Technical information

[66] Sleep Mode Forces frequency converter into Sleep Mode
(see parameter group 22-4*). Reacts on the
rising edge of signal applied!
[68] Timed Actions
Disabled
Timed actions are disabled. See parameter
group 23-0* Timed Actions.
[69] Constant OFF
Timed Actions are set for Constant OFF. See
parameter group 23-0* Timed Actions.
[70] Constant ON
Timed Actions are set for Constant ON. See
parameter group 23-0* Timed Actions.
[78] Reset
Preventive
Maintenance
Word
Resets all data in 16-96 Maintenance Word
to 0.
[80] PTC Card 1 All Digital Inputs can be set to PTC Card 1
[80]. However, only one Digital Input must
be set to this choice.
5-10 Terminal 18 Digital Input
Same options and functions as parameter group 5-1*, except for
Pulse input.
Option: Function:
[8] * Start
5-11 Terminal 19 Digital Input
Same options and functions as parameter group 5-1*, except for
Pulse input.
Option: Function:
[0] * No operation
5-12 Terminal 27 Digital Input
Option: Function:
[2] * Coast inverse Functions are described under parameter
group 5-1* Digital Inputs
3.7.4 5-13 Terminal 29 Digital Input
5-13 Terminal 29 Digital Input
Option: Function:
Select the function from the available digital input
range and the additional options [60], [61], [63] and
[64]. Counters are used in Smart Logic Control
functions.
[14] * Jog
Functions are described under 5-1* Digital Inputs
5-14 Terminal 32 Digital Input
Option: Function:
[0] * No Operation Same options and functions as parameter
group 5-1* Digital Inputs, except for Pulse
input.
5-15 Terminal 33 Digital Input
Option: Function:
[0] * No Operation Same options and functions as parameter
group 5-1* Digital Inputs.
5-16 Terminal X30/2 Digital Input
This parameter is active when option module MCB 101 is
installed in the frequency converter. Same options and functions
as parameter group 5-1* except for Pulse input [32].
Option: Function:
[0] * No operation
5-17 Terminal X30/3 Digital Input
This parameter is active when option module MCB 101 is
installed in the frequency converter. Same options and functions
as parameter group 5-1* except for Pulse input [32].
Option: Function:
[0] * No operation
5-18 Terminal X30/4 Digital Input
This parameter is active when option module MCB 101 is
installed in the frequency converter. Same options and functions
as parameter group 5-1* except for Pulse input [32].
Option: Function:
[0] * No operation
5-19 Terminal 37 Safe Stop
Option: Function:
[1]
*
Safe Stop
Alarm
Coasts frequency converter when safe stop is
activated. Manual reset from LCP, digital
input or fieldbus.
[3] Safe Stop
Warning
Coasts frequency converter when safe stop is
activated (T-37 off). When safe stop circuit is
reestablished, the frequency converter will
continue without manual reset.
[4] PTC 1 Alarm Coasts frequency converter when safe stop is
activated. Manual reset from LCP, digital
input or fieldbus. Choice 4 is only available
when the MCB 112 PTC Thermistor Card is
connected.
[5] PTC 1
Warning
Coasts frequency converter when safe stop is
activated (T-37 off). When safe stop circuit is
reestablished, the frequency converter will
continue without manual reset, unless a
Digital Input set to PTC Card 1 [80] is still
enabled. Choice 5 is only available when the
MCB 112 PTC Thermistor Card is connected.
[6] PTC 1 &
Relay A
This choice is used when the PTC option is
gated together with a Stop button through a
Safety relay to T-37. Coasts frequency
converter when safe stop is activated. Manual
reset from LCP, digital input or fieldbus.
Choice 6 is only available when the MCB 112
PTC Thermistor Card is connected.
[7] PTC 1 &
Relay W
This choice is used when the PTC option is
gated together with a Stop button through a
Safety relay to T-37. Coasts frequency
converter when safe stop is activated (T-37
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG11CD02 - VLT
®
is a registered Danfoss trademark 65