Technical information
130BT105.11
0
Custom Readout (Value)
P 16-09
Custom Readout
Unit P 0-30
Max value
P 0-32
Min value
P 0-31
Motor Speed
Motor Speed
High limit
P 4-13 (RPM)
P 4-14 (Hz)
Linear Unit (e.g. Speed and ow)
Quadratic Unit (Pressure)
Cubic Unit (Power)
Liniar
units only
The relation will depend on the type of unit selected in
0-30 Custom Readout Unit:
Unit Type Speed Relation
Dimensionless
Linear
Speed
Flow, volume
Flow, mass
Velocity
Length
Temperature
Pressure Quadratic
Power Cubic
0-30 Custom Readout Unit
Option: Function:
Program a value to be shown in the display of
the LCP. The value has a linear, squared or cubed
relation to speed. This relation depends on the
unit selected (see Table 3.3). The actual calculated
value can be read in 16-09 Custom Readout,
and/or shown in the display be selecting Custom
Readout [16-09] in 0-20 Display Line 1.1 Small to
0-24 Display Line 3 Large.
[0] None
[1] * %
[5] PPM
[10] 1/min
[11] RPM
[12] Pulse/s
[20] l/s
[21] l/min
[22] l/h
[23] m³/s
[24] m³/min
[25] m³/h
[30] kg/s
[31] kg/min
[32] kg/h
[33] t/min
[34] t/h
0-30 Custom Readout Unit
Option: Function:
[40] m/s
[41] m/min
[45] m
[60] °C
[70] mbar
[71] bar
[72] Pa
[73] kPa
[74] m WG
[75] mm Hg
[80] kW
[120] GPM
[121] gal/s
[122] gal/min
[123] gal/h
[124] CFM
[125] ft³/s
[126] ft³/min
[127] ft³/h
[130] lb/s
[131] lb/min
[132] lb/h
[140] ft/s
[141] ft/min
[145] ft
[160] °F
[170] psi
[171] lb/in²
[172] in WG
[173] ft WG
[174] in Hg
[180] HP
0-31 Custom Readout Min Value
Range: Function:
Size
related*
[ 0.00 - 100.00
CustomRea-
doutUnit]
This parameter allows the choice
of the min. value of the custom
defined readout (occurs at zero
speed). It is only possible to select
a value different to 0 when
selecting a linear unit in
0-30 Custom Readout Unit. For
Quadratic and Cubic units the
minimum value will be 0.
Parameter Description
VLT
®
HVAC Drive Programming Guide
30 MG11CD02 - VLT
®
is a registered Danfoss trademark
3
3