Technical information
1-06 Clockwise Direction
This parameter defines the term “Clockwise” corresponding to
the LCP direction arrow. Used for easy change of direction of
shaft rotation without swapping motor wires. (Valid from SW
version 5.84)
Option: Function:
[0] * Normal Motor shaft will turn in clockwise
direction when the frequency
converter is connected U -> U; V -
> V, and W -> W to motor.
[1] Inverse Motor shaft will turn in counter
clockwise direction when the
frequency converter is connected
U -> U; V -> V, and W -> W to
motor.
NOTE
This parameter cannot be changed while the motor is
running.
3.3.2 1-10 - 1-13 Motor Selection
NOTE
This parameter group cannot be adjusted while the motor
is running.
The following parameters are active ('x') depending on the
setting of 1-10 Motor Construction
1-10 Motor construction
[0]
Asynchron
[1] PM Motor
non salient
1-00 -Configuration mode
x x
1-03 Torque Characteristics
x
1-06 Clockwise direction
x x
1-14 Damping gain
x
1-15 High pass filter damp time low
speed
x
1-16 High pass filter damp time
high speed
x
1-17 Machine voltage filter time
x
1-20 Motor power [KW]
x
1-21 - Motor power [HP]
x
1-22 Motor Voltage
x
1-23 Motor frequency
x
1-24 Motor current
x x
1-25 Motor Nom. speed
x x
1-26 Motor rated torque
x
1-28 Motor rotation check
x x
1-29 AMA
x
1-30 RS
x x
1-31 Rr
x
1-35 Xh
x
1-37 Ld
x
1-10 Motor construction
[0]
Asynchron
[1] PM Motor
non salient
1-38 Lq
1-39 Motor poles
x x
1-40 Back EMF
x
1-50 Motor Magnet. at 0 speed
x
1-51 Min Speed norm. magne. [rpm]
x
1-52 Min Speed norm. magne. [Hz]
x
1-58 Flystart test pulses current
x x
1-59 Flystart test pulses frequency
x x
1-60 Low Speed Load Compensation
x
1-61 High Speed Load Compen-
sation
x
1-62 Slip Compensation
x
1-63 Slip Compensation time const.
x
1-64 Resonance Damping
x
1-65 Resonance Damping time
const.
x
1-66 Min Current at low speed
x
1-70 PM Startmode
x
1-71 Start Delay
x x
1-72 Start Function
x x
1-73 Flying Start
x x
1-77 Compressor Max Start speed
[rpm]
x
1-78 Compressor Max Start speed
[Hz]
x
1-79 Compressor start max time to
trip
x
1-80 Stop Function
x x
1-81 Min Speed funct. at stop [rpm]
x x
1-82 Min Speed funct. at stop [Hz]
x x
1-86 Trip speed low [rpm]
x x
1-87 Trip speed low [Hz]
x x
1-90 Motor Thermal Protection
x x
1-91 Motor External Fan
x x
1-93 Thermistor Resource
x x
2-00 DC Hold current
x
2-01 DC Brake current
x x
2-02 DC Braking Time
x
2-03 DC Brake Cut In Speed [rpm]
x
2-04 DC Brake Cut In Speed [Hz]
x
2-06 Parking Current
x
2-07 Parking Time
x
2-10 Brake Function
x x
2-11 Brake Resistor
x x
2-12 Brake Power Limit
x x
2-13 Brake Power Monitoring
x x
2-15 Brake Check
x x
2-16 AC Brake Max Current
x
2-17 Over-voltage Control
x
4-10 Motor speed direction
x x
4-11 Motor speed low limit [rpm]
x x
4-12 Motor speed low limit [Hz]
x x
Parameter Description
VLT
®
HVAC Drive Programming Guide
36 MG11CD02 - VLT
®
is a registered Danfoss trademark
3
3