Installation manual

8
However, if the partition is disarmed while the door unlock
schedule is active, the door will unlock, and will remain
unlocked until the scheduled end time.
NOTE: If the door is assigned to more than one parti-
tion, the door will only lock once the last partition to be
armed has begun its exit delay.
The default date schedule is 00 (disabled).
Request To Exit (REX) Schedule
Ref # [0011XX01YY07] where XX = module #, YY =
door #
This schedule controls the Unlock on REX option. When
the schedule is active, tripping a Request To Exit device
will cause the door to unlock for the programmed Door
Unlock time (see section 3.5 “Door Times”). If the sched-
ule is not active, a Request To Exit will not cause the door
to unlock.
The default date schedule is 01.
Second Card Schedule
Ref # [0011XX01YY08] where XX = module #, YY =
door #
This schedule will determine when users with the Wait For
Privilege option enabled will require a Privileged user to
grant them access to the area. If the Second Card Schedule
is active, the following will occur:
The user with the Wait For Privilege card presents their
card first. The LED on the card reader will flash slowly for
10 seconds. If during this time a Privileged card is used,
the door will be unlocked. Only privileged cards are capa-
ble of allowing access to the system. If a non-privileged
card is used, the door will not be unlocked and the event
will be logged to the buffer. This feature is used for moni-
toring the access of users on the system.
The default date schedule is 00 (disabled).
Disarm Request Schedule
Ref # [0011XX01YY09] where XX = module #, YY =
door #
This schedule will program the times when the selected
partitions may be disarmed by a user presenting their
access card at the appropriate reader. Only partitions
which have the doors zone assigned to them, and which
are selected in the Arm/Disarm mask, will be affected.
To disarm the partition(s), the user must present their
access card and open the door. The partition(s) will be dis-
armed if the Disarm Request schedule is active. If the user
presenting their card is outside of the Disarm Request
schedule time window, the door will be unlocked but the
partition(s) will not be disarmed when the door is opened.
The user must then enter their access code at a keypad to
disarm the partition(s).
NOTE: To disarm a partition or enter a partition which is
armed, the user must be assigned to the partition, and
the user’s disarm attribute must be enabled in access
code and card programming. See your PC4010/4020
Instruction Manual for information on programming
access codes and cards.
The default date schedule is 00 (disabled).
Code Schedule
Ref # [0011XX01YY11] where XX = module #, YY =
door #
When this schedule is active, the door will not unlock until
the card is presented AND a valid access code is entered
on the keypad. When the schedule is inactive, the door
will unlock when an access card is presented.
If Schedule [00] is programmed into this section, the door
will be unlocked by an access card only when the parti-
tion(s) the door is assigned to are disarmed. When the par-
titions are armed, an access code will also be required.
NOTE: The Code Required option must be enabled in
order for this feature to work.
The default date schedule is 01.
Forced Open Schedule
Ref # [0011XX01YY12] where XX = module #, YY =
door #
When this schedule is active and a door is opened without
tripping a REX device, a Door Forced Open event will be
logged to the event buffer and transmitted to the central
station. When the schedule is inactive and a door is forced
open, the event will be logged, but not transmitted.
NOTE: In order for this option to work, the door must
be assigned a zone and that zone must be assigned to
one or more partitions.
The default date schedule is 00 (disabled).
Forced Open Bell Schedule
Ref # [0011XX01YY13] where XX = module #, YY =
door #
When this schedule is active and a door is opened without
tripping a REX device, the partition(s) the door is assigned
to will go into alarm. The alarm will be on until the bell
cut-off time expires, or until an access code is entered to
silence the alarm.
NOTE: In order for this option to work, the door must
be assigned a zone and that zone must be assigned to
one or more partitions.
The default date schedule is 00 (disabled).
Open Too Long Schedule
Ref # [0011XX01YY14] where XX = module #, YY =
door #
When the schedule is active and the assigned door is left
open past the Door Open time, an Open Too Long event
will be logged to the event buffer and transmitted. When
the schedule is inactive and the door is left open past the
Door Open time, the event will be logged but not transmit-
ted. The default Door Open time is set at 30 seconds but
can be changed (see Section 3.4 “Door Times”).
NOTE: In order for this option to work, the door must
be assigned a zone and that zone must be assigned to
one or more partitions.
The default date schedule is 00 (disabled).
Open Too Long Bell Schedule
Ref # [0011XX01YY15] where XX = module #, YY =
door #
When the schedule is active and the assigned door is left
open past the Door Open time, the partition(s) the door is
assigned to will go into alarm. The alarm will remain on
until the bell cut-off time expires, or until an access code is
entered to silence the alarm. The Door Open time is set at
30 seconds by default, but can be changed (see Section 3.4
“Door Times”).
NOTE: In order for this option to work, the door must
be assigned a zone and that zone must be assigned to
one or more partitions.
The default date schedule is 00 (disabled).