Technical information

0-20 Display Line 1.1 Small
Option: Function:
[1605] Main Actual Value
[%]
View the two-byte word sent with
the Status word to the bus Master
reporting the Main Actual Value.
[1609] Custom Readout View the user-defined readouts as
defined in 0-30 Custom Readout
Unit, 0-31 Custom Readout Min Value
and 0-32 Custom Readout Max Value.
[1610] Power [kW] Actual power consumed by the
motor in kW.
[1611] Power [hp] Actual power consumed by the
motor in HP.
[1612] Motor Voltage Voltage supplied to the motor.
[1613] Frequency Motor frequency, i.e. the output
frequency from the frequency
converter in Hz.
[1614] Motor Current Phase current of the motor
measured as effective value.
[1615] Frequency [%] Motor frequency, i.e. the output
frequency from the frequency
converter in percent.
[1616] Torque [Nm] Present motor load as a percentage
of the rated motor torque.
[1617] Speed [RPM] Motor speed reference. Actual
speed will depend on slip compen-
sation being used (compensation
set in 1-62 Slip Compensation). If not
used, actual speed will be the value
read in the display minus motor
slip.
[1618] Motor Thermal Thermal load on the motor,
calculated by the ETR function. See
also parameter group 1-9* Motor
Temperature.
[1622] Torque [%] Shows the actual torque produced,
in percentage.
[1626] Power Filtered
[kW]
[1627] Power Filtered
[hp]
[1630] DC Link Voltage Intermediate circuit voltage in the
frequency converter.
[1632] Brake Energy /s Present brake power transferred to
an external brake resistor.
Stated as an instantaneous value.
[1633] Brake Energy /2
min
Brake power transferred to an
external brake resistor. The mean
power is calculated continuously for
the most recent 120 seconds.
0-20 Display Line 1.1 Small
Option: Function:
[1634] Heatsink Temp. Present heat sink temperature of
the frequency converter. The cut-
out limit is 95 ± 5° C; cutting back
in occurs at 70 ± 5° C.
[1635] Inverter Thermal Percentage load of the inverters
[1636] Inv. Nom. Current Nominal current of the frequency
converter
[1637] Inv. Max. Current Maximum current of the frequency
converter
[1638] SL Controller
State
State of the event executed by the
control
[1639] Control Card
Temp.
Temperature of the control card.
[1643] Timed Actions
Status
See parameter group 23-0* Timed
Actions.
[1650] External Reference Sum of the external reference as a
percentage, i.e. the sum of analog/
pulse/bus.
[1652] Feedback [Unit] Reference value from programmed
digital input(s).
[1653] Digi Pot Reference View the contribution of the digital
potentiometer to the actual
reference Feedback.
[1654] Feedback 1 [Unit] View the value of Feedback 1. See
also par. 20-0*.
[1655] Feedback 2 [Unit] View the value of Feedback 2. See
also par. 20-0*.
[1656] Feedback 3 [Unit] View the value of Feedback 3. See
also par. 20-0*.
[1658] PID Output [%] Returns the Drive Closed Loop PID
controller output value in percent.
[1660] Digital Input Displays the status of the digital
inputs. Signal low = 0; Signal high =
1.
Regarding order, see 16-60 Digital
Input. Bit 0 is at the extreme right.
[1661] Terminal 53
Switch Setting
Setting of input terminal 53. Current
= 0; Voltage = 1.
[1662] Analog Input 53 Actual value at input 53 either as a
reference or protection value.
[1663] Terminal 54
Switch Setting
Setting of input terminal 54. Current
= 0; Voltage = 1.
[1664] Analog Input 54 Actual value at input 54 either as
reference or protection value.
[1665] Analog Output 42
[mA]
Actual value at output 42 in mA.
Use 6-50 Terminal 42 Output to
select the variable to be
represented by output 42.
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG11CD02 - VLT
®
is a registered Danfoss trademark 27
3