Technical information
3.24 Main Menu - Analog I/O Option MCB 109 - Group 26
The Analog I/O Option MCB 109 extends the functionality of VLT
®
HVAC Drive frequency converters, by adding a number of
additional, programmable analog inputs and outputs. This could be especially useful in Building Management System instal-
lations where the frequency converter may be used as de-central I/O, obviating the need for an outstation and thus
reducing cost.
Consider the diagram
130BA382.10
M
M
M
P T
T
T
H
Analog I/O Carsd Control Card Power card
Room temperature
Supply temperature
Outdoor temperature
Heating Coil
Cooling coil
Dampers or
Heat recover Wheel
Humidier
Duct Pressure
Humidity sensor
Humidier steps
or
Cooling steps
RELAY1
RELAY2
1 2 3 10 11 124 5 6 7 8 9 12 13 18 19 27 29 32 33 20 37 39 42 50 53 54 55 01 02 03 04 05 06
130BA381.10
X42
AIN
AIN
AIN
AOUT
AOUT
AOUT
24VDC
24VDC
DIN
DIN
DIN/DOUT
DIN/DOUT
DIN
DIN
AOUT
AIN
AIN
This shows a typical Air Handling Unit (AHU). As can be seen, the addition of the Analog I/O option offers the possibility to
control all of the functions from the frequency converter, such as inlet-, return- and exhaust dampers or heating/cooling
coils with temperature and pressure measurements being read by the frequency converter.