Technical information

6. To move to a different digit within a parameter
setting, use the [
] and [
] buttons
7. Highlighted area indicates digit selected for
change
8. Press [Cancel] button to disregard change, or
press [OK] to accept change and enter the new
setting
Example of changing parameter data
Assume 22-60 Broken Belt Function is set to [Off]. However,
you want to monitor the fan-belt condition - non- broken
or broken - according to the following procedure
1. Press Quick Menu key
2.
Choose Function Setups with the [
] button
3. Press [OK]
4.
Choose Application Settings with the [
] button
5. Press [OK]
6. Press [OK] again for Fan Functions
7. Choose Broken Belt Function by pressing [OK]
8.
With [
] button, choose [2] Trip
The frequency converter will now trip if a broken fan-belt
is detected.
Select [My Personal Menu] to display personal parameters
For example, an AHU or pump OEM may have pre-
programmed personal parameters to be in My Personal
Menu during factory commissioning to make on-site
commissioning/fine tuning simpler. These parameters are
selected in 0-25 My Personal Menu. Up to 20 different
parameters can be programmed in this menu.
Select [Changes Made] to get information about
The last 10 changes. Use the up/down navigation
keys to scroll between the last 10 changed
parameters.
The changes made since default setting.
Select [Loggings]
to get information about the display line read-outs. The
information is shown as graphs.
Only display parameters selected in 0-20 Display Line 1.1
Small and 0-24 Display Line 3 Large can be viewed. It is
possible to store up to 120 samples in the memory for
later reference.
Quick Setup
Efficient Parameter Set-up for VLT
®
HVAC Drive
Applications
The parameters can easily be set up for the vast majority
of the VLT
®
HVAC Drive applications only by using the
[Quick Setup] option.
After pressing [Quick Menu], the different choices in the
Quick Menu are listed. See also illustration 6.1 below and
tables Q3-1 to Q3-4 in the following Function Setups
section.
Example of using the Quick Setup option
Assume you want to set the Ramp Down Time to 100
seconds:
1.
Select [Quick Setup]. 0-01 Language in Quick
Setup appears
2.
Press [
] repeatedly until 3-42 Ramp 1 Ramp
Down Time appears with the default setting of 20
seconds
3. Press [OK]
4.
Use the [
] button to highlight the 3rd digit
before the comma
5.
Change '0' to '1' by using the [
] button
6.
Use the [
] button to highlight the digit '2'
7.
Change '2' to '0' with the [
] button
8. Press [OK]
The new ramp-down time is now set to 100 sec.
It is recommended to do the set-up in the order listed.
NOTE
A complete description of the function is found in
3 Parameter Description.
130BP064.10
Q1 My Personal Menu
Q2 Quick Setup
Q3 Function Setups
Q5 Changes Made
40.0% 4.84 A 1(1)
Quick Menus
Illustration 2.5 Quick Menu View
The Quick Setup menu gives access to the 18 most
important setup parameters of the frequency converter.
After programming the frequency converter will, in most
cases, be ready for operation. The 18 Quick Setup
parameters are shown in the table below. A complete
description of the function is given in the parameter
description sections of this manual.
How to Programme
VLT
®
HVAC Drive Programming Guide
MG11CD02 - VLT
®
is a registered Danfoss trademark 15