Technical information
No. Description Warning Alarm/
Trip
Alarm/Trip Lock Parameter Reference
93 Dry Pump X X 22-2*
94 End of Curve X X 22-5*
95 Broken Belt X X 22-6*
96 Start Delayed X 22-7*
97 Stop Delayed X 22-7*
98 Clock Fault X 0-7*
201 Fire M was Active
202 Fire M Limits Exceeded
203 Missing Motor
204 Locked Rotor
243 Brake IGBT X X
244 Heatsink temp X X X
245 Heatsink sensor X X
246 Pwr.card supply X X
247 Pwr.card temp X X
248 Illegal PS config X X
250 New spare parts X
251 New Type Code X X
Table 4.1 Alarm/Warning code list
(X) Dependent on parameter
1) Can not be Auto reset via 14-20 Reset Mode
A trip is the action when an alarm has appeared. The trip
will coast the motor and can be reset by pressing the reset
button or make a reset by a digital input (parameter group
5-1* [1]). The original event that caused an alarm cannot
damage the frequency converter or cause dangerous
conditions. A trip lock is an action when an alarm occurs,
which may cause damage to frequency converter or
connected parts. A Trip Lock situation can only be reset by
a power cycling.
LED indication
Warning yellow
Alarm flashing red
Trip locked yellow and red
Troubleshooting
VLT
®
HVAC Drive Programming Guide
MG11CD02 - VLT
®
is a registered Danfoss trademark 193
4 4