3*
Setting in 25-06 Number of Pumps
[0] No [1] Yes
[200] Pump 1
Running
Controlled by
RELAY1
Frequency Converter
controlled
[201] Pump 2
Running
Controlled by
RELAY2
Controlled by
RELAY1
[203] Pump 3
Running
Controlled by
RELAY3
Controlled by
RELAY2
5-30 Terminal 27 Digital Output
Same options and functions as parameter group 5-3*.
Option: Function:
[0] * No operation
5-31 Terminal 29 Digital Output
Same options and functions as parameter group 5-3*.
Option: Function:
[0] * No operation
5-32 Term X30/6 Digi Out (MCB 101)
This parameter is active when option module MCB 101 is
mounted in the frequency converter. Same options and functions
as parameter group 5-3*.
Option: Function:
[0] * No operation
5-33 Term X30/7 Digi Out (MCB 101)
This parameter is active when option module MCB 101 is
mounted in the frequency converter. Same options and functions
as parameter group 5-3*.
Option: Function:
[0] * No operation
3.7.6 5-4* Relays
Parameters for configuring the timing and the output
functions for the relays.
5-40 Function Relay
Array [8]
(Relay 1 [0], Relay 2 [1]
Option MCB 105: Relay 7 [6], Relay 8 [7] and Relay 9 [8]).
Select options to define the function of the relays.
The selection of each mechanical relay is realised in an array
parameter.
Option: Function:
[0] * No operation
[1] Control ready
[2] Drive ready
[3] Drive rdy/rem ctrl
[4] Standby / no warning
[5] * Running Default setting for relay
2.
[6] Running / no warning
[8] Run on ref/no warn
[9] * Alarm Default setting for relay
1.
[10] Alarm or warning
[11] At torque limit
[12] Out of current range
[13] Below current, low
[14] Above current, high
[15] Out of speed range
[16] Below speed, low
[17] Above speed, high
[18] Out of feedb. range
[19] Below feedback, low
[20] Above feedback, high
[21] Thermal warning
[25] Reverse
[26] Bus OK
[27] Torque limit & stop
[28] Brake, no brake war
[29] Brake ready, no fault
[30] Brake fault (IGBT)
[35] External Interlock
[36] Control word bit 11
[37] Control word bit 12
[40] Out of ref range
[41] Below reference, low
[42] Above ref, high
[45] Bus ctrl.
[46] Bus ctrl, 1 if timeout
[47] Bus ctrl, 0 if timeout
[60] Comparator 0
[61] Comparator 1
[62] Comparator 2
[63] Comparator 3
[64] Comparator 4
[65] Comparator 5
[70] Logic rule 0
[71] Logic rule 1
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG11CD02 - VLT
®
is a registered Danfoss trademark 69
3