Technical information

3.13.4 13-2* Timers
Use the result (TRUE or FALSE) from timers directly to
define an event (see 13-51 SL Controller Event), or as
boolean input in a logic rule (see 13-40 Logic Rule Boolean
1, 13-42 Logic Rule Boolean 2 or 13-44 Logic Rule Boolean 3).
A timer is only FALSE when started by an action (i.e. Start
timer 1 [29]) until the timer value entered in this
parameter is elapsed. Then it becomes TRUE again.
All parameters in this parameter group are array
parameters with index 0 to 2. Select index 0 to program
Timer 0, select index 1 to program Timer 1, and so on.
13-20 SL Controller Timer
Array [3]
Range: Function:
Size
related*
[ 0.000 -
0.000 ]
Enter the value to define the duration
of the FALSE output from the
programmed timer. A timer is only
FALSE if it is started by an action (i.e.
Start timer 1 [29]) and until the given
timer value has elapsed.
3.13.5 13-4* Logic Rules
Combine up to three boolean inputs (TRUE / FALSE inputs)
from timers, comparators, digital inputs, status bits and
events using the logical operators AND, OR, and NOT.
Select boolean inputs for the calculation in 13-40 Logic Rule
Boolean 1, 13-42 Logic Rule Boolean 2 and 13-44 Logic Rule
Boolean 3. Define the operators used to logically combine
the selected inputs in 13-41 Logic Rule Operator 1 and
13-43 Logic Rule Operator 2.
. . .
. . .
. . .
. . .
Par. LC-43
Logic Rule Operator 2
Par. LC-41
Logic Rule Operator 1
Par. LC-40
Logic Rule Boolean 1
Par. LC-42
Logic Rule Boolean 2
Par. LC-44
Logic Rule Boolean 3
130BB673.10
Priority of calculation
The results of 13-40 Logic Rule Boolean 1, 13-41 Logic Rule
Operator 1 and 13-42 Logic Rule Boolean 2 are calculated
first. The outcome (TRUE / FALSE) of this calculation is
combined with the settings of 13-43 Logic Rule Operator 2
and 13-44 Logic Rule Boolean 3, yielding the final result
(TRUE / FALSE) of the logic rule.
13-40 Logic Rule Boolean 1
Array [6]
Option: Function:
[0] * False Enters the fixed value of FALSE in the
logic rule.
13-40 Logic Rule Boolean 1
Array [6]
Option: Function:
[1] True Enters the fixed value TRUE in the
logic rule.
[2] Running See parameter group 5-3* for further
description.
[3] In range See parameter group 5-3* for further
description.
[4] On reference See parameter group 5-3* for further
description.
[5] Torque limit See parameter group 5-3* for further
description.
[6] Current limit See parameter group 5-3* for further
description.
[7] Out of current
range
See parameter group 5-3* for further
description.
[8] Below I low See parameter group 5-3* for further
description.
[9] Above I high See parameter group 5-3* for further
description.
[10] Out of speed range
[11] Below speed low See parameter group 5-3* for further
description.
[12] Above speed high See parameter group 5-3* for further
description.
[13] Out of feedb. range See parameter group 5-3* for further
description.
[14] Below feedb. low See parameter group 5-3* for further
description.
[15] Above feedb. high See parameter group 5-3* for further
description.
[16] Thermal warning See parameter group 5-3* for further
description.
[17] Mains out of range See parameter group for further
description.
[18] Reversing See parameter group 5-3* for further
description.
[19] Warning See parameter group 5-3* for further
description.
[20] Alarm (trip) See parameter group 5-3* for further
description.
[21] Alarm (trip lock) See parameter group 5-3* for further
description.
[22] Comparator 0 Use the result of comparator 0 in the
logic rule.
[23] Comparator 1 Use the result of comparator 1 in the
logic rule.
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG11CD02 - VLT
®
is a registered Danfoss trademark 103