Technical information

13-02 Stop Event
Option: Function:
[51] Comparator 5 Use the result of comparator 5 in the
logic rule.
[60] Logic rule 4 Use the result of logic rule 4 in the
logic rule.
[61] Logic rule 5 Use the result of logic rule 5 in the
logic rule.
[70] SL Time-out 3 Use the result of timer 3 in the logic
rule.
[71] SL Time-out 4 Use the result of timer 4 in the logic
rule.
[72] SL Time-out 5 Use the result of timer 5 in the logic
rule.
[73] SL Time-out 6 Use the result of timer 6 in the logic
rule.
[74] SL Time-out 7 Use the result of timer 7 in the logic
rule.
[76] Digital Input x30 2
[77] Digital Input x30 3
[78] Digital Input x30 4
[80] No Flow
[81] Dry Pump
[82] End of Curve
[83] Broken Belt
[90] ECB Drive Mode
[91] ECB Bypass Mode
[92] ECB Test Mode
[100] Fire Mode
13-03 Reset SLC
Option: Function:
[0] * Do not reset
SLC
Retains programmed settings in all group
13 parameters (13-**).
[1] Reset SLC Resets all group 13 parameters (13-**) to
default settings.
3.13.3 13-1* Comparators
Comparators are used for comparing continuous variables
(i.e. output frequency, output current, analog input etc.) to
fixed preset values.
Par. LC-11
Comparator Operator
=
TRUE longer than.
. . .
. . .
Par. LC-10
Comparator Operand
Par. LC-12
Comparator Value
130BB672.10
In addition, there are digital values that will be compared
to fixed time values. See explanation in 13-10 Comparator
Operand. Comparators are evaluated once in each scan
interval. Use the result (TRUE or FALSE) directly. All
parameters in this parameter group are array parameters
with index 0 to 5. Select index 0 to programme
Comparator 0, select index 1 to programme Comparator 1,
and so on.
13-10 Comparator Operand
Array [4]
Option: Function:
Select the variable to be monitored
by the comparator.
[0] * DISABLED
[1] Reference
[2] Feedback
[3] Motor speed
[4] Motor current
[5] Motor torque
[6] Motor power
[7] Motor voltage
[8] DC-link voltage
[9] Motor thermal
[10] Drive thermal
[11] Heat sink temp.
[12] Analog input AI53
[13] Analog input AI54
[14] Analog input AIFB10
[15] Analog input AIS24V
[17] Analog input AICCT
[18] Pulse input FI29
[19] Pulse input FI33
[20] Alarm number
[21] Warning number
[22] Analog input x30 11
[23] Analog input x30 12
[30] Counter A
[31] Counter B
[40] Analog input x42/1
[41] Analog input x42/3
[42] Analog input x42/5
[50] FALSE
[51] TRUE
[52] Control ready
[53] Drive ready
[54] Running
[55] Reversing
[56] In range
[60] On reference
[61] Below reference, low
[62] Above ref, high
[65] Torque limit
[66] Current limit
[67] Out of current range
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG11CD02 - VLT
®
is a registered Danfoss trademark 101