Technical information
13-10 Comparator Operand
Array [4]
Option: Function:
[68] Below I low
[69] Above I high
[70] Out of speed range
[71] Below speed low
[72] Above speed high
[75] Out of feedb. range
[76] Below feedb. low
[77] Above feedb. high
[80] Thermal warning
[82] Mains out of range
[85] Warning
[86] Alarm (trip)
[87] Alarm (trip lock)
[90] Bus OK
[91] Torque limit & stop
[92] Brake fault (IGBT)
[93] Mech. brake control
[94] Safe stop active
[100] Comparator 0
[101] Comparator 1
[102] Comparator 2
[103] Comparator 3
[104] Comparator 4
[105] Comparator 5
[110] Logic rule 0
[111] Logic rule 1
[112] Logic rule 2
[113] Logic rule 3
[114] Logic rule 4
[115] Logic rule 5
[120] SL Time-out 0
[121] SL Time-out 1
[122] SL Time-out 2
[123] SL Time-out 3
[124] SL Time-out 4
[125] SL Time-out 5
[126] SL Time-out 6
[127] SL Time-out 7
[130] Digital input DI18
[131] Digital input DI19
[132] Digital input DI27
[133] Digital input DI29
[134] Digital input DI32
[135] Digital input DI33
[150] SL digital output A
[151] SL digital output B
[152] SL digital output C
[153] SL digital output D
[154] SL digital output E
[155] SL digital output F
[160] Relay 1
13-10 Comparator Operand
Array [4]
Option: Function:
[161] Relay 2
[180] Local ref. active
[181] Remote ref. active
[182] Start command
[183] Drive stopped
[185] Drive in hand mode
[186] Drive in auto mode
[187] Start command
given
[190] Digital input x30 2
[191] Digital input x30 3
[192] Digital input x30 4
13-11 Comparator Operator
Array [6]
Option: Function:
[0] * < Select < [0] for the result of the evaluation
to be TRUE, when the variable selected in
13-10 Comparator Operand is smaller than
the fixed value in 13-12 Comparator Value.
The result will be FALSE, if the variable
selected in 13-10 Comparator Operand is
greater than the fixed value in
13-12 Comparator Value.
[1] ≈ (equal) Select ≈ [1] for the result of the evaluation
to be TRUE, when the variable selected in
13-10 Comparator Operand is approximately
equal to the fixed value in 13-12 Comparator
Value.
[2] > Select > [2] for the inverse logic of option <
[0].
[5] TRUE longer
than..
[6] FALSE longer
than..
[7] TRUE shorter
than..
[8] FALSE
shorter
than..
13-12 Comparator Value
Array [6]
Range: Function:
Size related* [-100000.000 -
100000.000 ]
Enter the ‘trigger level’ for the
variable that is monitored by
this comparator. This is an
array parameter containing
comparator values 0 to 5.