Technical information

13-52 SL Controller Action
Array [20]
Option: Function:
[2] Select set-up 1
Changes the active set-up (0-10 Active
Set-up) to ‘1’.
[3] Select set-up 2
Changes the active set-up (0-10 Active
Set-up) to ‘2’.
[4] Select set-up 3
Changes the active set-up (0-10 Active
Set-up) to ‘3’.
[5] Select set-up 4
Changes the active set-up (0-10 Active
Set-up) to ‘4’. If the set-up is changed,
it will merge with other set-up
commands coming from either the
digital inputs or via a fieldbus.
[10] Select preset ref 0 Selects preset reference 0.
[11] Select preset ref 1 Selects preset reference 1.
[12] Select preset ref 2 Selects preset reference 2.
[13] Select preset ref 3 Selects preset reference 3.
[14] Select preset ref 4 Selects preset reference 4.
[15] Select preset ref 5 Selects preset reference 5.
[16] Select preset ref 6 Selects preset reference 6.
[17] Select preset ref 7 Selects preset reference 7. If the active
preset reference is changed, it will
merge with other preset reference
commands coming from either the
digital inputs or via a fieldbus.
[18] Select ramp 1 Selects ramp 1
[19] Select ramp 2 Selects ramp 2
[22] Run Issues a start command to the
frequency converter.
[23] Run reverse Issues a start reverse command to the
frequency converter.
[24] Stop Issues a stop command to the
frequency converter.
[26] DC Brake Issues a DC stop command to the
frequency converter.
[27] Coast The frequency converter coasts
immediately. All stop commands
including the coast command stop the
SLC.
[28] Freeze output Freezes the output frequency of the
frequency converter.
[29] Start timer 0
Starts timer 0, see 13-20 SL Controller
Timer for further description.
[30] Start timer 1
Starts timer 1, see 13-20 SL Controller
Timer for further description.
[31] Start timer 2
Starts timer 2, see 13-20 SL Controller
Timer for further description.
13-52 SL Controller Action
Array [20]
Option: Function:
[32] Set digital out A
low
Any output with ‘digital output 1’
selected is low (off).
[33] Set digital out B
low
Any output with ‘digital output 2’
selected is low (off).
[34] Set digital out C
low
Any output with ‘digital output 3’
selected is low (off).
[35] Set digital out D
low
Any output with ‘digital output 4’
selected is low (off).
[36] Set digital out E
low
Any output with ‘digital output 5’
selected is low (off).
[37] Set digital out F
low
Any output with ‘digital output 6’
selected is low (off).
[38] Set digital out A
high
Any output with ‘digital output 1’
selected is high (closed).
[39] Set digital out B
high
Any output with ‘digital output 2’
selected is high (closed).
[40] Set digital out C
high
Any output with ‘digital output 3’
selected is high (closed).
[41] Set digital out D
high
Any output with ‘digital output 4’
selected is high (closed).
[42] Set digital out E
high
Any output with ‘digital output 5’
selected is high (closed).
[43] Set digital out F
high
Any output with ‘digital output 6’
selected is high (closed).
[60] Reset Counter A Resets Counter A to zero.
[61] Reset Counter B Resets Counter A to zero.
[70] Start Timer 3
Starts timer 3, see 13-20 SL Controller
Timer for further description.
[71] Start Timer 4
Starts timer 4, see 13-20 SL Controller
Timer for further description.
[72] Start Timer 5
Starts timer 5, see 13-20 SL Controller
Timer for further description.
[73] Start Timer 6
Starts timer 6, see 13-20 SL Controller
Timer for further description.
[74] Start Timer 7
Starts timer 7, see 13-20 SL Controller
Timer for further description.
[80] Sleep Mode
[90] Set ECB Bypass
Mode
[91] Set ECB Drive
Mode
[100] Reset Alarms
Parameter Description
VLT
®
HVAC Drive Programming Guide
108 MG11CD02 - VLT
®
is a registered Danfoss trademark
3