Technical information

exceed rated value, but those registrations will be included
in 90%-100% (MAX) counter.
Relative value
operating variable
Counter 1: +1
Counter 0: +5
Counter 2: +0
Counter 3: +1
Counter 4: +0
Counter 5: +11
Counter 6: +1
Counter 7: +2
Counter 8: +6
Counter 9: +0
130BA281.10
80
70
50
60
30
40
10
20
%
90
100
Once a second, the value of the operating variable
selected is registered. If a value has been registered to
equal 13%, the counter “10% - <20%” will be updated with
the value “1”. If the value stays at 13% for 10s, then “10”
will be added to the counter value.
The contents of counters can be displayed as bars on LCP.
Select Quick Menu >Loggings: Trending Continued Bin /
Trending Timed Bin / Trending Comparison.
NOTE
The counters starts counting whenever the frequency
converter is powered-up. Power cycle shortly after a reset
will zero the counters. EEProm data are updated once per
hour.
23-60 Trend Variable
Option: Function:
Select the desired operating variable to be
monitored for Trending.
[0] * Power [kW] Power yielded to the motor. Reference for
the relative value is the rated motor power
programmed in 1-20 Motor Power [kW] or
1-21 Motor Power [HP]. Actual value can be
read in 16-10 Power [kW] or 16-11 Power [hp].
[1] Current [A] Output current to the motor. Reference for
the relative value is the rated motor current
programmed in 1-24 Motor Current. Actual
value can be read in 16-14 Motor Current.
[2] Frequency
[Hz]
Output frequency to the motor. Reference
for the relative value is the maximum output
frequency programmed in 4-14 Motor Speed
High Limit [Hz]. Actual value can be read in
16-13 Frequency.
[3] Motor Speed
[RPM]
Speed of the motor. Reference for relative
value is the maximum motor speed
programmed in 4-13 Motor Speed High Limit
[RPM].
23-61 Continuous Bin Data
Range: Function:
0
*
[0 -
4294967295 ]
Array with 10 elements ([0]-[9] below
parameter number in display). Press OK and
step between elements by means of
and
buttons on the LCP.
10 counters with the frequency of
occurrence for the operating variable
monitored, sorted according to the
following intervals:
Counter [0]: 0% - <10%
Counter [1]: 10% - <20%
Counter [2]. 20% - <30%
Counter [3]: 30% - <40%
Counter [4]: 40% - <50%
Counter [5]: 50% - <60%
Counter [6]. 60% - <70%
Counter [7]: 70% - <80%
Counter [8]. 80% - <90%
Counter [9]: 90% - <100% or Max
The above minimum limits for the intervals
are the default limits. These can be changed
in 23-65 Minimum Bin Value.
Starts to count when the frequency
converter is powered up for the first time.
All counters can be reset to 0 in 23-66 Reset
Continuous Bin Data.
23-62 Timed Bin Data
Range: Function:
0 * [0 -
4294967295 ]
Array with 10 elements ([0]-[9] below
parameter number in display). Press OK and
step between elements by means of
and
buttons on the LCP.
10 counters with the frequency of
occurrence for the operating data
monitored sorted according to the intervals
as for 23-61 Continuous Bin Data.
Starts to count at the date/time
programmed in 23-63 Timed Period Start,
and stops at the time/date programmed in
23-64 Timed Period Stop. All counters can be
reset to 0 in 23-67 Reset Timed Bin Data.
Parameter Description
VLT
®
HVAC Drive Programming Guide
166 MG11CD02 - VLT
®
is a registered Danfoss trademark