MAKING MODERN LIVING POSSIBLE Programming Guide VLT® HVAC Drive
VLT® HVAC Drive Programming Guide Contents Contents 1 Introduction 3 1.1.1 Copyright, Limitation of Liability and Revision Rights 3 1.1.2 Approvals 3 1.1.3 Symbols 3 1.1.4 Abbreviations 4 1.1.6 Definitions 4 2 How to Programme 9 2.1 Local Control Panel 9 2.1.1 How to Operate Graphical LCP (GLCP) 9 2.1.2 How to Operate Numeric LCP (NLCP) 12 2.1.5 Quick Menu Mode 14 2.1.6 Function Set-ups 16 2.1.7 Main Menu Mode 19 3 Parameter Description 22 3.1 Parameter Selection 22 3.1.
VLT® HVAC Drive Programming Guide Contents 3.22 Main Menu - Application Functions 2 - Group 24 169 3.23 Main Menu - Cascade Controller - Group 25 175 3.24 Main Menu - Analog I/O Option MCB 109 - Group 26 184 4 Troubleshooting 191 4.1 Troubleshooting 191 4.1.1 Alarm Words 195 4.1.2 Warning Words 196 4.1.3 Extended Status Words 197 4.1.4 Fault Messages 198 5 Parameter Lists 204 5.1 Parameter Options 204 5.1.1 Default settings 204 5.1.2 0-** Operation and Display 205 5.1.
VLT® HVAC Drive Programming Guide Introduction 1 1 1 Introduction VLT® HVAC Drive FC 100 Series equipment, loss of computer programs, loss of data, the costs to substitute these, or any claims by third parties. Danfoss reserves the right to revise this publication at any time and to make changes to its contents without prior notice or any obligation to notify former or present users of such revisions or changes. 1.1.
1 1 VLT® HVAC Drive Programming Guide Introduction 1.1.
VLT® HVAC Drive Programming Guide Introduction 1 1 Start-disable command A stop command belonging to the group 1 control commands - see this group. fM Motor frequency. fMAX Maximum motor frequency. Stop command See Control commands. fMIN Minimum motor frequency. fM,N Rated motor frequency (nameplate data). IM Motor current (actual). References: Analog Reference A signal transmitted to the analog inputs 53 or 54, can be voltage or current. IM,N Rated motor current (nameplate data).
1 1 Introduction VLT® HVAC Drive Programming Guide Digital Inputs The digital inputs can be used for controlling various functions of the frequency converter. Digital Outputs The frequency converter features two Solid State outputs that can supply a 24V DC (max. 40mA) signal. DSP Digital Signal Processor. ETR Electronic Thermal Relay is a thermal load calculation based on present load and time. Its purpose is to estimate the motor temperature. Hiperface® Hiperface® is a registered trademark by Stegmann.
VLT® HVAC Drive Programming Guide Introduction VVCplus If compared with standard voltage/frequency ratio control, Voltage Vector Control (VVCplus ) improves the dynamics and the stability, both when the speed reference is changed and in relation to the load torque. 60° AVM Switching pattern called 60° Asynchronous Vector Modulation (14-00 Switching Pattern). 4. The earth leakage current exceeds 3.5mA. 5. Protection against motor overload is not included in the factory setting.
Introduction 1 1 VLT® HVAC Drive Programming Guide activated in error, be delayed or fail to occur entirely. When used in situations where safety is critical, e.g. when controlling the electromagnetic brake function of a hoist application, these control signals must not be relied on exclusively. WARNING High Voltage Touching the electrical parts may be fatal - even after the equipment has been disconnected from mains.
VLT® HVAC Drive Programming Guide How to Programme 130BA018.13 2 How to Programme 2.1 Local Control Panel 2.1.1 How to Operate Graphical LCP (GLCP) Status 1(0) 1234rpm 10,4A a 43,5Hz The following instructions are valid for the GLCP (LCP 102). The GLCP is divided into four functional groups 1. Graphical display with Status lines. 2. Menu keys and indicator lights (LEDs) - selecting mode, changing parameters and switching between display functions. 3.
Status 1 (1) 5.25A 207RPM 24.4 kW 1.1 6.9 Hz Each value/measurement readout parameter selected in 0-20 Display Line 1.1 Small to 0-24 Display Line 3 Large has its own scale and number of digits after a possible decimal point. Larger numeric values are displayed with few digits after the decimal point. Ex.: Current readout 5.25 A; 15.2 A 105 A. 2 Status display III This state displays the event and action of the Smart Logic Control. For further information, see 3.13 Main Menu Smart Logic - Group 13.
VLT® HVAC Drive Programming Guide applications and specific functions related to Fans, Pumps and Compressors. 130BP044.10 How to Programme On The Quick Menu parameters can be accessed immediately unless a password has been created via 0-60 Main Menu Password, 0-61 Access to Main Menu w/o Password, 0-65 Personal Menu Password or 0-66 Access to Personal Menu w/o Password. It is possible to switch directly between Quick Menu mode and Main Menu mode. Warn.
Navigation Keys The four navigation arrows are used to navigate between the different choices available in [Quick Menu], [Main Menu] and [Alarm Log]. Use the keys to move the cursor. l ce ck n Ca 130BT117.10 [OK] is used for choosing a parameter marked by the cursor and for enabling the change of a parameter. Ba [Off] stops the connected motor. The key can be selected as Enabled [1] or Disabled [0] via 0-41 [Off] Key on LCP.
VLT® HVAC Drive Programming Guide 130BA191.10 How to Programme Quick Setup Main Menu Auto on Reset Ba ck Menu 130BP079.10 Status 2 2 2 Navigation Keys [Back] for stepping backwards Arrow [▼] [▲] keys are used for manoeuvring between parameter groups, parameters and within parameters. [OK] is used for choosing a parameter marked by the cursor and for enabling the change of a parameter. Setup 1 Select the wanted data value and press [OK] 3 OK On P 2-03 Warn.
If no external stop function is selected and the [Off] key is inactive the motor can be stopped by disconnecting the mains supply. [Auto On] enables the frequency converter to be controlled via the control terminals and/or serial communication. When a start signal is applied on the control terminals and/or the bus, the frequency converter will start. The key can be selected as Enable [1] or Disable [0] via 0-42 [Auto on] Key on LCP.
VLT® HVAC Drive Programming Guide 6. To move to a different digit within a parameter setting, use the [◀] and [▶] buttons 7. Highlighted area indicates digit selected for change 8. Press [Cancel] button to disregard change, or press [OK] to accept change and enter the new setting Example of changing parameter data Assume 22-60 Broken Belt Function is set to [Off].
[Units] How to access Function set-up - example 1-20 Motor Power [kW] [kW] Step 1: Turn on the frequency converter (yellow LED lights) 1-21 Motor Power [HP] [HP] 1-22 Motor Voltage* [V] 1-23 Motor Frequency [Hz] 1-24 Motor Current [A] 1-25 Motor Nominal Speed [RPM] 1-28 Motor Rotation Check [Hz] 3-41 Ramp 1 Ramp Up Time [s] 3-42 Ramp 1 Ramp Down Time [s] 4-11 Motor Speed Low Limit [RPM] [RPM] 4-12 Motor Speed Low Limit [Hz]* [Hz] 4-13 Motor Speed High Limit [RPM] [RPM] 4-14 Motor
Step 6: Choose 6-50 Terminal 42 Output. Press [OK]. 5.82A 1(1) 03.11 6 - 50 Terminal 42 Output 130BA115.10 26.3% Analog Output 43.4% Analog Output 7.99A 6-50 Terminal 42 Output [107] 1(1) Q3-11 130BT116.10 VLT® HVAC Drive Programming Guide How to Programme Speed (100) Output frequency Step 7: Use the up/down navigation keys to select between the different choices. Press [OK].
2 2 How to Programme VLT® HVAC Drive Programming Guide Q3-3 Closed Loop Settings Q3-30 Single Zone Int. Set Point Q3-31 Single Zone Ext. Set Point Q3-32 Multi Zone / Adv 1-00 Configuration Mode 1-00 Configuration Mode 1-00 Configuration Mode 20-12 Reference/Feedback Unit 20-12 Reference/Feedback Unit 3-15 Reference 1 Source 20-13 Minimum Reference/Feedb. 20-13 Minimum Reference/Feedb. 3-16 Reference 2 Source 20-14 Maximum Reference/Feedb. 20-14 Maximum Reference/Feedb.
VLT® HVAC Drive Programming Guide How to Programme Q3-4 Application Settings Q3-40 Fan Functions Q3-41 Pump Functions Q3-42 Compressor Functions 22-60 Broken Belt Function 22-20 Low Power Auto Set-up 1-03 Torque Characteristics 22-61 Broken Belt Torque 22-21 Low Power Detection 1-71 Start Delay 22-62 Broken Belt Delay 22-22 Low Speed Detection 22-75 Short Cycle Protection 4-64 Semi-Auto Bypass Set-up 22-23 No-Flow Function 22-76 Interval between Starts 1-03 Torque Characteristics 22-24 No-
Parameter group: 0 Operation/Display 740RPM Basic Settings 1 Load/Motor 0 -01 Language 2 Brakes 3 References/Ramps 4 Limits/Warnings 5 Digital In/Out 6 Analog In/Out 8 Comm. and Options 9 Profibus 10 CAN Fieldbus 11 LonWorks 12 Ethernet IP / Modbus TCP / PROFINET 13 Smart Logic 14 Special Functions 15 Drive Information 16 Data Readouts 18 Data Readouts 2 20 Drive Closed Loop 21 Ext.
VLT® HVAC Drive Programming Guide How to Programme Use 3-10 Preset Reference as another example: Choose the parameter, press [OK], and use the up/down navigation keys keys to scroll through the indexed values. To change the parameter value, select the indexed value and press [OK]. Change the value by using the up/down keys. Press [OK] to accept the new setting. Press [Cancel] to abort. Press [Back] to leave the parameter. 2.1.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 3 Parameter Description 3.1 Parameter Selection 3.1.1 Main Menu Structure Parameters for the frequency converter are grouped into various parameter groups for easy selection of the correct parameters for optimized operation of the frequency converter. The vast majority of VLT® HVAC Drive applications can be programmed using the Quick Menu button and selecting the parameters under Quick Setup and Function Setups.
VLT® HVAC Drive Programming Guide Parameter Description 3.2 Main Menu - Operation and Display - Group 0 Parameters related to the fundamental functions of the frequency converter, function of the LCP buttons and configuration of the LCP display. 0-02 Motor Speed Unit Option: 0-02 Motor Speed Unit and 0-03 Regional Settings. The 3.2.
3 3 Parameter Description VLT® HVAC Drive Programming Guide 0-04 Operating State at Power-up Option: Function: Select the operating mode upon reconnection of the frequency converter to mains voltage after power down when operating in Hand (local)mode.
VLT® HVAC Drive Programming Guide 0-11 Programming Set-up 0-12 This Set-up Linked to Option: Option: Function: 1. Change the edit set-up to Set-up 2 [2] in Select the set-up to be edited (i.e. programmed) during operation; either the active set-up or one of the inactive set-ups. The set-up number being edited is displayed in the LCP in (brackets). Factory setup cannot be edited but it is useful as a data source to return the other set-ups to a known state.
VLT® HVAC Drive Programming Guide Parameter Description 0-13 Readout: Linked Set-ups 0-20 Display Line 1.1 Small Array [5] Option: Range: 0* Function: [37] Display Text 1 Enables an individual text string to be written, for display in the LCP or to be read via serial communication. [38] Display Text 2 Enables an individual text string to be written, for display in the LCP or to be read via serial communication.
VLT® HVAC Drive Programming Guide Parameter Description 0-20 Display Line 1.1 Small 0-20 Display Line 1.1 Small Option: Option: [1605] [1609] Function: Main Actual Value [%] Custom Readout View the two-byte word sent with the Status word to the bus Master reporting the Main Actual Value. [1634] Function: Heatsink Temp. out limit is 95 ± 5° C; cutting back in occurs at 70 ± 5° C.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 0-20 Display Line 1.1 Small 0-20 Display Line 1.1 Small Option: Option: Function: Function: [1666] Digital Output [bin] Binary value of all digital outputs. [1693] Warning Word 2 [1667] Pulse Input #29 [Hz] Actual value of the frequency applied at terminal 29 as a pulse input. One or more warnings in a Hex code (used for serial communications) [1694] Ext.
VLT® HVAC Drive Programming Guide Parameter Description 0-20 Display Line 1.1 Small 0-23 Display Line 2 Large Option: Select a variable for display in line 2. [2138] [2139] Function: Ext. 2 Feedback [Unit] The value of the feedback signal for extended Closed Loop Controller 2 Ext. 2 Output [%] The value of the output from extended Closed Loop Controller 2 [2157] Ext. 3 Reference [Unit] The value of the reference for extended Closed Loop Controller 3 [2158] Ext.
VLT® HVAC Drive Programming Guide 130BT105.11 Parameter Description Custom Readout (Value) P 16-09 Custom Readout Unit P 0-30 Max value P 0-32 3 3 d ee e U ar Lin Min value Liniar units only P 0-31 nit . Sp e.
VLT® HVAC Drive Programming Guide Parameter Description 0-39 Display Text 3 0-32 Custom Readout Max Value Range: Function: 100.00 CustomReadoutUnit* [ par. 0-31 - This parameter sets the max 999999.99 value to be shown when CustomReathe speed of the motor has doutUnit] reached the set value for 4-13 Motor Speed High Limit Range: Function: inserted by placing the cursor between two characters and pressing [▲] or [▼]. 3 3 3.2.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 0-42 [Auto on] Key on LCP 0-50 LCP Copy Option: Option: [0] Function: Disabled No function [3] [1] * Enabled [Auto on] Key is enabled [2] Avoid unauthorized start in Auto Password Size indep. from LCP mode. If 0-42 [Auto on] Key on LCP is included in the My Personal Menu, then define the password in 0-65 Personal Menu Password. Otherwise define the password in 0-60 Main Menu Password.
Parameter Description VLT® HVAC Drive Programming Guide 0-65 Personal Menu Password 0-70 Date and Time Range: Range: 200 * Function: [0 - 999 ] Define the password for access to the My [ 0 - 0 ] Sets the date and time of the internal Personal Menu via the [Quick Menu] key. If clock. The format to be used is set in 0-66 Access to Personal Menu w/o Password is 0-71 Date Format and 0-72 Time Format. set to Full access [0], this parameter will be ignored.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 0-81 Working Days Array with 7 elements [0] - [6] displayed below parameter number in display. Press OK and step between elements by means of Option: ▲ and ▼ buttons on the LCP. Function: Set for each weekday if it is a working day or a nonworking day. First element of the array is Monday. The working days are used for Timed Actions.
Parameter Description VLT® HVAC Drive Programming Guide 3.3 Main Menu - Load and Motor - Group 1 3.3.1 1-0* General Settings 1-03 Torque Characteristics Define whether the frequency converter operates in open loop or closed loop. Option: 1-00 Configuration Mode Option: [0] * Open Loop must be set correctly. This value is set in Function: 14-43 Motor Cosphi. The parameter has a default value which is automatically adjusted when the motor data is programmed.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 1-06 Clockwise Direction 1-10 Motor construction This parameter defines the term “Clockwise” corresponding to the LCP direction arrow. Used for easy change of direction of shaft rotation without swapping motor wires. (Valid from SW version 5.84) Option: [0] * [1] Function: Normal Inverse Motor shaft will turn in clockwise direction when the frequency converter is connected U -> U; V > V, and W -> W to motor.
VLT® HVAC Drive Programming Guide Parameter Description [0] [1] PM Motor Asynchron non salient 1-10 Motor construction 4-13 Motor speed high limit [rpm] x x 4-14 Motor speed high limit [Hz] x x 4-16 Torque limit motor mode x x 4-17 Torque limit generator mode x x 4-18 Current limit x x 4-19 Max output frequency x x 4-58 Missing motor phase x 14-40 VT Level x 14-41 AEO Minimum Magnetisation x 14-42 Minimum AEO Frequency x 14-43 Motor Cosphi x 1-14 Damping Gain Range: 120 %* Fu
3 3 VLT® HVAC Drive Programming Guide Parameter Description 3.3.4 1-2* Motor Data 1-23 Motor Frequency Parameter group 1-2* comprises input data from the nameplate on the connected motor. NOTE Changing the value of these parameters affects the setting of other parameters. NOTE 1-20 Motor Power [kW], 1-21 Motor Power [HP], 1-22 Motor Voltage and 1-23 Motor Frequency will not have effect when 1-10 Motor Construction = [1] PM, non salient SPM.
VLT® HVAC Drive Programming Guide Parameter Description pressing the [OK] key the frequency converter is ready for operation. 1-28 Motor Rotation Check Option: Function: Following installation and connection of the motor, this function allows the correct motor rotation direction to be verified. Enabling this function overrides any bus commands or digital inputs, except External Interlock and Safe Stop (if included).
VLT® HVAC Drive Programming Guide Parameter Description ωsLqIq Par. 1-37 Ld 130BC056.10 Par. 1-30 Rs Id + - 1-35 Main Reactance (Xh) Ud 3 3 Range: Size related* d-axis equivalent circuit Par. 1-30 Rs Id NOTE 1-31 Rotor Resistance (Rr) will not have effect when 1-10 Motor Construction = [1] PM, non salient SPM. ωsLdId Par. 1-37 Lq=Ld - + Function: [ 1.0000 - Set the main reactance of the motor 10000.0000 using one of these methods: Ohm] 1. Run an AMA on a cold motor.
VLT® HVAC Drive Programming Guide NOTE 1-30 Stator Resistance This parameter gives stator winding resistance(Rs) Similar to Asynchronous (Rs) (Line to common) Motor Stator resistance. The Stator resistance is defined for line to common measurement. That means for line-line data (Where stator resistance is measured between any two lines you need to divide it with 2). 1-40 Back EMF at 1000 RPM RMS (Line to Line Value ) This parameter gives direct axis inductance of the PM motor.
NOTE 3.3.6 1-5* Load Indep. Setting 1-52 Min Speed Normal Magnetising [Hz] will not have effect when 1-10 Motor Construction = [1] PM, non salient SPM. 1-50 Motor Magnetisation at Zero Speed Range: 100 %* [0 300 %] Function: Use this parameter along with 1-51 Min Speed Normal Magnetising [RPM] to obtain a different thermal load on the motor when running at low speed. Enter a value which is a percentage of the rated magnetizing current.
VLT® HVAC Drive Programming Guide Parameter Description 3.3.7 1-6* Load Depend. Setting 1-62 Slip Compensation Range: 1-60 Low Speed Load Compensation Range: 100 %* 0 %* Function: [0 - 300 %] Enter the % value to compensate voltage in relation to load when the motor is running at low speed and obtain the optimum U/f characteristic. The motor size determines the frequency range within which this parameter is active. Motor size [kW] Change over [Hz] 0.25 -7.
VLT® HVAC Drive Programming Guide Parameter Description 1-66 Min. Current at Low Speed 1-73 Flying Start Range: Option: Function: Size related* 3 3 [ 1. - 200. Enter the minimum motor current at %] low speed. Increasing this current improves developed motor torque at low speed. Low speed is here defined as speeds below 6% of the Nominal Speed of This function makes it possible to catch a motor which is spinning freely due to a mains drop-out.
VLT® HVAC Drive Programming Guide Parameter Description motor at that speed and resume normal operation. Please refer to description of 1-70 PM Start Mode for recommended settings. Current limitations of the Flystart Principle used for PM motors: • The speed range is up to 100% Nominal Speed or the field weakening speed (which ever is lowest).
VLT® HVAC Drive Programming Guide Parameter Description 1-79 Compressor Start Max Time to Trip Range: 5.0 s* [0.0 10.0 s] Function: The time, from the start signal is given until the speed exceeds the speed set in 1-77 Compressor Start Max Speed [RPM] must not exceed the time set in the parameter or the frequency converter will trip with an alarm [A18] Start Failed. 3 3 Any time set in 1-71 Start Delay for use of a start function must be executed within the time limit.
NOTE t [s] This parameter is only available if 0-02 Motor Speed Unit is set to [Hz]. 3.3.11 1-9* Motor Temperature 1-90 Motor Thermal Protection Option: 175ZA052.12 VLT® HVAC Drive Programming Guide Parameter Description Function: The frequency converter determines the motor temperature for motor protection in two different ways: • Via a thermistor sensor connected to one of the analog or digital 2000 1000 600 500 400 300 200 3 3 fOUT = 1 x f M,N(par.
VLT® HVAC Drive Programming Guide Parameter Description 1-93 Thermistor Source Option: Function: Select the input to which the thermistor (PTC sensor) should be connected. An analog input option [1] or [2] cannot be selected if the analog input is already in 3 3 use as a reference source (selected in 3-15 Reference 1 Source, 3-16 Reference 2 Source or 3-17 Reference 3 Source). When using MCB 112, choice [0] None must always be selected.
VLT® HVAC Drive Programming Guide Parameter Description 3.4 Main Menu - Brakes - Group 2 3.4.1 2-0* DC-Brakes 2-03 DC Brake Cut In Speed [RPM] Parameter group for configuring the DC brake and DC hold functions. Range: Function: Size related* [ 0 - 0. Set the DC brake cut-in speed for RPM] activation of the DC braking current set in 2-01 DC Brake Current, upon a stop command.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 3.4.2 2-1* Brake Energy Funct. 2-12 Brake Power Limit (kW) Parameter group for selecting dynamic braking parameters. Only valid for frequency converters with brake chopper. Range: Function: Pbr,avg is the average power dissipated in the brake resistor, Rbr is the resistance of 2-10 Brake Function the brake resistor. tbr is the active breaking Option: time within the 120 s period, Tbr.
VLT® HVAC Drive Programming Guide Parameter Description 2-15 Brake Check 2-16 AC brake Max. Current Option: Range: Function: Select type of test and monitoring function to check the connection to the brake resistor, or whether a brake resistor is present, and then display a warning or an alarm in the event of a fault. The brake resistor disconnection function is tested during power-up. However the brake IGBT test is performed when there is no braking. A warning or trip disconnects the brake function.
3.5 Main Menu - Reference/Ramps - Group 3 3.5.1 3-0* Reference Limits 3-10 Preset Reference Parameters for setting the reference unit, limits and ranges. Array [8] Range: Function: array programming. The preset reference is stated as a percentage of the value RefMAX Please see also parameter group 20-0* for information on settings in closed loop. (3-03 Maximum Reference, for closed loop see 20-14 Maximum Reference/Feedb.). When using preset references, select Preset ref.
VLT® HVAC Drive Programming Guide Parameter Description 3-13 Reference Site 3-15 Reference 1 Source Option: Option: Function: Select which reference site to activate. [2] Analog input 54 [7] Pulse input 29 [8] Pulse input 33 [0] * Linked to Hand / Auto Use local reference when in Hand mode; or remote reference when in Auto mode. [1] Remote Use remote reference in both Hand mode and Auto mode. [2] Local Use local reference in both Hand mode and Auto mode.
VLT® HVAC Drive Programming Guide Parameter Description 3-17 Reference 3 Source Function: P 4-13 High-limit Reference P 1-25 Motor speed P 4-11 Low limit Select the reference input to be used for the third reference signal. 3-15 Reference 1 Source, 3-16 Reference 3 3 2 Source and 3-17 Reference 3 Source define up to three different reference signals. The sum of these reference signals defines the actual reference.
VLT® HVAC Drive Programming Guide Parameter Description 3-42 Ramp 1 Ramp Down Time 3-48 Ramp 1 S-ramp Ratio at Decel. End Range: Range: Size related* Function: lower the torque jerks in the application. [ 1.00 - Enter the ramp-down time, i.e. the 3600.00 s] deceleration time from 1-25 Motor Nominal Speed to 0 RPM.
VLT® HVAC Drive Programming Guide Parameter Description 3-57 Ramp 2 S-ramp Ratio at Decel. Start 3-81 Quick Stop Ramp Time Range: Range: [Application dependant] Enter the proportion of the total ramp-down time (3-52 Ramp 2 Ramp Application dependent* down Time) where the deceleration torque increases The larger the percentage value, the greater the jerk 3 3 compensation achieved, and thus the lower the torque jerks in the application. 3-58 Ramp 2 S-ramp Ratio at Decel.
VLT® HVAC Drive Programming Guide Parameter Description 3.5.6 3-9* Digital Pot.Meter 3-95 Ramp Delay The digital potentiometer function allows the user to increase or decrease the actual reference by adjusting the set-up of the digital inputs using the functions INCREASE, DECREASE or CLEAR. To activate the function, at least one digital input must be set up to INCREASE or DECREASE. Range: Size related* 3-90 Step Size See also 3-91 Ramp Time. Function: [0.01 200.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 3.6 Main Menu - Limits/Warnings - Group 4 Range: 3.6.1 4-1* Motor Limits 4-10 Motor Speed Direction Function: Selects the motor speed direction required. Use this parameter to prevent unwanted reversing. [0] Clockwise Only operation in clockwise direction will be allowed. [2] * Both directions Operation in both clockwise and anticlockwise direction will be allowed. Low Limit [RPM].
VLT® HVAC Drive Programming Guide Warnings are shown on display, programmed output or serial bus. 4-17 Torque Limit Generator Mode Range: 100.0 %* Function: [ 0.0 - Enter the maximum torque limit for 1000.0 %] generator mode operation. The torque limit is active in the speed range up to and including the rated motor speed 130BA064.10 Parameter Description Imotor (1-25 Motor Nominal Speed). Refer to ILIM (P 4-18) 14-25 Trip Delay at Torque Limit for further details.
3 3 VLT® HVAC Drive Programming Guide Parameter Description NOTE 4-58 Missing Motor Phase Function Any changes in 4-13 Motor Speed High Limit [RPM] will reset the value in 4-53 Warning Speed High to the same value as set in 4-13 Motor Speed High Limit [RPM]. If a different value is needed in 4-53 Warning Speed High, it must be set after programming of 4-13 Motor Speed High Limit [RPM] Option: Function: Displays an alarm in the event of a missing motor phase.
VLT® HVAC Drive Programming Guide Parameter Description 3.6.4 Semi-Automatic Bypass Speed Set-up The Semi-Automatic Bypass Speed Setup can be used to facilitate the programming of the frequencies to be skipped due to resonances in the system. 3 3 The following process is to be carried out 1. Stop the motor. 2. Select Enabled in 4-64 Semi-Auto Bypass Set-up. 3. Press Hand On on the LCP to start the search for frequency bands causing resonances. The motor will ramp up according to the ramp set. 4.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 3.7 Main Menu - Digital In/Out - Group 5 3.7.1 5-0* Digital I/O Mode Digital input function Parameters for configuring the input and output using NPN and PNP. 5-00 Digital I/O Mode Option: Function: Digital inputs and programmed digital outputs are pre-programmable for operation either in PNP or NPN systems.
Parameter Description VLT® HVAC Drive Programming Guide [0] No operation No reaction to signals transmitted to terminal. [1] Reset Resets frequency converter after a TRIP/ ALARM. Not all alarms can be reset. [2] [3] [5] Coast inverse Coast and reset inverse DC-brake inverse Leaves motor in free mode. Logic ‘0’ => coasting stop. (Default Digital input 27): Coasting stop, inverted input (NC). [8] Start Select start for a start/stop command. Logic ‘1’ = start, logic ‘0’ = stop.
VLT® HVAC Drive Programming Guide Parameter Description down to be used. If Speed up/down is used, the speed change always follows parameter group 5-3*, or parameter group 5-4*, will not be affected by Run Permissive. NOTE ramp 2 (3-51 Ramp 2 Ramp Up Time and 3-52 Ramp 2 Ramp Down Time) in the range If no Run Permissive signal is applied but either Run, Jog or Freeze commands is activated, the status line in the display will show either Run Requested, Jog Requested or Freeze Requested.
VLT® HVAC Drive Programming Guide Parameter Description [66] Sleep Mode Forces frequency converter into Sleep Mode (see parameter group 22-4*). Reacts on the rising edge of signal applied! 5-16 Terminal X30/2 Digital Input [68] Timed Actions Disabled Timed actions are disabled. See parameter as parameter group 5-1* except for Pulse input [32]. [69] Constant OFF Timed Actions are set for Constant OFF. See group 23-0* Timed Actions. parameter group 23-0* Timed Actions.
VLT® HVAC Drive Programming Guide Parameter Description 3.7.5 5-3* Digital Outputs 5-19 Terminal 37 Safe Stop Option: Function: off). When safe stop circuit is reestablished, the frequency converter will continue without manual reset, unless a Digital Input set to PTC Card 1 [80] is (still) enabled. Choice 7 is only available when the MCB 112 PTC Thermistor Card is connected. 3 3 [8] [9] PTC 1 & Relay A/W PTC 1 & Relay W/A This choice makes it possible to use a combination of Alarm and Warning.
Parameter Description [19] [20] [21] [25] Below feedback low VLT® HVAC Drive Programming Guide The feedback is below the limit set in Above The feedback is above the limit set in feedback high 4-57 Warning Feedback High. Thermal warning Reverse The thermal warning turns on when the temperature exceeds the limit in the motor, the frequency converter, the brake resistor, or the thermistor. Reversing. Logic ‘1’ = relay activated, 24V DC when CW rotation of the motor.
Action [43] Set dig. out. F high is executed. The input will go low whenever the Smart given the bypass valve will be open until Logic Action [37] Set dig. out. F low is executed. Speed Low Limit [RPM]). After the limit has been reached the bypass valve will be closed, allowing the compressor to operate normally.
VLT® HVAC Drive Programming Guide Parameter Description [200] Full Capacity All pumps running and at full speed [201] Pump1 Running One or more of the pumps controlled by the Cascade Controller are running. The function will also depend on the setting of in 25-06 Number of Pumps. If set to No [0] Pump 1 refers to the pump controlled by relay RELAY1 etc.
Array [8] (Relay 1 [0], Relay 2 [1] Option MCB 105: Relay 7 [6], Relay 8 [7] and Relay 9 [8]). Select options to define the function of the relays. The selection of each mechanical relay is realised in an array parameter.
VLT® HVAC Drive Programming Guide 130BA076.10 Parameter Description Ref. (RPM) High ref. value P 5-53/ p 5-58 5-54 Pulse Filter Time Constant #29 Range: Function: This parameter cannot be adjusted while the motor is running. 3 3 5-55 Term. 33 Low Frequency Range: Function: 100 Hz* Low ref. value P 5-52/ p 5-57 Low freq. P 5-50/ P 5-55 High freq. P 5-51/ P 5-56 [0 - 110000 Hz] Enter the low frequency corresponding to the low motor shaft speed (i.e.
3.7.8 5-6* Pulse Outputs 5-60 Terminal 27 Pulse Output Variable Parameters for configuring the scaling and output functions of pulse outputs. The pulse outputs are designated to terminals 27 or 29. Select terminal 27 output in 5-01 Terminal 27 Mode and terminal 29 output in 5-02 Terminal 29 Mode. Output value 130BA089.11 3 3 VLT® HVAC Drive Programming Guide Parameter Description High output value P 5-60(term27) P 5-63(term29) Option: Function: [45] Bus ctrl. [48] Bus ctrl.
VLT® HVAC Drive Programming Guide Parameter Description 5-66 Terminal X30/6 Pulse Output Variable 5-90 Digital & Relay Bus Control Select the variable for read-out on terminal X30/6. This parameter is active when option module MCB 101 is installed in the frequency converter. Same options and functions as parameter group 5-6*.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 5-97 Pulse Out #X30/6 Bus Control Range: 0.00 %* Function: [0.00 - 100.00 %] Contains the frequency to apply to the digital output terminal 27, when it is configured as [Bus Controlled. 5-98 Pulse Out #X30/6 Timeout Preset Range: 0.00 %* 74 Function: [0.00 - 100.00 %] Contains the frequency to apply to the digital output terminal 6, when it is configured as [Bus Controlled Timeout] and time-out is detected.
VLT® HVAC Drive Programming Guide Parameter Description 3.8 Main Menu - Analog In/Out - Group 6 3.8.1 6-0* Analog I/O Mode 6-01 Live Zero Timeout Function NOTE Option: [1] Freeze output [2] Stop [3] Jogging [4] Max. speed [5] Stop and trip Thermistors may be connected to either an analog or a digital input. Function: 3 3 130BA038.13 Parameter group for setting up the analog I/O configuration. The frequency converter is equipped with 2 analog inputs: Terminal 53 and 54.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 3.8.2 6-1* Analog Input 1 6-16 Terminal 53 Filter Time Constant Parameters for configuring the scaling and limits for analog input 1 (terminal 53). Range: Function: 0.001 s* [0.001 10.000 s] 6-10 Terminal 53 Low Voltage Range: 0.07 V* Function: [ 0.00 - par. Enter the low voltage value. This analog 6-11 V] input scaling value should correspond to the low reference/feedback value set in 6-14 Terminal 53 Low Ref./Feedb. Value.
VLT® HVAC Drive Programming Guide Parameter Description 6-22 Terminal 54 Low Current 6-27 Terminal 54 Live Zero Range: Option: Function: 4.00 mA* [ 0.00 - Enter the low current value. This reference par. 6-23 signal should correspond to the low mA] reference/feedback value, set in 6-24 Terminal 54 Low Ref./Feedb. Value. The value must be set at >2 mA in order to activate the Live Zero Time-out Function in 6-01 Live Zero Timeout Function. 6-23 Terminal 54 High Current Range: Function: 20.
VLT® HVAC Drive Programming Guide Parameter Description 6-37 Term. X30/11 Live Zero NOTE Option: This parameter cannot be changed while the motor is running. Function: This parameter makes it possible to disable the Live Zero monitoring. E.g. to be used if the analog outputs are used as part of a decentral I/O system (e.g. when not part of any frequency converter related control functions, but feeding a Building Management System with data). 3 3 6-47 Term.
VLT® HVAC Drive Programming Guide Parameter Description 6-50 Terminal 42 Output 6-52 Terminal 42 Output Max Scale Function: Range: [131] Reference 4-20mA Minimum Reference - Maximum Reference [132] Feedback 4-20mA -200% to +200% of 20-14 Maximum Function: Current (mA) 130BA075.12 Option: 20 3 3 Reference/Feedb. [133] Motor cur. 4-20mA 0 - Inverter Max. Current (16-37 Inv. 0/4 Max. Current) [134] 0% Analogue output Min Scale par. 6-93 Torq.
EXAMPLE 2: Variable= FEEDBACK, range= -200% to +200% Range needed for output= 0-100% Output signal 0 or 4mA is needed at 0% (50% of range) set 6-51 Terminal 42 Output Min Scale to 50% Output signal 20mA is needed at 100% (75% of range) set 6-52 Terminal 42 Output Max Scale to 75% 6-54 Terminal 42 Output Timeout Preset Range: In case of a bus timeout and a timeout Output the output will preset to this level. 130BA856.10 20 mA 0/4 mA 0% 50% 75% Function: function is selected in 6-50 Terminal 42 3.8.
VLT® HVAC Drive Programming Guide Parameter Description 6-63 Terminal X30/8 Output Bus Control Range: 0.00 %* Function: [0.00 - 100.00 %] Contains the value to apply to the output terminal, when it is configured as [Bus Controlled]. 3 3 6-64 Terminal X30/8 Output Timeout Preset Range: 0.00 %* Function: [0.00 - 100.00 %] Contains the value to apply to the output terminal, when it is configured as [Bus Controlled Timeout] and timeout is detected.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 3.9 Main Menu - Communications and Options - Group 8 3.9.1 8-0* General Settings 8-03 Control Timeout Time Range: Function: 8-01 Control Site Option: In BACnet the control timeout is only triggered if some specific objects are written. The object list hold information on the objects that triggers the control timeout: Function: The setting in this parameter overrides the settings in 8-50 Coasting Select to 8-56 Preset Reference Select.
VLT® HVAC Drive Programming Guide Parameter Description 8-05 End-of-Timeout Function 8-13 Configurable Status Word STW Option: Option: Function: until 8-06 Reset Control Timeout toggles. Then the frequency converter resumes its original set-up. [1] * Resume setup Resumes the set-up active prior to the timeout. [3] Trip excl Alarm 68 [10] T18 DI status. Function: Set in case of a trip, except if the trip is executed by an Alarm 68. The bit indicates the status of terminal 3 3 18*1.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 3.9.3 8-3* FC Port Settings 8-13 Configurable Status Word STW Option: [72] Logic Rule 2 Function: See parameter group 13-4*. If Logic Rule 2 is evaluated as TRUE, the output will go high. Otherwise, it will be low. [73] Logic Rule 3 See parameter group 13-4*. If Logic Rule 3 is evaluated as TRUE, the output will go high. Otherwise, it will be low. [74] Logic Rule 4 See parameter group 13-4*.
VLT® HVAC Drive Programming Guide Parameter Description 8-31 Address 8-36 Maximum Response Delay Range: Size related* Function: Range: [ 1. - 255. ] Enter the address for the FC (standard) port. Valid range: 1 - 126. Size related* 8-32 Baud Rate Option: Function: Baud rates 9600, 19200, 38400 and 76800 baud are valid for BACnet only. [0] 2400 Baud [1] 4800 Baud 19200 Baud [4] 38400 Baud [5] 57600 Baud [6] 76800 Baud [7] 115200 Baud [ 11. - 10001.
3 3 Parameter Description VLT® HVAC Drive Programming Guide 3.9.5 8-5* Digital/Bus 8-53 Start Select Parameters for configuring the control word Digital/Bus merging. NOTE These parameters are active only when 8-01 Control Site is set to [0] Digital and control word. Option: [1] Bus Activates Start command via the serial communication port or fieldbus option. [2] Logic AND Activates Start command via the fieldbus/serial communication port, AND additionally via one of the digital inputs.
VLT® HVAC Drive Programming Guide Parameter Description 8-56 Preset Reference Select 8-75 Initialisation Password Option: Range: Function: [0] Digital input Activates Preset Reference selection via a digital input. [1] Bus Activates Preset Reference selection via the serial communication port or fieldbus option. [2] Logic AND [3] * Logic OR Activates Preset Reference selection via the fieldbus/serial communication port, AND additionally via one of the digital inputs.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 8-91 Bus Jog 2 Speed Range: 200 RPM* Function: [ 0 - par. 4-13 Enter the jog speed. This is a fixed RPM] jog speed activated via the serial port or fieldbus option. 8-94 Bus Feedback 1 Range: 0* [-200 200 ] Function: Write a feedback to this parameter via the serial communication port or fieldbus option. This parameter must be selected in 20-00 Feedback 1 Source, 20-03 Feedback 2 Source or 20-06 Feedback 3 Source as a feedback source.
Parameter Description VLT® HVAC Drive Programming Guide 3.10 Main Menu - Profibus - Group 9 9-15 PCD Write Configuration 9-15 PCD Write Configuration Array [10] Array [10] Option: Function: Select the parameters to be assigned to PCD 3 to 10 of the telegrams. The number of available PCDs depends on the telegram type. The values in PCD 3 to 10 will then be written to the selected parameters as data values.
3 3 VLT® HVAC Drive Programming Guide Parameter Description PB-16 PCD Read Configuration 9-22 Telegram Selection Array [10] Option: Option: Function: uration and 9-16 PCD Read Function: Configuration.
Parameter Description VLT® HVAC Drive Programming Guide 9-23 Parameters for Signals 9-23 Parameters for Signals Array [1000] Array [1000] Option: Function: Option: Function: [1601] Reference [Unit] [1690] Alarm Word [1602] Reference [%] [1691] Alarm Word 2 [1603] Status Word [1692] Warning Word [1605] Main Actual Value [%] [1693] Warning Word 2 [1609] Custom Readout [1694] Ext. Status Word [1610] Power [kW] [1695] Ext.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 9-53 Profibus Warning Word 9-70 Programming Set-up Range: Option: 0* Function: Select the set-up to be edited. [0 - 65535 ] This parameter displays Profibus communication warnings. Please refer to the Profibus Operating Instructions for further information. Function: [0] Factory setup Uses default data. This option can be used as a data source to return the other set-ups to a known state. [1] Set-up 1 Edits Set-up 1.
Parameter Description VLT® HVAC Drive Programming Guide 9-80 Defined Parameters (1) 9-92 Changed Parameters (3) Array [116] No LCP access Read only Array [116] No LCP access Read only Range: 0* Function: Range: [0 - 9999 ] This parameter displays a list of all the defined frequency converter parameters available for Profibus. 0* Function: [0 - 9999 ] This parameter displays a list of all the frequency converter parameters deviating from default setting.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 3.11 Main Menu - CAN Fieldbus - Group 10 3.11.1 10-** DeviceNet and CAN Fieldbus 3.11.2 10-0* Common Settings 3.11.3 10-1* DeviceNet 10-10 Process Data Type Selection Option: 10-00 CAN Protocol Option: [1] * Function: DeviceNet dependent upon the setting of 8-10 Control View the active CAN protocol. Profile. NOTE When 8-10 Control Profile is set to [0] FC profile, 10-10 Process Data Type Selection options [0] and [1] are available.
VLT® HVAC Drive Programming Guide Parameter Description 10-11 Process Data Config Write Option: 10-12 Process Data Config Read Function: Option: [417] Torque Limit Generator Mode [1618] Motor Thermal [590] Digital & Relay Bus Control [1622] Torque [%] [593] Pulse Out #27 Bus Control [1626] Power Filtered [kW] [595] Pulse Out #29 Bus Control [1627] Power Filtered [hp] [597] Pulse Out #X30/6 Bus Control [1630] DC Link Voltage [653] Terminal 42 Output Bus Control [1632] Brake Energy /s [
Parameter Description VLT® HVAC Drive Programming Guide 10-13 Warning Parameter 10-21 COS Filter 2 Range: Range: 0* 3 3 Function: [0 - 65535 ] View a DeviceNet-specific Warning word. One bit is assigned to every warning. Please refer to the DeviceNet Operating Instructions (MG. 33.DX.YY) for further information. 0* Function: [0 - 65535 ] Enter the value for COS Filter 2, to set up the filter mask for the Main Actual Value.
VLT® HVAC Drive Programming Guide Parameter Description 3.12 Main Menu - LonWorks - Group 11 Parameter group for all LonWorks specific parameters. Parameters related to LonWorks ID. 11-21 Store Data Values Option: 11-00 Neuron ID Range: 0* Function: [0 - 0 ] View the Neuron chip's unique Neuron ID number. 11-10 Drive Profile Option: Function: This parameter is used to activate storing of data in non-volatile memory. [0] * Off Store function is inactive.
3.13 Main Menu - Smart Logic - Group 13 3.13.1 13-** Prog. Features Prog. Features Smart Logic Control (SLC) is essentially a sequence of user defined actions (see 13-52 SL Controller Action [x]) executed by the SLC when the associated user defined event (see 13-51 SL Controller Event [x]) is evaluated as TRUE by the SLC. Events and actions are each numbered and linked together in pairs. This means that when event [0] is fulfilled (attains the value TRUE), action [0] is executed.
VLT® HVAC Drive Programming Guide Parameter Description 13-01 Start Event Option: 13-01 Start Event Function: Option: Function: [22] Comparator 0 Use the result of comparator 0 in the logic rule. [44] Reset Key This event is TRUE if the Reset key on the LCP is pressed. [23] Comparator 1 Use the result of comparator 1 in the logic rule. [45] Left Key This event is TRUE if the Left key on the LCP is pressed. [24] Comparator 2 Use the result of comparator 2 in the logic rule.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 13-02 Stop Event Option: 13-02 Stop Event Function: Option: Function: [8] Below I low See parameter group 5-3* for further description. [31] SL Time-out 1 Use the result of timer 1 in the logic rule. [9] Above I high See parameter group 5-3* for further description. [32] SL Time-out 2 Use the result of timer 2 in the logic rule.
VLT® HVAC Drive Programming Guide Parameter Description 13-02 Stop Event Option: Function: [51] Comparator 5 Use the result of comparator 5 in the logic rule. [60] Logic rule 4 Use the result of logic rule 4 in the logic rule. [61] Logic rule 5 Use the result of logic rule 5 in the logic rule. [70] SL Time-out 3 Use the result of timer 3 in the logic rule. [71] SL Time-out 4 Use the result of timer 4 in the logic rule. [72] SL Time-out 5 Use the result of timer 5 in the logic rule.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 13-10 Comparator Operand 13-10 Comparator Operand Array [4] Array [4] Option: Function: Option: Function: [68] Below I low [161] Relay 2 [69] Above I high [180] Local ref. active [70] Out of speed range [181] Remote ref. active [71] Below speed low [182] Start command [72] Above speed high [183] Drive stopped [75] Out of feedb. range [185] Drive in hand mode [76] Below feedb.
VLT® HVAC Drive Programming Guide Parameter Description 3.13.4 13-2* Timers 13-40 Logic Rule Boolean 1 Use the result (TRUE or FALSE) from timers directly to define an event (see 13-51 SL Controller Event), or as boolean input in a logic rule (see 13-40 Logic Rule Boolean 1, 13-42 Logic Rule Boolean 2 or 13-44 Logic Rule Boolean 3). A timer is only FALSE when started by an action (i.e. Start timer 1 [29]) until the timer value entered in this parameter is elapsed. Then it becomes TRUE again.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 13-40 Logic Rule Boolean 1 13-40 Logic Rule Boolean 1 Array [6] Array [6] Option: Function: Option: Function: [24] Comparator 2 Use the result of comparator 2 in the logic rule. [43] OK Key This logic rule is TRUE if the OK key on the LCP is pressed. [25] Comparator 3 Use the result of comparator 3 in the logic rule. [44] Reset Key This logic rule is TRUE if the Reset key on the LCP is pressed.
VLT® HVAC Drive Programming Guide Parameter Description 13-41 Logic Rule Operator 1 13-42 Logic Rule Boolean 2 Array [6] Array [6] Option: [0] * DISABLED Function: Option: Select the first logical operator to use on [15] Above feedb. high the Boolean inputs from 13-40 Logic Rule [16] Thermal warning Boolean 1 and 13-42 Logic Rule Boolean 2. [13-**] signifies the boolean input of parameter group 13-**.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 13-42 Logic Rule Boolean 2 13-44 Logic Rule Boolean 3 Array [6] Array [6] Option: Function: Option: [91] ECB Bypass Mode [11] Below speed low [92] ECB Test Mode [12] Above speed high [100] Fire Mode [13] Out of feedb. range [14] Below feedb. low [15] Above feedb.
VLT® HVAC Drive Programming Guide Parameter Description 13-44 Logic Rule Boolean 3 13-51 SL Controller Event Array [6] Array [20] Option: Function: Option: [81] Dry Pump [31] SL Time-out 1 [82] End of Curve [32] SL Time-out 2 [83] Broken Belt [33] Digital input DI18 [90] ECB Drive Mode [34] Digital input DI19 [91] ECB Bypass Mode [35] Digital input DI27 [92] ECB Test Mode [36] Digital input DI29 [37] Digital input DI32 [38] Digital input DI33 [39] Start command [100] F
3 3 VLT® HVAC Drive Programming Guide Parameter Description 13-52 SL Controller Action 13-52 SL Controller Action Array [20] Array [20] Option: [2] Select set-up 1 Function: Option: Changes the active set-up (0-10 Active Set digital out A low Any output with ‘digital output 1’ selected is low (off). [33] Set digital out B low Any output with ‘digital output 2’ selected is low (off). [34] Set digital out C low Any output with ‘digital output 3’ selected is low (off).
VLT® HVAC Drive Programming Guide Parameter Description 3.14 Main Menu - Special Functions -Group 14 3.14.1 14-0* Inverter Switching 14-03 Overmodulation Option: 14-00 Switching Pattern Option: Function: Select the switching pattern: 60° AVM or SFAVM. [0] * 60 AVM [1] 14-04 PWM Random Option: SFAVM Function: [0] * Off No change of the acoustic motor switching noise. 14-01 Switching Frequency Option: Function: (from 0% at nominal speed rising to approximately 12% at double nominal speed).
130BT101.10 DC Voltage Output Speed rpm Over Voltage Control Level Par 14-11 Time Mains DC Voltage Output Speed rpm Over Voltage Control Level Par 14-11 130BT108.10 Illustration 3.5 Controlled Ramp down - short mains failure. Ramping down to stop followed by ramping up to reference. Time Mains 14-12 Function at Mains Imbalance Option: [0] * Trip Function: Select Trip [0] to trip the frequency converter. [1] Warning Select Warning [1] to issue a warning.
VLT® HVAC Drive Programming Guide 14-22 Operation Mode 14-22 Operation Mode Option: Option: Function: Function: Use this parameter to specify normal operation, to perform tests or to initialise all parameters 12 13 18 19 27 29 32 33 20 37 except 15-03 Power Up's, 15-04 Over Temp's and 15-05 Over Volt's. This function is active only when the power is cycled (power off-power on) to the frequency converter.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 14-40 VT Level 14-29 Service Code Range: 0* Function: [-2147483647 - 2147483647 ] Service use only. Range: 66 %* 3.14.3 14-3* Current Limit Control The frequency converter features an integral Current Limit Controller which is activated when the motor current, and thus the torque, is higher than the torque limits set in 4-16 Torque Limit Motor Mode and 4-17 Torque Limit Generator Mode.
VLT® HVAC Drive Programming Guide Parameter Description 3.14.5 14-5* Environment 14-52 Fan Control These parameters help the frequency converter to operate under special environmental conditions. Option: Function: converter is in the range +35°C to approximately +55°C. The fan will run at low speed at +35°C and at full speed at approximately 3.14.6 14-50 RFI Filter +55°C.
3.14.8 No Trip at Inverter Overload 14-61 Function at Inverter Overload In some pump systems, the frequency converter has not been sized properly to yield the current needed in all points of the operational flow-head characteristic. At these points, the pump will need a current higher than the rated current of the frequency converter. The frequency converter can yield 110% of the rated current continuously for 60 sec.
VLT® HVAC Drive Programming Guide Parameter Description 3.15 Main Menu - Drive Information - Group 15 Parameter group containing frequency converter information such as operating data, hardware configuration and software versions. Option: [0] * Do not reset 15-00 Operating Hours 0 h* The reset is carried out by pressing [OK]. Function: [0 - 2147483647 h] View how many hours the frequency converter has run.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 15-10 Logging Source 15-12 Trigger Event Array [4] Option: [2] Running [1627] Power Filtered [hp] [3] In range [1630] DC Link Voltage [4] On reference [1632] Brake Energy /s [5] Torque limit [1633] Brake Energy /2 min [6] Current limit Option: Function: Function: [1634] Heatsink Temp.
VLT® HVAC Drive Programming Guide Parameter Description 15-14 Samples Before Trigger 15-21 Historic Log: Value Range: Array [50] 50 * Function: [0 - 100 ] Enter the percentage of all samples prior to a trigger event which are to be retained in the Range: Function: Digtal input log. See also 15-12 Trigger Event and 16-60 Digital Input for description after converting to binary value. 15-13 Logging Mode. 3.15.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 3.15.4 15-3* Alarm Log 15-42 Voltage Parameters in this group are array parameters, where up to 10 fault logs can be viewed. [0] is the most recent logged data, and [9] the oldest. Error codes, values, and time stamp can be viewed for all logged data. Range: 0* Function: [0 - 0 ] View the FC type. The read-out is identical to the frequency converter series power field of the type code definition, characters 11-12.
Parameter Description VLT® HVAC Drive Programming Guide 3.15.6 15-6* Option Ident. 15-75 Slot C0 Option SW Version This read-only parameter group contains information about the hardware and software configuration of the options installed in slots A, B, C0 and C1. Range: 0* Function: [0 - 0 ] View the software version for the option installed in slot C. 15-60 Option Mounted 15-76 Option in Slot C1 Range: Range: 0* [0 - 0 ] Function: View the installed option type.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 3.16 Main Menu - Data Readouts - Group 16 3.16.1 16-1* Motor Status 16-00 Control Word Range: 0* Function: [0 - 65535 ] View the Control word sent from the frequency converter via the serial communication port in hex code. 16-01 Reference [Unit] Range: [-999999.000 999999.
VLT® HVAC Drive Programming Guide Parameter Description 3.16.2 16-3* Drive Status 16-16 Torque [Nm] Range: 0.0 Nm* Function: [-30000.0 - View the torque value with sign, applied to 30000.0 the motor shaft. Linearity is not exact Nm] between 110% motor current and torque in relation to the rated torque. Some motors supply more than 160% torque. Consequently, the min. value and the max. value will depend on the max. motor current as well as the motor used. The value is filtered, and thus approx. 1.3 sec.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 16-39 Control Card Temp. 16-52 Feedback [Unit] Range: Range: 0 °C* Function: Function: par. 16-56) in the feedback manager. [0 - 100 °C] View the temperature on the control card, stated in °C See parameter group 20-0* 16-40 Logging Buffer Full Option: Feedback. Function: The value is limited by View whether the logging buffer is full (see parameter group 15-1*).
VLT® HVAC Drive Programming Guide Parameter Description 16-61 Terminal 53 Switch Setting 16-56 Feedback 3 [Unit] Range: Function: 0.000 ProcessCtrlUnit* [-999999.999 999999.999 ProcessCtrlUnit] Feedback. View the setting of input terminal 53. Current = 0; Voltage = 1. [0] Current The value is limited by [1] Voltage settings in 20-13 Minimum [2] Pt 1000 [°C] Reference/Feedb. and [3] Pt 1000 [°F] 20-12 Reference/Feedback Unit.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 16-69 Pulse Output #27 [Hz] 16-77 Analog Out X30/8 [mA] Range: Range: 0* Function: [0 - 40000 ] View the actual value of impulses applied to terminal 27 in digital output mode. 16-70 Pulse Output #29 [Hz] Range: 0* 0.000 * Function: [0.000 - 30.000 ] View the actual value at input X30/8 in mA. 3.16.5 16-8* Fieldbus & FC Port Function: [0 - 40000 ] View the actual value of pulses to terminal 29 in digital output mode.
VLT® HVAC Drive Programming Guide Parameter Description 3.16.6 16-9* Diagnosis Read-Outs 16-96 Maintenance Word Range: 16-90 Alarm Word Range: 0* Function: [0 - 4294967295 ] View the alarm word sent via the serial communication port in hex code. 16-91 Alarm Word 2 Range: 0* Function: [0 - 4294967295 ] View the alarm word 2 sent via the serial communication port in hex code.
Parameter Description VLT® HVAC Drive Programming Guide 16-96 Maintenance Word Range: Function: The third digit 0 indicates that no items from the second row requires maintenance The fourth digit A refers to the top row indicating that the Valve and the Pump Bearings require maintenance 3 3 126 MG11CD02 - VLT® is a registered Danfoss trademark
VLT® HVAC Drive Programming Guide Parameter Description 3.17 Main Menu - Data Readouts 2 - Group 18 3.17.1 18-0* Maintenance Log This group contains the last 10 Preventive Maintenance events. Maintenance Log 0 is the latest and Maintenance Log 9 the oldest. By selecting one of the logs and pressing [OK], the Maintenance Item, Action and time of the occurrence can be found in 18-00 Maintenance Log: Item – 18-03 Maintenance Log: Date and Time.
VLT® HVAC Drive Programming Guide Parameter Description 18-12 Fire Mode Log: Date and Time 18-34 Analog Out X42/9 [V] Range: Range: Size related* 3 3 Function: [ 0 - This parameter contains an array with 10 0] elements. The parameter shows at which date and time the logged event occurred. The function relies on that the actual date 0.000 * Function: [0.000 30.000 ] and time has been set in 0-70 Date and Time. Note: There is no build in battery back up of the clock.
VLT® HVAC Drive Programming Guide Parameter Description 3.18 Main Menu - FC Closed Loop - Group 20 This parameter group is used for configuring the closed loop PID Controller, that controls the output frequency of the frequency converter. 3.18.1 20-0* Feedback 0% Setpoint 1 Setpoint to Reference Handling 130BA354.12 This parameter group is used to configure the feedback signal for the frequency converter’s closed loop PID Controller.
3 3 VLT® HVAC Drive Programming Guide Parameter Description NOTE 20-02 Feedback 1 Source Unit If a feedback is not used, its source must be set to No Function [0]. 20-20 Feedback Function determines how the three possible feedbacks will be used by the PID Controller. 20-01 Feedback 1 Conversion Option: Function: This parameter allows a conversion function to be applied to Feedback 1. [0] Linear [0] has no effect on the feedback.
VLT® HVAC Drive Programming Guide Parameter Description NOTE 20-06 Feedback 3 Source This parameter is only available when using pressure to temperature feedback conversion. If the choice Linear [0] is selected in 20-01 Feedback 1 Conversion, then the setting of any choice in 20-02 Feedback 1 Source Unit does not matter as conversion will be one-to-one.
Parameter Description VLT® HVAC Drive Programming Guide 20-20 Feedback Function 20-14 Maximum Reference/Feedb. Range: 100.000 ProcessCtrlUnit* 3 3 Function: [ par. 20-13 - Enter the maximum 999999.999 reference/feedback for ProcessCtrlUnit] closed loop operation. The setting determines the highest value obtainable by summing all reference sources for closed loop operation. The setting determines 100% feedback in open and closed loop (total feedback range: -200% to +200%).
Parameter Description VLT® HVAC Drive Programming Guide 20-20 Feedback Function Option: Function: setpoint reference. If all feedback signals are above their corresponding setpoints, the PID Controller will use the feedback/setpoint pair in which the difference between the feedback and setpoint is the least. The frequency converter can be configured to handle multi zone applications.
The difference between the two is illustrated by the following examples: Example 1 – Multi zone, single setpoint In an office building, a VAV (variable air volume) VLT® HVAC Drive system must ensure a minimum pressure at selected VAV boxes. Due to the varying pressure losses in each duct, the pressure at each VAV box cannot be assumed to be the same. The minimum pressure required is the same for all VAV boxes.
VLT® HVAC Drive Programming Guide Parameter Description 20-31 User Defined Refrigerant A1 20-23 Setpoint 3 Range: 0.000 ProcessCtrlUnit* Function: [ par. 20-13 - Setpoint 3 is used in par. 20-14 Closed Loop Mode to enter ProcessCtrlUnit] a setpoint reference that may be used by the frequency converter’s PID Controller. See the description of 20-20 Feedback Function. NOTE The setpoint reference entered here is added to any other references that are enabled (see parameter group 3-1*).
3 3 VLT® HVAC Drive Programming Guide Parameter Description 20-36 Fan 2 Area [m2] 20-60 Sensorless Unit Range: Option: Function: 0.500 m2* [0.000 10.000 m2] [121] gal/s [122] gal/min [123] gal/h [124] CFM 20-37 Fan 2 Area [in2] Range: [125] ft³/s Function: Used for setting the area of the air ducts in connection with feedback conversion pressure/velocity to flow. The unit (in2) is determined by the setting of 0-03 Regional Settings. Fan 2 is used with feedback 2.
VLT® HVAC Drive Programming Guide Parameter Description 0 (zero). 20-81 PID Normal/ Inverse Control is determined during tuning process. These calculated values are presented on the LCP and the user can decide whether to accept or reject them. Once accepted, the values are written to the relevant parameters and auto-tuning mode is disabled in 20-79 PID Autotuning. Depending on the system being controlled the time required to carry out auto-tuning could be several minutes.
3 3 Parameter Description VLT® HVAC Drive Programming Guide 20-81 PID Normal/ Inverse Control 20-84 On Reference Bandwidth Option: Range: Function: will show “Run on Reference”. This status can be communicated externally by programming the [0] * Normal Normal [0] causes the frequency converter’s output frequency to decrease when the feedback is greater than the setpoint reference. This is common for pressure-controlled supply fan and pump applications.
Parameter Description VLT® HVAC Drive Programming Guide 20-94 PID Integral Time 20-96 PID Diff. Gain Limit Range: Range: 20.00 s* Function: [0.01 10000.00 s] Over time, the integrator accumulates a contribution to the output from the PID controller as long as there is a deviation between the Reference/Setpoint and feedback signals. The contribution is proportional to the size of the deviation. This ensures that the deviation (error) approaches zero.
3 3 Parameter Description VLT® HVAC Drive Programming Guide 3.19 Main Menu - Extended Closed Loop - Group 21 The FC 102 offers 3 Extended Closed Loop PID controllers in addition to the PID Controller. These can be configured independently to control either external actuators (valves, dampers etc.) or be used together with the internal PID Controller to improve the dynamic responses to setpoint changes or load disturbances.
VLT® HVAC Drive Programming Guide 21-02 PID Output Change 21-09 PID Autotuning Range: Option: 0.10 * Function: [0.01 0.50 ] This parameter sets the magnitude of step change during autotuning. The value is a percentage of full operating range. I.e. if maximum analog output voltage is set to 10 V, 0.10 is 10% of 10 V, which is 1 V. This parameter should be set to a value resulting in feedback changes of between 10% and 20% for best tuning accuracy.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 21-10 Ext. 1 Ref./Feedback Unit 21-13 Ext. 1 Reference Source Option: Option: [73] kPa [74] m WG [75] mm Hg [80] kW Function: This parameter defines which input on the frequency converter should be treated as the source of the reference signal for the Closed Loop 1 Controller. Analog input X30/11 and Analog input X30/12 refer to inputs on the General Purpose I/O.
VLT® HVAC Drive Programming Guide Parameter Description NOTE 21-15 Ext. 1 Setpoint Range: Function: 0.000 ExtPID1Unit* [ par. 21-11 - The setpoint reference is par. 21-12 used in extended 1 closed ExtPID1Unit] loop. Ext.1 Setpoint is added to the value from the Ext.1 Reference source selected in 21-13 Ext. 1 Reference Source. 21-17 Ext. 1 Reference [Unit] Range: Always set the desired for 20-14 Maximum Reference/Feedb. before setting the values for the PID controller in parameter group 20-9*.
3 3 Parameter Description VLT® HVAC Drive Programming Guide 3.19.4 21-3* Closed Loop 2 Ref/Fb 21-31 Ext. 2 Minimum Reference Range: 21-30 Ext. 2 Ref./Feedback Unit Option: 0.000 ExtPID2Unit* Function: See 21-10 Ext. 1 Ref./Feedback Unit for details [0] None [1] * % [5] PPM [10] 1/min [11] RPM [12] Pulse/s [20] l/s [21] l/min [22] l/h [23] m³/s Function: [ -999999.999 - par. See 21-11 Ext. 1 21-32 ExtPID2Unit] Minimum Reference for details. 21-32 Ext.
VLT® HVAC Drive Programming Guide Parameter Description 3.19.6 21-5* Closed Loop 3 Ref/Fb 21-35 Ext. 2 Setpoint Range: Function: 0.000 ExtPID2Unit* [ par. 21-31 - par. See 21-15 Ext. 1 21-32 ExtPID2Unit] Setpoint for details. Range: Function: [-999999.999 999999.999 ExtPID2Unit] See 21-17 Ext. 1 Reference [Unit], Ext. 1 Reference [Unit], for details. 21-38 Ext. 2 Feedback [Unit] Range: Function: 0.000 ExtPID2Unit* Option: [-999999.999 999999.999 ExtPID2Unit] See 21-18 Ext.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 21-51 Ext. 3 Minimum Reference Range: 0.000 ExtPID3Unit* 21-55 Ext. 3 Setpoint Function: [ -999999.999 - par. See 21-11 Ext. 1 21-52 ExtPID3Unit] Minimum Reference for details. Range: Function: 0.000 ExtPID3Unit* [ par. 21-51 - par. See 21-15 Ext. 1 21-52 ExtPID3Unit] Setpoint for details. 21-57 Ext. 3 Reference [Unit] 21-52 Ext. 3 Maximum Reference Range: 100.000 ExtPID3Unit* Range: Function: Function: 0.000 ExtPID3Unit* [ par.
VLT® HVAC Drive Programming Guide Parameter Description 3.20 Main Menu - Application Functions - Group 22 This group contains parameters used for monitoring VLT® HVAC Drive applications. 22-00 External Interlock Delay Range: Function: removed from the digital input programmed for External Interlock, before reaction takes place.
VLT® HVAC Drive Programming Guide Parameter Description NOTE 130BA253.10 FC 3 3 Head 1 130BA254.10 Carry out No Flow tuning before setting the PI controller parameters! 2 Flow P No Flow Detection is based on the measurement of speed and power. For a certain speed the frequency converter calculates the power at no flow. This coherence is based on the adjustment of two sets of speed and associated power at no flow.
VLT® HVAC Drive Programming Guide Parameter Description Dry pump detection: No Flow Detection can also be used for detecting if the pump has run dry (low power consumption-high speed). Can be used with both the integrated PI controller and an external PI controller. The condition for Dry Pump signal: - Power consumption below no flow level and NOTE Carry out the tuning with the same settings in 1-03 Torque Characteristics, as for operation after the tuning.
VLT® HVAC Drive Programming Guide Parameter Description 3.20.2 22-3* No-Flow Power Tuning 22-24 No-Flow Delay Range: 10 s* Function: [1 - 600 s] Set the time Low Power/Low Speed must stay detected to activate signal for actions. If detection disappears before run out of the timer, the timer will be reset. 3 3 22-26 Dry Pump Function Select desired action for dry pump operation. Option: Function: Tuning Sequence, if not choosing Auto Set Up in 22-20 Low Power Auto Set-up: 1.
VLT® HVAC Drive Programming Guide Parameter Description 22-32 Low Speed [RPM] Range: Size related* 22-38 High Speed Power [kW] Function: Range: [ 0 - par. To be used if 0-02 Motor Speed Unit 22-36 RPM] has been set for RPM (parameter not visible if Hz selected). Set used speed for the 50% level. This function is used for storing values needed to tune No Flow Detection. Size related* Function: [ 0.00 - To be used if 0-03 Regional Settings has 0.
When entering Sleep Mode, the lower status line in the Local Control Panel shows Sleep Mode. 130BA255.11 See also signal flow chart in 3.20.1 22-2* No-Flow Detection. There are three different ways of using the Sleep Mode function: If no flow is detected, the frequency converter will increase the set point for pressure to ensure a slight over pressure in the system (boost to be set in 22-45 Setpoint Boost).
VLT® HVAC Drive Programming Guide Parameter Description When low power or low speed is detected the motor is stopped, but the reference signal (fref) from the external controller is still monitored and because of the low pressure created, the controller will increase the reference signal to gain pressure. When the reference signal has reached a set value fwake the motor restarts. The speed is set manually by an external reference signal (Remote Reference).
Parameter Description VLT® HVAC Drive Programming Guide 22-45 Setpoint Boost 22-50 End of Curve Function Range: Option: 0 %* 3 3 [-100 - 100 %] Function: Only to be used if 1-00 Configuration Mode, is set for Closed Loop and the integrated PI controller is used. In systems with e.g. constant pressure control, it is advantageous to increase the system pressure before the motor is stopped. This will extend the time in which the motor is stopped and help to avoid frequent start/stop.
Parameter Description VLT® HVAC Drive Programming Guide broken belt function (22-60 Broken Belt Function) is performed 22-60 Broken Belt Function Selects the action to be performed if the Broken Belt condition is detected Option: Function: [0] * Off [1] [2] Warning The frequency converter will continue to run, but activate a Broken Belt Warning [W95]. A frequency converter digital output or a serial communication bus can communicate a warning to other equipment.
HDESIGN (Required pressure) is the setpoint for closed loop (PI) operation of the frequency converter and is set as for closed loop operation without flow compensation. 130BA547.10 H(head) HDESIGN Set Point It is recommended to use slip compensation and RPM as unit. HMIN 130BA383.11 3 3 VLT® HVAC Drive Programming Guide Parameter Description P22-87 1 2 3 Number of pumps There are two methods which can be employed, depending upon whether or not the Speed at System design Working Point is known.
VLT® HVAC Drive Programming Guide Parameter Description 130BA388.11 H (head) Option: Function: curve which will also include the System design Working Point A. 0% H (head) % 100 HRATED Par. 22-88 H DESIGN D B A D TE DESIGN Par. 22-89 Q RATED ED ESI T -f RA GN Q (flow) I ES HMIN Par.: 22-83/ 22-84/ Control Curve 22-87 Q n RA GN -f D Control Curve C nD Set point 3 3 130BA387.11 -81 P22 22-82 Work Point Calculation Q (flow) Par.
VLT® HVAC Drive Programming Guide Parameter Description 22-84 Speed at No-Flow [Hz] 22-88 Pressure at Rated Speed Range: Range: Size related* 3 3 Function: [ 0.0 - Resolution 0.033 Hz. par. The speed of the motor at which flow has 22-86 Hz] effectively stopped and minimum pressure HMIN is achieved should be 999999.999 * entered here in Hz. Alternatively, the speed in RPM can be entered in 22-83 Speed at No-Flow [RPM].
Parameter Description VLT® HVAC Drive Programming Guide 3.21 Main Menu - Time-based Functions - Group 23 NOTE 3.21.1 23-0* Timed Actions Use Timed Actions for actions needing to be performed on a daily or weekly basis, e.g. different references for working hours / non-working hours. Up to 10 Timed Actions can be programmed in the frequency converterThe Timed Action number is selected from the list when entering parameter group 23-0* from the LCP.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 23-01 ON Action 23-03 OFF Action Arra [10] Array [10] Option: Function: Option: Function: [36] Set digital out E low [12] Select preset ref 2 [37] Set digital out F low [13] Select preset ref 3 [38] Set digital out A high [14] Select preset ref 4 [39] Set digital out B high [15] Select preset ref 5 [40] Set digital out C high [16] Select preset ref 6 [41] Set digital out D high [17] Select preset ref 7 [42] Set d
VLT® HVAC Drive Programming Guide Parameter Description 3.21.2 23-1* Maintenance 23-08 Timed Actions Mode Used to enable and disable automatic timed actions. Option: Function: [0] * Timed Actions Auto Enable timed actions. [1] Timed Actions Disabled Disable timed actions, normal operation according to control commands. [2] Constant On Actions Disable timed actions. Constant On Actions activated. [3] Constant Off Actions Disable timed actions. Constant Off Actions activated.
130BA492.10 VLT® HVAC Drive Programming Guide Parameter Description Untitled - MCT 10 SET - up Software File Edit View Insert Communication Tools Network Project + - - 3 3 VLT AQUA DRIVE All Parameters + + + + + + + + + + + + + + + + - Operation/Display Load/Motor Brakes Reference / Ramps Limits / Warnings Digital In/Out Analog In/Out Comm. andOptions Smart logic Special Functions Drive Information Data Readouts Info & Readouts Drive Closed Loop Ext.
VLT® HVAC Drive Programming Guide Parameter Description 23-11 Maintenance Action 23-13 Maintenance Time Interval Option: Range: Function: Function: will be indicated the following Monday at 8:00. If this Maintenance Event is not reset until Tuesday at 9:00, the next occurrence will be the following Tuesday at 9:00. Select the action to be associated with the Preventive Maintenance Event.
VLT® HVAC Drive Programming Guide 23-16 Maintenance Text Range: Function: The text is written according to the guidelines in 0-37 Display Text 1. 3.21.3 23-5* Energy Log The frequency converter is continuously accumulating the consumption of the motor controlled, based on the actual power yielded by the frequency converter. These data can be used for an Energy Log function allowing the user to compare and structure the information about the energy consumption related to time.
VLT® HVAC Drive Programming Guide Parameter Description 23-51 Period Start Range: Size related* 23-54 Reset Energy Log Function: Option: Function: Select Do reset [1] to reset all values in the [ 0 - Set the date and time at which the Energy 0] Log starts update of the counters. First data will be stored in counter [00] and start at the time/date programmed in this parameter. Energy Log counters shown in 23-53 Energy Log.
VLT® HVAC Drive Programming Guide exceed rated value, but those registrations will be included in 90%-100% (MAX) counter. Relative value operating variable % 100 90 80 70 60 50 40 30 20 10 Counter 9: +0 Counter 8: +6 Counter 7: +2 Counter 6: +1 Counter 5: +11 Counter 4: +0 Counter 3: +1 Counter 2: +0 Counter 1: +1 Counter 0: +5 130BA281.10 3 3 Parameter Description 23-61 Continuous Bin Data Range: 0 * [0 4294967295 ] Function: Array with 10 elements ([0]-[9] below parameter number in display).
VLT® HVAC Drive Programming Guide Parameter Description 23-63 Timed Period Start 23-66 Reset Continuous Bin Data Range: Option: Function: Size related* [ 0 - 0 ] Set the date and time at which the Trending starts the update of the Timed Bin counters. Function: [0] * Do not reset Select Do reset [1] to reset all values in 23-61 Continuous Bin Data. After pressing OK the setting of the parameter value will automatically change to Date format will depend on setting in Do not reset [0].
3 3 VLT® HVAC Drive Programming Guide Parameter Description Cost Savings = { t ∑ ( Rated Motor Power ∗ Power Reference Factor ) t =0 × Energy Cost } − Actual Power Consumption − Investment Cost Break even (payback) occurs when the value read in the parameter turns from negative to positive. It is not possible to reset the Energy Savings counter, but the counter can be stopped any time by setting 23-80 Power Reference Factor to 0.
VLT® HVAC Drive Programming Guide Parameter Description 3.22 Main Menu - Application Functions 2 - Group 24 3.22.1 24-0* Fire Mode CAUTION Please note the frequency converter is only one component of the VLT® HVAC Drive system. Correct function of Fire Mode depends on the correct design and selection of system components. Ventilation systems working in life safety applications have to be approved by the local fire Authorities.
3 3 VLT® HVAC Drive Programming Guide Parameter Description NOTE 24-01 Fire Mode Configuration If in Fire Mode it is desired to use the Live Zero function, then it will also be active for analog inputs other than that used for Fire Mode setpoint / feedback. Should the feedback to any of those other analog inputs be lost, for example a cable is burned, Live Zero function will operate. If this is undesirable then Live Zero function must be disabled for those other inputs.
VLT® HVAC Drive Programming Guide Parameter Description 24-02 Fire Mode Unit 24-05 Fire Mode Preset Reference Option: Range: Function: [122] gal/min 0.00 %* [123] gal/h Function: [-100.00 100.00 %] Enter the required preset reference/set point as a percentage of the Fire Mode [124] CFM Max Reference set in 24-04 Fire Mode [125] ft³/s Max Reference.
VLT® HVAC Drive Programming Guide 24-09 Fire Mode Alarm Handling Option: [0] 3 3 Function: Trip+Reset, Critical Alarms If this mode is selected, the frequency converter will continue to run, ignoring most alarms, even if doing so it may result in damage of the frequency converter. Critical alarms are alarms, which cannot be suppressed but a restart attempt is possible (Infinity Automatic Reset).
Parameter Description VLT® HVAC Drive Programming Guide 24-10 Drive Bypass Function 24-11 Drive Bypass Delay Time Option: Range: Function: Where no restart attempts are programmed, the timer will run for the delay period set in this parameter and will then activate the Drive Bypass relay, which will have been programmed for Bypass This parameter determines, what circumstances will activate the Drive Bypass Function: [0] * Disabled [1] Enabled Function: If in normal operation the automatic Drive B
3 3 VLT® HVAC Drive Programming Guide Parameter Description 24-96 Locked Rotor Coefficient 1 Range: 0.0000 * Function: [-10.0000 10.0000 ] Enter the cubic coefficient of the Locked Rotor detection function multiplied by 1000. 24-97 Locked Rotor Coefficient 2 Range: 0.0000 * Function: [-100.0000 100.0000 ] Enter the quadratic coefficient of the Locked Rotor detection function multiplied by 1000. 24-98 Locked Rotor Coefficient 3 Range: 0.0000 * Function: [-100.0000 100.
VLT® HVAC Drive Programming Guide Parameter Description 3.23 Main Menu - Cascade Controller - Group 25 Parameters for configuring the Basic Cascade Controller for sequence control of multiple pumps. For a more application oriented description and wiring examples, see Chapter Application Examples, item Basic Cascade Controller in the Design Guide, MG20NXYY.
3 3 Parameter Description VLT® HVAC Drive Programming Guide 3.23.1 25-0* System Settings 25-05 Fixed Lead Pump Parameters related to control principles and configuration of the system. Option: and pump, this contactor will not be controlled by the frequency converter. If operating with 25-50 Lead Pump Alternation set to 25-00 Cascade Controller Option: other than Off[0], this parameter must be set to No [0].
Parameter Description VLT® HVAC Drive Programming Guide 25-20 Staging Bandwidth 25-21 Override Bandwidth Range: Range: 10 %* Function: pressure changes. Setting the OBW too high might lead to unacceptably high or low pressure in the system while the SBW timers are running. The value can be optimized with increased familiarity with the [ 1 - Set the staging bandwidth (SBW) percentage to par. accommodate normal system pressure fluctuation.
VLT® HVAC Drive Programming Guide 25-23 SBW Staging Delay 25-25 OBW Time Range: Range: 15 s* 3 3 Function: Function: after staging. The 10 second factory setting is appropriate in most applications. In highly dynamic systems, a shorter time may be desirable. [1 Immediate staging of a fixed speed pump is not 3000 s] desirable when a momentary pressure drop in the system exceeds the Staging Bandwidth (SBW). Staging is delayed by the length of time programmed.
VLT® HVAC Drive Programming Guide Parameter Description 25-29 Destage Function 25-41 Ramp Up Delay Option: Range: Function: The Destage Function ensures that the lowest numbers of pumps are running to save energy and to avoid dead head water circulation in the variable speed pump. If the Destage Function is 2.0 s* Function: [0.0 12.
NOTE 25-44 Staging Speed [RPM] If the set-point is reached after staging before the variable speed pump reaches its minimum speed - the system will enter the state closed loop as soon as the feedback pressure is crossing the set-point. Range: Function: where nHIGH is Motor Speed High Limit and nSTAGE100% is the value of Staging Threshold.
VLT® HVAC Drive Programming Guide Parameter Description 25-47 Destaging Speed [Hz] 25-50 Lead Pump Alternation Range: Option: 0.0 Hz* [0.0 - 0.0 Hz] Function: Readout of the below calculated value for Destaging Speed. When removing a fixed speed pump, in order to prevent an undershoot of pressure, the variable speed pump ramps up to a higher speed. When the variable speed pump reaches the “Destaging Speed” the fixed speed pump is destaged.
VLT® HVAC Drive Programming Guide Parameter Description 25-54 Alternation Predefined Time Range: 3 3 [ 0 - If optionPredefined Time [3] in 0] 25-51 Alternation Event, is selected, the variable speed pump alternation is carried out every day at the specified time set in Alternation Predefined Time. Default time is midnight (00:00 or 12:00AM depending on the time format).
VLT® HVAC Drive Programming Guide Parameter Description 3.23.5 25-8* Status 25-85 Relay ON Time Readout parameters informing about the operating status of the Cascade Controller and the pumps controlled. Array [2] Range: 0 h* 25-80 Cascade Status Range: 0* Function: [0 2147483647 h] Readout of the value for Relay ON time. The Cascade Controller has separate counters for the pumps and for the relays that control the pumps.
3.24 Main Menu - Analog I/O Option MCB 109 - Group 26 The Analog I/O Option MCB 109 extends the functionality of VLT® HVAC Drive frequency converters, by adding a number of additional, programmable analog inputs and outputs. This could be especially useful in Building Management System installations where the frequency converter may be used as de-central I/O, obviating the need for an outstation and thus reducing cost. T M 130BA382.
VLT® HVAC Drive Programming Guide Parameter Description NOTE The maximum current for the analog outputs 0-10V is 1mA. NOTE Where Live Zero Monitoring is used, it is important that any analog inputs not being used for the frequency controller, i.e. being used as part of the Building Management System decentral I/O, should have their Live Zero function disabled.
3 3 Parameter Description VLT® HVAC Drive Programming Guide 3.24.1 26-0* Analog I/O Mode 26-02 Terminal X42/5 Mode Parameter group for setting up the analog I/O configuration. The option is equipped with 3 analog inputs. These analog inputs can be freely allocated to either voltage (0V - +10V), Pt 1000 or Ni 1000 temperature sensor input.
VLT® HVAC Drive Programming Guide Parameter Description 26-15 Term. X42/1 High Ref./Feedb. Value 26-24 Term. X42/3 Low Ref./Feedb. Value Range: Range: Function: 100.000 * [-999999.999 999999.999 ] Function: voltage value set in 26-20 Terminal Enter the analog input scaling value that corresponds to the X42/3 Low Voltage. high voltage value set in 26-11 Terminal X42/1 High Voltage. 26-16 Term. X42/1 Filter Time Constant Range: Range: Function: 100.000 * [-999999.999 999999.999 ] [0.001 10.
VLT® HVAC Drive Programming Guide Parameter Description 26-34 Term. X42/5 Low Ref./Feedb. Value 26-40 Terminal X42/7 Output Range: Option: 0.000 * Function: [-999999.999 999999.999 ] Enter the analog input scaling value that corresponds to the low voltage value set in 26-30 Terminal 3 3 X42/5 Low Voltage. 26-35 Term. X42/5 High Ref./Feedb. Value Range: 100.
VLT® HVAC Drive Programming Guide Parameter Description 26-43 Terminal X42/7 Bus Control 26-51 Terminal X42/9 Min. Scale Range: Range: 0.00 %* Function: be higher than the corresponding setting [0.00 - 100.00 %] Holds the level of terminal X42/7 if controlled by bus. 26-44 Terminal X42/7 Timeout Preset Range: 0.00 %* Function: Function: [0.00 100.00 %] in 26-52 Terminal X42/9 Max. Scale. See principle graph for 6-51 Terminal 42 Output Min Scale. 26-52 Terminal X42/9 Max.
3 3 VLT® HVAC Drive Programming Guide Parameter Description 26-60 Terminal X42/11 Output 26-63 Terminal X42/11 Bus Control Option: Range: Function: [102] Feedback +-200% -200% to +200% of 20-14 Maximum 0.00 %* Reference/Feedb., (0-20 mA) [103] Motor cur. 0-Imax 0 - Inverter Max. Current (16-37 Inv. Max.
Troubleshooting VLT® HVAC Drive Programming Guide 4 Troubleshooting If an alarm cannot be reset, the reason may be that its cause has not been rectified, or the alarm is trip-locked (see also table on following page). 4.1 Troubleshooting A warning or an alarm is signalled by the relevant LED on the front of the frequency converter and indicated by a code on the display.
4 4 Troubleshooting No.
VLT® HVAC Drive Programming Guide Troubleshooting No. Description Warning Alarm/ Trip Alarm/Trip Lock Parameter Reference 93 Dry Pump X X 22-2* 94 End of Curve X X 22-5* 95 Broken Belt X X 22-6* 96 Start Delayed X 22-7* 97 Stop Delayed X 22-7* 98 Clock Fault X 0-7* 4 4 201 Fire M was Active 202 Fire M Limits Exceeded 203 Missing Motor 204 Locked Rotor 243 Brake IGBT X X 244 Heatsink temp X X X 245 Heatsink sensor X X 246 Pwr.card supply X X 247 Pwr.
4 4 VLT® HVAC Drive Programming Guide Troubleshooting Alarm Word and Extended Status Word Bit Hex Dec Alarm Word Warning Word Extended Status Word 0 1 00000001 1 Brake Check Brake Check Ramping 00000002 2 Pwr. Card Temp Pwr. Card Temp AMA Running 2 00000004 4 Earth Fault Earth Fault Start CW/CCW 3 00000008 8 Ctrl.Card Temp Ctrl.Card Temp Slow Down 4 00000010 16 Ctrl. Word TO Ctrl.
VLT® HVAC Drive Programming Guide Troubleshooting 4.1.1 Alarm Words 16-90 Alarm Word Bit (Hex) 16-91 Alarm Word 2 Alarm Word (16-90 Alarm Word) Bit (Hex) Alarm Word 2 (16-91 Alarm Word 2) 00000001 00000001 00000002 Power card over temperature 00000002 Reserved 00000004 Earth fault 00000004 Service Trip, Typecode / Sparepart 00000008 Reserved 00000010 Reserved 00000008 00000010 Control word timeout 00000020 Over current 00000080 Motor thermistor over temp.
VLT® HVAC Drive Programming Guide Troubleshooting 4.1.2 Warning Words 16-92 Warning Word Bit (Hex) 16-93 Warning Word 2 Warning Word Bit (Hex) (16-92 Warning Word) 00000001 4 4 (16-93 Warning Word 2) 00000001 00000002 Power card over temperature 00000002 00000004 Earth fault 00000004 Clock Failure 00000008 Reserved Reserved 00000008 00000010 Control word timeout 00000010 00000020 Over current 00000020 00000040 00000040 00000080 Motor thermistor over temp.
VLT® HVAC Drive Programming Guide Troubleshooting 4.1.3 Extended Status Words Extended status word, 16-94 Ext. Status Word Bit (Hex) Extended Status Word (16-94 Ext. Status Word) Extended status word 2, 16-95 Ext. Status Word 2 Bit (Hex) Extended Status Word 2 (16-95 Ext.
4 4 Troubleshooting VLT® HVAC Drive Programming Guide 4.1.4 Fault Messages Troubleshooting Connect a brake resistor The warning/alarm information below defines each warning/alarm condition, provides the probable cause for the condition, and details a remedy or troubleshooting procedure. Extend the ramp time WARNING 1, 10 Volts low The control card voltage is below 10V from terminal 50. Remove some of the load from terminal 50, as the 10V supply is overloaded. Max. 15mA or minimum 590Ω.
Troubleshooting VLT® HVAC Drive Programming Guide Ensure that Motor data in parameters 1-20 through 1-25 are set correctly. Troubleshooting If an external fan is in use, check in 1-91 Motor External Fan that it is selected. Remove power and check if the motor shaft can be turned. Running AMA in 1-29 Automatic Motor Adaptation (AMA) may tune the frequency converter to the motor more accurately and reduce thermal loading. Check that the motor size matches the frequency converter.
4 4 Troubleshooting VLT® HVAC Drive Programming Guide Verify a proper installation based on EMC requirements. ALARM 18, Start failed The speed has not been able to exceed 1-77 Compressor Start Max Speed [RPM] during start within the allowed time. (set in 1-79 Compressor Start Max Time to Trip). This may be caused by a blocked motor. WARNING 23, Internal fan fault The fan warning function is an extra protective function that checks if the fan is running/mounted.
VLT® HVAC Drive Programming Guide Troubleshooting ALARM 38, Internal fault When an internal fault occurs, a code number defined in the table below is displayed. Troubleshooting Cycle power Check that the option is properly installed Check for loose or missing wiring It may be necessary to contact your Danfoss supplier or service department. Note the code number for further troubleshooting directions. No. 0 Text Serial port cannot be initialised.
4 4 VLT® HVAC Drive Programming Guide Troubleshooting ALARM 50, AMA calibration failed Contact your Danfoss supplier or Danfoss Service Department. ALARM 51, AMA check Unom and Inom The settings for motor voltage, motor current, and motor power are wrong. Check the settings in parameters 1-20 to 1-25. ALARM 52, AMA low Inom The motor current is too low. Check the setting in 4-18 Current Limit. ALARM 53, AMA motor too big The motor is too big for the AMA to operate.
Troubleshooting VLT® HVAC Drive Programming Guide ALARM 80, Drive initialised to default value Parameter settings are initialised to default settings after a manual reset. Reset the unit to clear the alarm. ALARM 92, No flow A no-flow condition has been detected in the system. 22-23 No-Flow Function is set for alarm. Troubleshoot the system and reset the frequency converter after the fault has been cleared.
5 5 VLT® HVAC Drive Programming Guide Parameter Lists 5 Parameter Lists 5.1 Parameter Options 5.1.1 Default settings Changes during operation: ”TRUE” means that the parameter can be changed while the frequency converter is in operation and “FALSE” means that the frequency converter must be stopped before a change can be made. 4-Set-up: 'All set-up': the parameter can be set individually in each of the four set-ups, i. e. one single parameter can have four different data values.
VLT® HVAC Drive Programming Guide Parameter Lists 5.1.2 0-** Operation and Display Par. Parameter description No.
5 5 Parameter Lists Par. Parameter description No. # VLT® HVAC Drive Programming Guide Default value 4-set-up Change during operation Conversion index Type 0-81 Working Days ExpressionLimit 1 set-up TRUE - Uint8 0-82 Additional Working Days ExpressionLimit 1 set-up TRUE 0 TimeOfDay 0-83 Additional Non-Working Days ExpressionLimit 1 set-up TRUE 0 TimeOfDay 0-89 Date and Time Readout 0 N/A All set-ups TRUE 0 VisStr[25] 5.1.3 1-** Load / Motor Par. Parameter description No.
VLT® HVAC Drive Programming Guide Parameter Lists Par. Parameter description No. # Default value 4-set-up 1-66 ExpressionLimit All set-ups TRUE Parking All set-ups TRUE 0 Uint8 0.0 s All set-ups TRUE -1 Uint16 Min.
5 5 Parameter Lists VLT® HVAC Drive Programming Guide 5.1.5 3-** Reference / Ramps Par. Parameter description No. # Default value 4-set-up Change Converduring sion index operation Type 3-0* Reference Limits 3-02 Minimum Reference ExpressionLimit All set-ups TRUE -3 3-03 Maximum Reference ExpressionLimit All set-ups TRUE -3 Int32 Int32 3-04 Reference Function ExpressionLimit All set-ups TRUE - Uint8 3-1* References 3-10 Preset Reference 0.
Parameter Lists VLT® HVAC Drive Programming Guide 5.1.6 4-** Limits / Warnings Par. Parameter description No.
5 5 Parameter Lists VLT® HVAC Drive Programming Guide 5.1.7 5-** Digital In / Out Par. Parameter description No.
VLT® HVAC Drive Programming Guide Parameter Lists 5.1.8 6-** Analog In / Out Par. Parameter description No. # Default value 4-set-up Change Converduring sion index operation Type 6-0* Analog I/O Mode 6-00 Live Zero Timeout Time 10 s All set-ups TRUE 0 Uint8 6-01 Live Zero Timeout Function [0] Off All set-ups TRUE - Uint8 6-02 Fire Mode Live Zero Timeout Function [0] Off All set-ups TRUE - Uint8 6-1* Analog Input 53 6-10 Terminal 53 Low Voltage 0.
5 5 Parameter Lists VLT® HVAC Drive Programming Guide 5.1.9 8-** Communication and Options Par. No.
Parameter Lists Par. No.
5 5 Parameter Lists VLT® HVAC Drive Programming Guide 5.1.10 9-** Profibus Par. Parameter description No.
Parameter Lists VLT® HVAC Drive Programming Guide 5.1.11 10-** CAN Fieldbus Par. Parameter description No.
5 5 Parameter Lists VLT® HVAC Drive Programming Guide 5.1.13 13-** Smart Logic Controller Par. Parameter description No.
VLT® HVAC Drive Programming Guide Parameter Lists 5.1.14 14-** Special Functions Par. Parameter description No.
5 5 Parameter Lists VLT® HVAC Drive Programming Guide 5.1.15 15-** Drive Information Par. Parameter description No.
Parameter Lists Par. Parameter description No.
5 5 Parameter Lists Par. Parameter description No. # 16-50 External Reference 16-52 Feedback [Unit] 16-53 16-54 VLT® HVAC Drive Programming Guide Default value 4-set-up Change Converduring sion index operation Type 0.0 N/A All set-ups FALSE -1 Int16 0.000 ProcessCtrlUnit All set-ups FALSE -3 Int32 Digi Pot Reference 0.00 N/A All set-ups FALSE -2 Int16 Feedback 1 [Unit] 0.000 ProcessCtrlUnit All set-ups FALSE -3 Int32 16-55 Feedback 2 [Unit] 0.
Parameter Lists VLT® HVAC Drive Programming Guide 5.1.17 18-** Info & Readouts Par. Parameter description No.
5 5 Parameter Lists VLT® HVAC Drive Programming Guide 5.1.18 20-** FC Closed Loop Par. Parameter description No.
VLT® HVAC Drive Programming Guide Parameter Lists 5.1.19 21-** Ext. Closed Loop Par. Parameter description No. # Default value 4-set-up Change Converduring sion index operation Type 21-0* Ext. CL Autotuning 21-00 Closed Loop Type [0] Auto 2 set-ups TRUE - 21-01 PID Performance [0] Normal 2 set-ups TRUE - Uint8 Uint8 21-02 PID Output Change 0.10 N/A 2 set-ups TRUE -2 Uint16 21-03 Minimum Feedback Level -999999.
Parameter Lists Par. Parameter description No. # VLT® HVAC Drive Programming Guide Default value 4-set-up Change Converduring sion index operation Type [0] Normal All set-ups TRUE - Uint8 Uint16 21-6* Ext. CL 3 PID 21-60 Ext. 3 Normal/Inverse Control 21-61 Ext. 3 Proportional Gain 21-62 Ext. 3 Integral Time 21-63 Ext. 3 Differentation Time 21-64 Ext. 3 Dif. Gain Limit 0.01 N/A All set-ups TRUE -2 10000.00 s All set-ups TRUE -2 Uint32 0.00 s All set-ups TRUE -2 Uint16 5.
VLT® HVAC Drive Programming Guide Parameter Lists 5.1.20 22-** Application Functions Par. Parameter description No. # Default value 4-set-up Change Converduring sion index operation Type 0s All set-ups TRUE 0 Uint16 0.
Parameter Lists VLT® HVAC Drive Programming Guide Par. Parameter description No. # Default value 4-set-up 22-85 Speed at Design Point [RPM] ExpressionLimit All set-ups TRUE 67 Uint16 22-86 Speed at Design Point [Hz] ExpressionLimit All set-ups TRUE -1 Uint16 22-87 Pressure at No-Flow Speed 22-88 Pressure at Rated Speed 22-89 22-90 Type 0.000 N/A All set-ups TRUE -3 Int32 999999.999 N/A All set-ups TRUE -3 Int32 Flow at Design Point 0.
Parameter Lists VLT® HVAC Drive Programming Guide 5.1.21 23-** Time Based Funtions Par. Parameter description No.
5 5 Parameter Lists VLT® HVAC Drive Programming Guide 5.1.22 24-** Application Functions 2 Par. Parameter description No.
Parameter Lists VLT® HVAC Drive Programming Guide 5.1.23 25-** Cascade Pack Controller Par. Parameter description No.
5 5 Parameter Lists VLT® HVAC Drive Programming Guide 5.1.24 26-** Analog I / O Option MCB 109 Par. Parameter description No. # Default value 4-set-up Change Converduring sion index operation Type 26-0* Analog I/O Mode 26-00 Terminal X42/1 Mode [1] Voltage All set-ups TRUE - Uint8 26-01 Terminal X42/3 Mode [1] Voltage All set-ups TRUE - Uint8 26-02 Terminal X42/5 Mode [1] Voltage All set-ups TRUE - Uint8 26-1* Analog Input X42/1 26-10 Terminal X42/1 Low Voltage 0.
Index VLT® HVAC Drive Programming Guide Index Derating................................................................................................. 198 A Abbreviations........................................................................................... 4 Acceleration Time................................................................................. 54 Alarm Log...................................................................................................... 118 Words...................
Index VLT® HVAC Drive Programming Guide Programming...................................................................................... 198 L Protection Mode..................................................................................... 8 Language Package 1............................................................................................ 23 Package 2............................................................................................ 23 LCP 102.................................
Index VLT® HVAC Drive Programming Guide W Warning Words...................................................................................
www.danfoss.com/drives 130R0318 MG11CD02 *MG11CD02* Rev.