B.6 Sensor Reset for 4-Wire Smoke Detectors
AUX Connection
B.7 Other PGM Connections
SMOKE
DETECTOR
POWER
12 VDC
IN
OUT
NO
ALM
-
OUT
+
-
IN
+
BLK WHT
RED GRN
LATCHING 4-WIRE
SMOKE DETECTOR
FOR EXAMPLE,
DSC MN240 Series.
EOLR-2
END OF LINE RESISTOR
5600 0.5WΩ
Refer to installation guidelines in
Installation Manual and detector manufacturer's
literature when locating smoke detectors.
RM-1 POWER LOOP
SUPERVISORY RELAY
12V
DC 35mA MAXIMUM
WHT
4-WIRE SMOKE DETECTORS
Smoke Detector must be latching type (such as
DSC MN240 Series).
To reset smoke detectors, enter [ ] [7] [2].✱
+ AUX
PGM
2
1
Zone Input
COM
ALARM
INITIATING
LOOP
RESISTANCE:
100Ω
PGM1
PGM2
PGM3
PGM4
PGM1 PGM2 PGM3 PGM4
NOTE: For devices requiring more than 50mA, use a relay
(DSC RM-1) or UL-recognized parts only for this application.
NOTE: The RM-1 relay module cannot be installed outside of
the main panel enclosure.