Technical information
NOTE
This parameter is only available when using pressure to
temperature feedback conversion.
If the choice Linear [0] is selected in 20-01 Feedback 1
Conversion, then the setting of any choice in
20-02 Feedback 1 Source Unit does not matter as conversion
will be one-to-one.
20-03 Feedback 2 Source
Option: Function:
See 20-00 Feedback 1 Source for
details.
[0] * No function
[1] Analog input 53
[2] Analog input 54
[3] Pulse input 29
[4] Pulse input 33
[7] Analog input X30/11
[8] Analog input X30/12
[9] Analog Input X42/1
[10] Analog Input X42/3
[11] Analog Input X42/5
[15] Analog Input X48/2
[100] Bus feedback 1
[101] Bus feedback 2
[102] Bus feedback 3
20-04 Feedback 2 Conversion
Option: Function:
See 20-01 Feedback 1 Conversion
for details.
[0] * Linear
[1] Square root
[2] Pressure to temperature
[3] Pressure to flow
[4] Velocity to flow
20-05 Feedback 2 Source Unit
Option: Function:
See 20-02 Feedback 1 Source Unit for details.
20-06 Feedback 3 Source
Option: Function:
See 20-00 Feedback 1 Source for
details.
[0] * No function
[1] Analog input 53
[2] Analog input 54
[3] Pulse input 29
[4] Pulse input 33
[7] Analog input X30/11
[8] Analog input X30/12
[9] Analog Input X42/1
[10] Analog Input X42/3
20-06 Feedback 3 Source
Option: Function:
[11] Analog Input X42/5
[15] Analog Input X48/2
[100] Bus feedback 1
[101] Bus feedback 2
[102] Bus feedback 3
20-07 Feedback 3 Conversion
Option: Function:
See 20-01 Feedback 1 Conversion
for details.
[0] * Linear
[1] Square root
[2] Pressure to temperature
[3] Pressure to flow
[4] Velocity to flow
20-08 Feedback 3 Source Unit
Option: Function:
See 20-02 Feedback 1 Source Unit for details.
20-12 Reference/Feedback Unit
Option: Function:
See 20-02 Feedback 1 Source Unit for details.
20-13 Minimum Reference/Feedb.
Range: Function:
0.000
ProcessCtrlUnit*
[ -999999.999 -
par. 20-14
ProcessCtrlUnit]
Enter the desired minimum
value for the remote
reference when operating
with 1-00 Configuration
Mode set for Closed Loop
[3] operation. Units are set
in 20-12 Reference/Feedback
Unit.
Minimum feedback will be
-200% of either the value
set in 20-13 Minimum
Reference/Feedb. or in
20-14 Maximum Reference/
Feedb., which ever numeric
value is the highest.
NOTE
If operating with 1-00 Configuration Mode set for Open
Loop [0], 3-02 Minimum Reference must be used.
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG11CD02 - VLT
®
is a registered Danfoss trademark 131