Installation manual

32
[320]-[323] - Alarm Reporting Codes, Zones 1-64
The panel will transmit the Zone Alarm reporting code for
a zone when the zone goes into alarm. 24-hr type zones
will go into alarm whether the panel is armed or disarmed
and report to the central station. All other zone types will
only go into alarm if the panel is armed.
Reporting codes can be one or two digits and can use Hex
digits (A through F). The following is a description of the
different reporting codes that can be programmed and
when the events will be reported to the central station.
[324]-[327] - Alarm Restoral Reporting Codes,
Zones 1-64
If the Restoral on Bell Time-out option is selected the
panel will send the Zone Restoral Reporting Code for the
zone when the alarm output times out AND the zone is
secure. If the zone is not secured when the alarm output
times out the panel will send the restoral immediately after
the zone is secured.
If the Restoral on Bell Time-out option is not selected the
panel will immediately send the Zone Restoral reporting
code when the zone is secured or when the panel is dis-
armed, regardless if the alarm output is active or not.
NOTE:
24-hr type zones will report the restoral immedi-
ately after the zone is secured.
[328] - Miscellaneous Alarm Reporting Codes
Duress Alarm: this reporting code will be transmitted to the
monitoring station whenever a Duress code is used to per-
form any function on the system.
Opening After Alarm: this reporting code will be transmit-
ted to the monitoring station on opening if an alarm has
occurred during the previous armed period.
Recent Closing: a Recent Closing transmission will be sent
if an alarm occurs within 2 minutes of an exit time expira-
tion. The Recent Closing report will be sent for the first
alarm only.
Zone Expander Supervisory Alarm: this reporting code is
sent when the system loses communications with any zone
expander module (PC5108, PC5132, or keypad with on-
board zone).
Zone Expander Supervisory Restoral: this reporting code is
sent when the system regains communications with all
zone expander modules (PC5108, PC5132, or keypad with
on-board zone) that have been enrolled on the system.
Cross Zone / Police Code Alarm: When using Cross Zoning
(Section 018, Option 6 ON), this reporting code will be sent
when two Crossed Zones go into alarm during the cross
zone period.
When using Police Code (Section 018, Option 6 OFF), this
reporting code will be sent when any two zones go into
alarm.
If the
Double Hit option has been enabled, this reporting
code will be sent when two zone alarms occur on the same
zone and the Burglary Verified timer has not expired.
NOTE: Only one reporting code will be sent during
each armed to armed period when using Police Code.
Burglary Not Verified: this reporting code will be sent after
the Burglary Verified Timer expires after a zone alarm
occurs.
Alarm Cancelled: this reporting code will be sent if a valid
access code is entered during the Alarm Cancel window. If
a valid access code is entered during this window, then the
Alarm Cancelled event is logged and sent. When the cen-
tral station has acknowledged this reporting code/event, a
keypad ring-back will occur.
[329] - Priority Alarm and Restoral Reporting Codes
[F], [A], [P] Alarm: this reporting code will be sent if the [F]
[A] or [P] key is used to generate manual alarms.
Auxiliary Input Alarm: this reporting code will be sent
when PGM2 is being used for 2-wire smoke detectors and
the 2-wire smoke detector goes into alarm.
[F], [A], [P] Restoral: this reporting code will be sent after
the [F] [A] [P] alarm reporting code is sent.
Auxiliary Input Restoral: the panel will transmit this
reporting code when the 2-wire smoke detector has
restored after an alarm.
[330]-[333] - Tamper Reporting Codes, Zones 1-64
If the panel is programmed for Double EOL zones (see Sec-
tion 2.10 "Zone Wiring") the panel will report a
Zone
Tamper Alarm reporting code if an open condition is
present on a zone. A different reporting code can be pro-
grammed for each zone for identification.
[334]-[337] - Tamper Reporting Codes, Zones 1-64
The Zone Tamper Restoral reporting code will be transmit-
ted immediately when the Tamper condition is restored.
[338] - Miscellaneous Tamper Reporting Codes
General System Tamper: a General System Tamper
Reporting code will be transmitted when the tamper zone
on any module is violated.
General System Tamper Restoral: the General System
Tamper Restoral reporting code will be transmitted when
the tamper zone on the module is restored.
Keypad Lockout: the panel will transmit the Keypad
Lockout reporting code if the lockout is activated.
[339]-[340] - Closing (Arming) Reporting Codes,
Zones 1-32
The panel will transmit a Closing reporting code to indi-
cate a partition(s) is armed. A different reporting code can
be transmitted for each User Code, Partition Master Code
and System Master Code to identify who armed the parti-
tion(s).
[341] - Miscellaneous Closing (Arming) Reporting
Codes
Closing by Duress Code 33/34: a Closing by Duress code
Reporting code will be transmitted in addition to the
Duress reporting code if a partition(s) is armed using a
Duress Code.
Closing by Master or Supervisory Code: the panel will
transmit a Closing reporting code to indicate a partition(s)
is armed. A different reporting code can be transmitted for
each User Code, Supervisory Code and System Master
Code to identify who armed the partition(s).
Partial Closing: a Partial Closing reporting code will be
transmitted if a partition is armed with zones manually
bypassed. The code will also be transmitted if a partition
Auto-arms with zone(s) in violation.