Technical information

5-19 Terminal 37 Safe Stop
Option: Function:
off). When safe stop circuit is reestablished,
the frequency converter will continue without
manual reset, unless a Digital Input set to
PTC Card 1 [80] is (still) enabled. Choice 7 is
only available when the MCB 112 PTC
Thermistor Card is connected.
[8] PTC 1 &
Relay A/W
This choice makes it possible to use a
combination of Alarm and Warning. Choice 8
is only available when the MCB 112 PTC
Thermistor Card is connected.
[9] PTC 1 &
Relay W/A
This choice makes it possible to use a
combination of Alarm and Warning. Choice 9
is only available when the MCB 112 PTC
Thermistor Card is connected.
Choises 4 - 9 are only available when the MCB 112 PTC
Thermistor Card is connected.
NOTE
When Auto Reset/Warning is selected the frequency
converter opens up for automatic restart.
Overview of functions, alarms and warnings
Function
No. PTC Relay
No Function [0] - -
Safe Stop Alarm [1]* - Safe Stop [A68]
Safe Stop Warning [3] - Safe Stop [W68]
PTC 1 Alarm [4] PTC 1 Safe Stop
[A71]
-
PTC 1 Warning [5] PTC 1 Safe Stop
[W71]
-
PTC 1 & Relay A [6] PTC 1 Safe Stop
[A71]
Safe Stop [A68]
PTC 1 & Relay W [7] PTC 1 Safe Stop
[W71]
Safe Stop [W68]
PTC 1 & Relay A/W [8] PTC 1 Safe Stop
[A71]
Safe Stop [W68]
PTC 1 & Relay W/A [9] PTC 1 Safe Stop
[W71]
Safe Stop [A68]
W means warning and A means alarm. For further information, see
Alarms and Warnings in section Troubleshooting in the Design Guide
or the Operating Instructions
A dangerous failure related to Safe Stop will give Alarm:
Dangerous Failure [A72].
Please refer to Table 4.2 in 4.1 Troubleshooting.
3.7.5
5-3* Digital Outputs
Parameters for configuring the output functions for the
output terminals. The 2 solid-state digital outputs are
common for terminals 27 and 29. Set the I/O function for
terminal 27 in 5-01 Terminal 27 Mode and set the I/O
function for terminal 29 in 5-02 Terminal 29 Mode. These
parameters cannot be adjusted while the motor is running.
The digital outputs can be programmed
with these functions:
[0] No operation
Default for all digital outputs and relay
outputs
[1] Control ready The control board receives supply voltage.
[2] Drive ready The frequency converter is ready for
operation and applies a supply signal on
the control board.
[3] Drive ready /
remote
control
The frequency converter is ready for
operation and is in Auto On mode.
[4] Stand-by / no
warning
The frequency converter is ready for
operation. No start or stop command is
been given (start/disable). There are no
warnings.
[5] Running The motor is running.
[6] Running / no
warning
The output speed is higher than the speed
set in 1-81 Min Speed for Function at Stop
[RPM]. The motor is running and there are
no warnings.
[8] Run on
reference / no
warning
The motor runs at reference speed.
[9] Alarm An alarm activates the output. There are
no warnings.
[10] Alarm or
warning
An alarm or a warning activates the
output.
[11] At torque
limit
The torque limit set in 4-16 Torque Limit
Motor Mode or 4-13 Motor Speed High Limit
[RPM] has been exceeded.
[12] Out of
current range
The motor current is outside the range set
in 4-18 Current Limit.
[13] Below
current, low
The motor current is lower than set in
4-50 Warning Current Low.
[14] Above
current, high
The motor current is higher than set in
4-51 Warning Current High.
[15] Out of speed
range
The output speed is outside the range set
in 4-52 Warning Speed Low and
4-53 Warning Speed High.
[16] Below speed,
low
The output speed is lower than the setting
in 4-52 Warning Speed Low.
[17] Above speed,
high
The output speed is higher than the
setting in 4-53 Warning Speed High.
[18] Out of
feedback
range
The feedback is outside the range set in
4-56 Warning Feedback Low and
4-57 Warning Feedback High.
Parameter Description
VLT
®
HVAC Drive Programming Guide
66 MG11CD02 - VLT
®
is a registered Danfoss trademark
3
3