Technical information

24-96 Locked Rotor Coefficient 1
Range: Function:
0.0000 * [-10.0000 -
10.0000 ]
Enter the cubic coefficient of the
Locked Rotor detection function
multiplied by 1000.
24-97 Locked Rotor Coefficient 2
Range: Function:
0.0000 * [-100.0000 -
100.0000 ]
Enter the quadratic coefficient of
the Locked Rotor detection
function multiplied by 1000.
24-98 Locked Rotor Coefficient 3
Range: Function:
0.0000 * [-100.0000 -
100.0000 ]
Enter the linear coefficient of
the Locked Rotor detection
function.
24-99 Locked Rotor Coefficient 4
Range: Function:
0.000 * [-500.000 - 500.000 ] Enter the constant of the Locked
Rotor detection function.
Parameter Description
VLT
®
HVAC Drive Programming Guide
174 MG11CD02 - VLT
®
is a registered Danfoss trademark
3
3