Technical information
3.3.4 1-2* Motor Data
Parameter group 1-2* comprises input data from the
nameplate on the connected motor.
NOTE
Changing the value of these parameters affects the setting
of other parameters.
NOTE
1-20 Motor Power [kW], 1-21 Motor Power [HP], 1-22 Motor
Voltage and 1-23 Motor Frequency will not have effect
when 1-10 Motor Construction = [1] PM, non salient SPM.
1-20 Motor Power [kW]
Range: Function:
Size
related*
[ 0.09 -
3000.00
kW]
Enter the nominal motor power in kW
according to the motor nameplate data.
The default value corresponds to the
nominal rated output of the unit.
This parameter cannot be adjusted
while the motor is running. Depending
on the choices made in 0-03 Regional
Settings, either 1-20 Motor Power [kW] or
1-21 Motor Power [HP] is made invisible.
1-21 Motor Power [HP]
Range: Function:
Size
related*
[ 0.09 -
3000.00 hp]
Enter the nominal motor power in HP
according to the motor nameplate data.
The default value corresponds to the
nominal rated output of the unit.
This parameter cannot be adjusted
while the motor is running.
Depending on the choices made in
0-03 Regional Settings, either 1-20 Motor
Power [kW] or 1-21 Motor Power [HP] is
made invisible.
1-22 Motor Voltage
Range: Function:
Size
related*
[ 10. -
1000. V]
Enter the nominal motor voltage
according to the motor nameplate
data. The default value corresponds to
the nominal rated output of the unit.
This parameter cannot be adjusted
while the motor is running.
1-23 Motor Frequency
Range: Function:
Size
related*
[20 -
1000 Hz]
Select the motor frequency value from
the motor nameplate data. For 87Hz
operation with 230/400 V motors, set the
nameplate data for 230V/50Hz. Adapt
1-23 Motor Frequency
Range: Function:
4-13 Motor Speed High Limit [RPM] and
3-03 Maximum Reference to the 87Hz
application.
NOTE
This parameter cannot be changed while the motor is
running.
1-24 Motor Current
Range: Function:
Size
related*
[ 0.10 -
10000.00 A]
Enter the nominal motor current
value from the motor nameplate
data. This data is used for
calculating motor torque, motor
thermal protection etc.
NOTE
This parameter cannot be changed while the motor is
running.
1-25 Motor Nominal Speed
Range: Function:
Size related* [100 - 60000
RPM]
Enter the nominal motor speed
value from the motor nameplate
data. This data is used for
calculating automatic motor
compensations.
NOTE
This parameter cannot be changed while the motor is
running.
1-26 Motor Cont. Rated Torque
Range: Function:
Size
related*
[0.1 -
10000.0 Nm]
Enter the value from the motor
nameplate data. The default value
corresponds to the nominal rated
output. This parameter is available
when 1-10 Motor Construction is set to
PM, non salient SPM [1], i.e. the
parameter is valid for PM and
nonsalient SPM motors only.
Parameter Description
VLT
®
HVAC Drive Programming Guide
38 MG11CD02 - VLT
®
is a registered Danfoss trademark