Technical information
exceed rated value, but those registrations will be included
in 90%-100% (MAX) counter.
Relative value
operating variable
Counter 1: +1
Counter 0: +5
Counter 2: +0
Counter 3: +1
Counter 4: +0
Counter 5: +11
Counter 6: +1
Counter 7: +2
Counter 8: +6
Counter 9: +0
130BA281.10
80
70
50
60
30
40
10
20
%
90
100
Once a second, the value of the operating variable
selected is registered. If a value has been registered to
equal 13%, the counter “10% - <20%” will be updated with
the value “1”. If the value stays at 13% for 10s, then “10”
will be added to the counter value.
The contents of counters can be displayed as bars on LCP.
Select Quick Menu >Loggings: Trending Continued Bin /
Trending Timed Bin / Trending Comparison.
NOTE
The counters starts counting whenever the frequency
converter is powered-up. Power cycle shortly after a reset
will zero the counters. EEProm data are updated once per
hour.
23-60 Trend Variable
Option: Function:
Select the desired operating variable to be
monitored for Trending.
[0] * Power [kW] Power yielded to the motor. Reference for
the relative value is the rated motor power
programmed in 1-20 Motor Power [kW] or
1-21 Motor Power [HP]. Actual value can be
read in 16-10 Power [kW] or 16-11 Power [hp].
[1] Current [A] Output current to the motor. Reference for
the relative value is the rated motor current
programmed in 1-24 Motor Current. Actual
value can be read in 16-14 Motor Current.
[2] Frequency
[Hz]
Output frequency to the motor. Reference
for the relative value is the maximum output
frequency programmed in 4-14 Motor Speed
High Limit [Hz]. Actual value can be read in
16-13 Frequency.
[3] Motor Speed
[RPM]
Speed of the motor. Reference for relative
value is the maximum motor speed
programmed in 4-13 Motor Speed High Limit
[RPM].
23-61 Continuous Bin Data
Range: Function:
0
*
[0 -
4294967295 ]
Array with 10 elements ([0]-[9] below
parameter number in display). Press OK and
step between elements by means of
▲
and
▼
buttons on the LCP.
10 counters with the frequency of
occurrence for the operating variable
monitored, sorted according to the
following intervals:
Counter [0]: 0% - <10%
Counter [1]: 10% - <20%
Counter [2]. 20% - <30%
Counter [3]: 30% - <40%
Counter [4]: 40% - <50%
Counter [5]: 50% - <60%
Counter [6]. 60% - <70%
Counter [7]: 70% - <80%
Counter [8]. 80% - <90%
Counter [9]: 90% - <100% or Max
The above minimum limits for the intervals
are the default limits. These can be changed
in 23-65 Minimum Bin Value.
Starts to count when the frequency
converter is powered up for the first time.
All counters can be reset to 0 in 23-66 Reset
Continuous Bin Data.
23-62 Timed Bin Data
Range: Function:
0 * [0 -
4294967295 ]
Array with 10 elements ([0]-[9] below
parameter number in display). Press OK and
step between elements by means of
▲
and
▼
buttons on the LCP.
10 counters with the frequency of
occurrence for the operating data
monitored sorted according to the intervals
as for 23-61 Continuous Bin Data.
Starts to count at the date/time
programmed in 23-63 Timed Period Start,
and stops at the time/date programmed in
23-64 Timed Period Stop. All counters can be
reset to 0 in 23-67 Reset Timed Bin Data.
Parameter Description
VLT
®
HVAC Drive Programming Guide
166 MG11CD02 - VLT
®
is a registered Danfoss trademark
3