Installation manual

Programming Worksheets
31
[012] Keypad Lockout Options (Section 5.21 “Keypad Lockout Options” on page 24)
NOTE:If Keypad Lockout is active, the panel cannot be disarmed with a keyswitch.
Default
000 I_______I_______I_______I Number of Invalid Codes Before Lockout (001-255 codes)
000 I_______I_______I_______I Lockout Duration (001-255 minutes)
[013] First System Option Code
Default Option ON Off Section Page #
OFF
I________I 1 Normally Closed Loops End-of-Line Resistors 2.8 5
OFF I________I 2 Double End-of-Line Resistors Single End-of-Line Resistors 2.8 5
ON*
I________I 3 Panel shows all troubles when armed Panel shows only Fire troubles when armed 3.4 8
OFF I________I 4 Tampers/Faults do not show as open Tampers/Faults show as open 3.4 8
OFF I________I 5 For future use
ON
I________I 6 Audible Exit Fault Enabled Audible Exit Fault Disabled 5.18 24
ON I________I 7 Event Buffer Follows Swinger Shutdown Event Buffer Logs Events Past shutdown 5.20 24
OFF I________I 8 Temporal Three Fire Signal Enabled Standard Pulsed Fire Signal 5.13 22
* Option 3 must be OFF if LCD keypads older than v2.0 are used.
[014] Second System Option Code
Default Option ON Off Section Page #
OFF I________I 1 Arm / Disarm Bell Squawk enabled Arm / Disarm Bell Squawk disabled 5.17 23
OFF I________I 2 Bell Squawk During Auto Arm No Bell Squawk During Auto Arm 5.18 24
OFF I________I 3 Bell Squawk On Exit Delay No Bell Squawk On Exit Delay 5.18 24
OFF
I________I 4 Bell Squawk On Entry Delay No Bell Squawk On Entry Delay 5.18 24
OFF I________I 5 Bell Squawk On Trouble No Bell Squawk On Trouble 3.4 8
ON I________I 6 Audible Exit with Urgency Silent Exit Delay 5.18 24
OFF
I________I 7 Exit Delay Termination Enabled Exit Delay Termination Disabled 5.18 24
OFF I________I 8 Fire Bell is Continuous Fire Bell Follows Bell Cut-off 5.13 22
[015] Third System Option Code
Default Option ON Off Section Page #
ON
I________I 1 Fire Keys Enabled Fire Keys Disabled 5.16 23
OFF I________I 2 Panic Keys Audible (Bell / Beeps) Panic Keys Silent 5.16 23
OFF
I________I 3 Quick Exit Enabled Quick Exit Disabled 3.4 8
ON* I________I 4 Quick Arming Enabled Quick Arming Dis. / Function keys Req. Code 3.4 8
OFF
I________I 5 Code Required For Bypassing No Code Required 3.4 8
OFF I________I 6 Master Code Not Changeable Master Code Changeable 5.1 15
ON I________I 7 TLM Enabled TLM Disabled 5.12 22
OFF
I________I 8 TLM Audible (Bell) When Armed TLM Trouble Beeps When Armed 5.12 22
* When using a PC5132 version 2.1 or older with WLS909 Wireless Keys, option [4] must be ON for the Arm button to work.
[016] Fourth System Option Code
Default Option ON Off Section Page #
ON
I________I 1 AC Trouble Displayed AC Trouble Not Displayed 3.4 8
OFF
I________I 2 Trouble Light Flashes if AC Fails Trouble Light Does Not Follow AC Status 3.4 8
OFF
I________I 3 Blank Keypad When Not Used Keypad Active Always 5.22 25
OFF
I________I 4 Code Required to Remove Kypd BlankingNo Code Required 5.22 25
ON
I________I 5 Keypad Backlighting is enabled Keypad Backlighting is disabled 5.23 25
OFF
I________I 6 Power Save Mode enabled Power Save Mode disabled 5.22 25
OFF
I________I 7 Bypass Status Displayed While Armed Bypass Status Not Displayed While Armed 5.17 23
OFF
I________I 8 Keypad Tampers enabled Keypad Tampers disabled 5.25 25