Technical information
Use 3-10 Preset Reference as another example:
Choose the parameter, press [OK], and use the up/down
navigation keys keys to scroll through the indexed values.
To change the parameter value, select the indexed value
and press [OK]. Change the value by using the up/down
keys. Press [OK] to accept the new setting. Press [Cancel]
to abort. Press [Back] to leave the parameter.
2.1.14 Initialisation to Default Settings
Initialise the frequency converter to default settings in two
ways.
Recommended initialisation (via 14-22 Operation Mode)
1.
Select 14-22 Operation Mode
2. Press [OK]
3. Select “initialisation”
4. Press [OK]
5. Cut off the mains supply and wait until the
display turns off.
6. Reconnect the mains supply - the frequency
converter is now reset.
7.
Change 14-22 Operation Mode back to Normal
Operation.
NOTE
Resets parameters selected in Personal Menu with default
factory setting.
14-22 Operation Mode initialises all except
14-50 RFI Filter
8-30 Protocol
8-31 Address
8-32 Baud Rate
8-35 Minimum Response Delay
8-36 Maximum Response Delay
8-37 Maximum Inter-Char Delay
15-00 Operating Hours to 15-05 Over Volt's
15-20 Historic Log: Event to 15-22 Historic Log: Time
15-30 Alarm Log: Error Code to 15-32 Alarm Log:
Time
Manual initialisation
1. Disconnect from mains and wait until the display turns
off.
2a. Press [Status] - [Main Menu] - [OK] at the same time
while power up for LCP 102, Graphical Display
2b. Press [Menu] while power up for LCP 101, Numerical
Display
3. Release the keys after 5 seconds
4. The frequency converter is now programmed according
to default settings.
This procedure initialises all except: 15-00 Operating Hours;
15-03 Power Up's; 15-04 Over Temp's; 15-05 Over Volt's.
NOTE
When you carry out manual initialisation, you also reset
serial communication, 14-50 RFI Filter and fault log settings.
Removes parameters selected in 25-00 Cascade Controller.
NOTE
After initialisation and power cycling, the display will not
show any information until after a couple of minutes.
How to Programme
VLT
®
HVAC Drive Programming Guide
MG11CD02 - VLT
®
is a registered Danfoss trademark 21
2 2