Technical information
0-13 Readout: Linked Set-ups
Array [5]
Range: Function:
0 * [0 - 255 ]
View a list of all the set-ups linked by means of
0-12 This Set-up Linked to. The parameter has one
index for each parameter set-up. The parameter
value displayed for each index represents which
setups are linked to that parameter setup.
Index LCP value
0 {0}
1 {1,2}
2 {1,2}
3 {3}
4 {4}
Table 3.2 Example: Set-up 1 and Set-up 2 are
linked
0-14 Readout: Prog. Set-ups / Channel
Range: Function:
0 * [-2147483648
- 2147483647 ]
View the setting of 0-11 Programming Set-
up for each of the four different
communication channels. When the
number is displayed in hex, as it is in the
LCP, each number represents one channel.
Numbers 1-4 represent a set-up number; ‘F’
means factory setting; and ‘A’ means active
set-up. The channels are, from right to left:
LCP, FC-bus, USB, HPFB1.5.
Example: The number AAAAAA21h means
that the FC-bus selected Set-up 2 in
0-11 Programming Set-up, the LCP selected
Set-up 1 and all others used the active set-
up.
3.2.3
0-2* LCP Display
Define the variables displayed in the Graphical Local
Control Panel.
NOTE
Please refer to 0-37 Display Text 1, 0-38 Display Text 2 and
0-39 Display Text 3 for information on how to write display
texts.
0-20 Display Line 1.1 Small
Option: Function:
Select a variable for display in line
1, left position.
[0] * None No display value selected
0-20 Display Line 1.1 Small
Option: Function:
[37] Display Text 1 Enables an individual text string to
be written, for display in the LCP or
to be read via serial communication.
[38] Display Text 2 Enables an individual text string to
be written, for display in the LCP or
to be read via serial communication.
[39] Display Text 3 Enables an individual text string to
be written, for display in the LCP or
to be read via serial communication.
[89] Date and Time
Readout
Displays the current date and time.
[953] Profibus Warning
Word
Displays Profibus communication
warnings.
[1005] Readout Transmit
Error Counter
View the number of CAN control
transmission errors since the last
power-up.
[1006] Readout Receive
Error Counter
View the number of CAN control
receipt errors since the last power-
up.
[1007] Readout Bus Off
Counter
View the number of Bus Off events
since the last power-up.
[1013] Warning
Parameter
View a DeviceNet-specific warning
word. One separate bit is assigned
to every warning.
[1115] LON Warning
Word
Shows the LON-specific warnings.
[1117] XIF Revision Shows the version of the external
interface file of the Neuron C chip
on the LON option.
[1118] LonWorks
Revision
Shows the software version of the
application program of the Neuron
C chip on the LON option.
[1230] Warning
Parameter
[1501] Running Hours View the number of running hours
of the motor.
[1502] kWh Counter View the mains power consumption
in kWh.
[1600] Control Word View the Control Word sent from
the frequency converter via the
serial communication port in hex
code.
[1601] Reference [Unit] Total reference (sum of digital/
analog/preset/bus/freeze ref./catch
up and slow-down) in selected unit.
[1602] * Reference [%] Total reference (sum of digital/
analog/preset/bus/freeze ref./catch
up and slow-down) in percent.
[1603] Status Word Present status word
Parameter Description
VLT
®
HVAC Drive Programming Guide