Installation manual
9
3.7 Access Level
Ref # [0011XX01YY10] where XX = module #, YY = door #
Access levels allow specific users to have access to areas of
the system at various times of the day. Each door can have
multiple access levels assigned to it. Each access level will
follow one date schedule.
There are 63 access levels for each door. To program access
levels, select an access level number (02-63) and then enter
the schedule number that the access level will follow.
Access cards programmed with access level 01 always have
access to all doors. Access levels 02 - 63 will be recognized
by the card reader during the windows provided by the
assigned date schedule.
Date Schedules 00 and 01
Access levels programmed with date schedule 01 will
always be recognized by the door. Access levels pro-
grammed with date schedule 00 will never be recognized by
the door. In order to disable an access level for a door,
assign the access level to Date Schedule 00.
By default all access levels are assigned to Date Schedule
00 (disabled).
3.8 Programming Access Cards
In order for an access card to function on the PC4820 the
card must first be programmed into the PC4010/4020. This
is done through user programming (enter [*][5][system
master code] or [supervisory code]). See your PC4010/4020
Instruction Manual for more information on programming
access codes and cards.