Technical information

16-56 Feedback 3 [Unit]
Range: Function:
0.000
ProcessCtrlUnit*
[-999999.999 -
999999.999
ProcessCtrlUnit]
View value of Feedback 3,
see parameter group 20-0*
Feedback.
The value is limited by
settings in 20-13 Minimum
Reference/Feedb. and
20-14 Maximum Reference/
Feedb.. Units as set in
20-12 Reference/Feedback
Unit.
16-58 PID Output [%]
Range: Function:
0.0 %* [0.0 - 100.0 %] This parameter returns the Drive Closed
Loop PID controller output value in
percent.
3.16.4 16-6* Inputs and Outputs
16-60 Digital Input
Range: Function:
0
*
[0 -
1023 ]
View the signal states from the active digital inputs.
Example: Input 18 corresponds to bit no. 5, ‘0’ = no
signal, ‘1’ = connected signal. Bit 6 works in the
opposite way, on = '0', off = '1' (safe stop input).
Bit 0 Digital input term. 33
Bit 1 Digital input term. 32
Bit 2 Digital input term. 29
Bit 3 Digital input term. 27
Bit 4 Digital input term. 19
Bit 5 Digital input term. 18
Bit 6 Digital input term. 37
Bit 7 Digital input GP I/O term. X30/4
Bit 8 Digital input GP I/O term. X30/3
Bit 9 Digital input GP I/O term. X30/2
Bit 10-63 Reserved for future terminals
16-61 Terminal 53 Switch Setting
Option: Function:
View the setting of input terminal 53. Current =
0; Voltage = 1.
[0] Current
[1] Voltage
[2] Pt 1000 [°C]
[3] Pt 1000 [°F]
[4] Ni 1000 [°C]
[5] Ni 1000 [°F]
16-62 Analog Input 53
Range: Function:
0.000 * [-20.000 - 20.000 ] View the actual value at input 53.
16-63 Terminal 54 Switch Setting
Option: Function:
View the setting of input terminal 54. Current =
0; Voltage = 1.
[0] Current
[1] Voltage
[2] Pt 1000 [°C]
[3] Pt 1000 [°F]
[4] Ni 1000 [°C]
[5] Ni 1000 [°F]
16-64 Analog Input 54
Range: Function:
0.000 * [-20.000 - 20.000 ] View the actual value at input 54.
16-65 Analog Output 42 [mA]
Range: Function:
0.000 * [0.000 -
30.000 ]
View the actual value at output 42 in
mA. The value shown reflects the
selection in 6-50 Terminal 42 Output.
16-66 Digital Output [bin]
Range: Function:
0 * [0 - 15 ] View the binary value of all digital outputs.
16-67 Pulse Input #29 [Hz]
Range: Function:
0 * [0 - 130000 ] View the actual frequency rate on terminal
29.
16-68 Pulse Input #33 [Hz]
Range: Function:
0 * [0 - 130000 ] View the actual value of the frequency
applied at terminal 33 as an impulse input.
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG11CD02 - VLT
®
is a registered Danfoss trademark 123