Technical information

0-20 Display Line 1.1 Small
Option: Function:
[1666] Digital Output
[bin]
Binary value of all digital outputs.
[1667] Pulse Input #29
[Hz]
Actual value of the frequency
applied at terminal 29 as a pulse
input.
[1668] Pulse Input #33
[Hz]
Actual value of the frequency
applied at terminal 33 as a pulse
input.
[1669] Pulse Output #27
[Hz]
Actual value of pulses applied to
terminal 27 in digital output mode.
[1670] Pulse Output #29
[Hz]
Actual value of pulses applied to
terminal 29 in digital output mode.
[1671] Relay Output [bin] View the setting of all relays.
[1672] Counter A View the present value of Counter
A.
[1673] Counter B View the present value of Counter
B.
[1675] Analog In X30/11 Actual value of the signal on input
X30/11 (General Purpose I/O Card.
Option)
[1676] Analog In X30/12 Actual value of the signal on input
X30/12 (General Purpose I/O Card.
Optional)
[1677] Analog Out X30/8
[mA]
Actual value at output X30/8
(General Purpose I/O Card. Optional)
Use 6-60 Terminal X30/8 Output to
select the variable to be shown.
[1680] Fieldbus CTW 1 Control word (CTW) received from
the Bus Master.
[1682] Fieldbus REF 1 Main reference value sent with
control word via the serial
communications network e.g. from
the BMS, PLC or other master
controller.
[1684] Comm. Option
STW
Extended fieldbus communication
option status word.
[1685] FC Port CTW 1 Control word (CTW) received from
the Bus Master.
[1686] FC Port REF 1 Status word (STW) sent to the Bus
Master.
[1690] Alarm Word One or more alarms in a Hex code
(used for serial communications)
[1691] Alarm Word 2 One or more alarms in a Hex code
(used for serial communications)
[1692] Warning Word One or more warnings in a Hex
code (used for serial communi-
cations)
0-20 Display Line 1.1 Small
Option: Function:
[1693] Warning Word 2 One or more warnings in a Hex
code (used for serial communi-
cations)
[1694] Ext. Status Word One or more status conditions in a
Hex code (used for serial communi-
cations)
[1695] Ext. Status Word 2 One or more status conditions in a
Hex code (used for serial communi-
cations)
[1696] Maintenance
Word
The bits reflect the status for the
programmed Preventive
Maintenance Events in parameter
group 23-1*
[1830] Analog Input
X42/1
Shows the value of the signal
applied to terminal X42/1 on the
Analog I/O card.
[1831] Analog Input
X42/3
Shows the value of the signal
applied to terminal X42/3 on the
Analog I/O card.
[1832] Analog Input
X42/5
Shows the value of the signal
applied to terminal X42/5 on the
Analog I/O card.
[1833] Analog Out X42/7
[V]
Shows the value of the signal
applied to terminal X42/7 on the
Analog I/O card.
[1834] Analog Out X42/9
[V]
Shows the value of the signal
applied to terminal X42/9 on the
Analog I/O card.
[1835] Analog Out
X42/11 [V]
Shows the value of the signal
applied to terminal X42/11 on the
Analog I/O card.
[1836] Analog Input
X48/2 [mA]
[1837] Temp. Input
X48/4
[1838] Temp. Input
X48/7
[1839] Temp. Input
X48/10
[1850] Sensorless
Readout [unit]
[2117] Ext. 1 Reference
[Unit]
The value of the reference for
extended Closed Loop Controller 1
[2118] Ext. 1 Feedback
[Unit]
The value of the feedback signal for
extended Closed Loop Controller 1
[2119] Ext. 1 Output [%] The value of the output from
extended Closed Loop Controller 1
[2137] Ext. 2 Reference
[Unit]
The value of the reference for
extended Closed Loop Controller 2
Parameter Description
VLT
®
HVAC Drive Programming Guide
28 MG11CD02 - VLT
®
is a registered Danfoss trademark
3